• Max Discharging Current: 80 (max. 20A pro Einheit- 80A bei 4 Einheiten)
• Feeding grid power calibration R: 100
• Feeding grid power calibration S: 100
• Feeding grid power calibration T: 100
4.2 Pylontech/Neoom
ACHTUNG: Lithiumtechnologien erfordert unbedingt ein externes BMS
• Bulk charging voltage: 54,5
• Floating charging voltage: 54
• Battery cut-off discharging voltage when grid is available: 46
• Battery re-discharging voltage when Grid is available: 49,5
• Battery cut-off discharging voltage when grid is unavailable: 45,5
• Battery re-discharging voltage when Grid is unavailable: 48,5
• Max Charging Current: 120
• Max AC Charging Current: 120
• Max Discharging Current: 120
• Feeding grid power calibration R: 100
• Feeding grid power calibration S: 100
• Feeding grid power calibration T: 100
4.3 Blei
ACHTUNG: nur in belüfteten Räumen
• Bulk charging voltage: 56
• Floating charging voltage: 55,5
• Battery cut-off discharging voltage when grid is available: 46
• Battery re-discharging voltage when Grid is available: 53
• Battery cut-off discharging voltage when grid is unavailable: 45
• Battery re-discharging voltage when Grid is unavailable: 50
• Max Charging Current: 150
• Max AC Charging Current: 60
• Max Discharging Current: 150
• Feeding grid power calibration R: 100
• Feeding grid power calibration S: 100
• Feeding grid power calibration T: 100
8