Multifunction instrument without
communication gates and with inputs via CT
7. GENERAL FATURES
(continued)
Cover marking:
Marking by indelible tampography
1
4
6
7
9
3
I1
I2
I3
+ Aux
L1
L2
L3
N
2
5
8
11
20
21
Front marking:
Adhesive film
Display:
- Type: backlit LCD
- Resolution: automatic adjustment of the display resolution for the
decimal figures and the engineering units as a function of the
transformation ratio of the external CT
kCT= external CTs ratio
(e.g. 800A / 5A, kCT = 160).
- Update time: 1 sec.
Display of the value and programming:
- By means of the front keypad, 4 pushbuttons
).
manual
- Access protected by identification code (
Auxiliary supply
(terminals 20 and 21):
- Rated value Uaux ac: 230Vac
- Frequency: 50....60Hz +/-10%
- Self consumption: ≤ 2,5VA
@230 Vac
"
Operating room temperatures:
- Min. = - 5 °C Max. = + 55 °C.
Room storage temperatures:
- Min. = - 25 °C Max. = + 70 °C.
Maximum dissipated thermal power for the thermal
dimensioning of the panels:
Technical data sheet: IDP000206EN_01
(kCT
).
1
(please refer to the user
)
predefined code 1000
+/-15%
"
"
≤ 5W
Codes: MFD45A00
7. GENERAL FATURES
Measurements and precision in conformity with
- Current: cl.0,5
- Voltage: cl.0,5
- Frequency: ± 0,1 Hz
- Instantaneous total active power, phase, average value and max.
average value : cl.1
- Instantaneous total reactive power, phase, average value and max.
average value : cl.2
- Instantaneous total apparent power, phase, average value and
max. average value : cl.1
- Power Factor : cl.1
- Total and partial active energy, positive and negative: : cl.1
- Total and partial reactive energy, positive and negative : cl.2
- THD cl.2
Average current - Average power:
- Measurement: current-apparent, reactive, active power
- Calculation: moving average, on the selected period
- Average time: 5/8/10/15/20/30/60min.
- Average time: same for all the magnitudes
Hour meter:
- Counting of operating hours and minutes
- Start count: can be selected, presence of voltage or power
- Voltage: Phase voltage > 20V
- Three phase rated active power
- Programmable value : 0...50% Pn
Pn =
three phase rated active power
Unx Current In x √3
Un 400V
In 5A
Pn= 400V x 5A x √3 = 3464W
Diagnostic, Phase sequence correction:
In the software there is a diagnostic and correction algorithm of the
voltmetric and amperometric connection sequence.
The function can be activated on request and password protected: it
can display and modify the wiring sequence with the following
limitations:
1) The neutral conductor
positioned
(terminal 11)
2) There are no conductor crossings between different CT
(
e.g. on phase 1 of the device there is a cable from CT 1 and on the other a cable
from CT 2)
3) The power factor must be between 0.9cap and 0.7ind for each
phase.
See www.imeitaly.com "TECHNICAL SUPPORT".
Protection class:
- Terminal protection index against solid bodies and liquids:
IP 20 (IEC/EN 60529).
- Housing protection index against solid bodies and liquids:
IP 54 (IEC/EN 60529).
Room:
Mechanical M1 – Electric E2
Housing material:
Packaged volume:
Updated: -
(resettable meter)
=
Three-phase rated voltage
must be correctly
(in the 4-wire connections)
Self-extinguishing polycarbonate
.
0,70 dm
3
Created: 28/01/2019
EN/IEC 61557-12
3 / 4