®
GENERAL INFORMATION
The No. 4275EX Passive Infrared motion detector/Remote Point
Module is designed for use only with the VISTA and Advantage
series of multiplex security systems. It is a tamper-protected
wall-mounted
unit
offering
either
range/curtain (narrow) area protection (2 separate easy-to-install
mirrors come supplied). Best coverage will be obtained if
mounting is selected such that the likely direction of intruder
motion is across the pattern.
SPECIFICATIONS
Detection Method: Passive Infrared
Coverage: 35 ft (10.6m) x 45 ft (13.7m), 84°
(wide angle mirror)
70 ft (21.3m) x 10 ft (3m)
(long range curtain mirror)
Detection Zones: 9 zones (6 long, 3 short)
(wide angle mirror). 1 zone, 7 tiers
(long range curtain mirror)
Pulse Count: Installer option
Detectable Walk Rate: 0.5 - 5 ft sec (0.15 - 1.5m/Sec)
Mounting Height: 7 ft nominal (2.1m), wall mounting
Indicator: Red LED (Switch selectable)
Tamper Protection: Integral switch that signals on the
same multiplex polling loop as
alarm signals
Input Voltage: 8-11V peak to peak at polling loop
terminals
Current Drain: Less than 1mA (LED inactive)
6mA approx (LED active)
Standby Capability: Power source should be capable
of at least 4 hours of battery standby
Operating Temperature: 0° to 50°C (+32° to +122°F)
Operating Humidity: Up to 95% RH (max.), noncondensing
Dimensions: 3''W x 3 11 / 16 ''H x l- 1 / 2 ''D
(76mm x 94mm x 38mm)
INSTALLATION HINTS
Do not install where the detector is exposed to direct sunlight or
directly above strong sources of heat.
Make sure the detection area does not have obstructions
(curtains, screens, large pieces of furniture, plants, etc.) which
may block the pattern of coverage.
Avoid locating a unit in areas which contain objects likely to
produce a rapid change in temperature, such as central heating,
radiators or ducts (or heaters of any kind), air conditioners, open
flame, etc.
Install the detector at a height of approximately 7 feet (2.1m)
from floor. Do not mount on an unstable surface.
IMPORTANT: Avoid running alarm wiring close to telephone line
and alarm sounder wiring.
PROTECTION PATTERNS
Note: The protection patterns shown for wide angle and long
range mirrors can be modified to suit the needs of a particular
area by selective use of the masking strips supplied.
TOP VIEW
20'
[at 7 ft. (2.1m) Mounting Height]
(6.0m)
10'
(3.0m)
0
10'
(3.0m)
20'
(6.0m)
10'
20'
30' 35'
(3.0m) (6.0m) (9.0m) (10.5m)
SIDE VIEW
7'
(2.1m)
0
3'
10'
35'
(0.9m)
(3.0m)
(10.5m)
NOTE:
NOTE:
DEAD ZONE
THE DETECTION PATTERN OF THE DETECTOR
THE DETECTION PETTERN OF THE DETECTOR IN
APPROX
IN THE INVERTED POSITION IS IDENTICAL TO
THE INVERTED POSITION IS IDENTICAL TO THE
THE PATTERN IN THE NORMAL MOUNTING
PATTERN IN THE NORMAL MOUNTING POSITION
EXCEPT THAT THE BEAMS TILT UPWARD.
Detection Area (Long Range Mirror)
TOP VIEW [at 7 ft. (2.1m) Mounting Height]
CORRIDOR / CURTAIN PATTERN
7'
(2.1m)
2.6'
(0.8m)
INSTALLATION
A. Changing from Wide Angle to Long Range Coverage:
1. Remove front cover by inserting a screwdriver blade in the
groove between cover and base (see Diagram 1), rotating
blade to override snap fit, and then lifting cover off.
2. Spread either or both plastic prongs holding the wide angle
(35 ft/10.6m) mirror and remove the mirror (Diagram 2).
3. Insert one side of the narrow angle (70 ft/21.3m) mirror
under a prong and snap the other side under the other
prong. Make sure that the mirror sides are squarely in
their corner rests and are held securely under the prongs.
Note: Mirror surface should be free of dirt, foreign matter
and fingerprints. Use a clean dry soft cloth to wipe mirror
surfaces, if required.
B. Normal Wall Mounting:
Note: For ANPI approved installations, you cannot use
the mounting plate.
INSTALLATION INSTRUCTIONS
1. Remove the front cover as shown in Diagram 1.
2. Mount the wall plate to a firm vertical surface (flat on wall
or in corner). Position the plate so that field wiring is
centered in the rectangular slot at the top of the plate.
See Diagram 3 and Detail A.
wide-angle
or
long
3. Feed wiring through top access hole of detector (past foam
draft protector) but do not connect to terminal block yet.
4. Attach unit to wall plate by engaging all four hooks on the
plate into slots on the rear of the base and by pressing
downward (see Diagram 3). (Puncture the label on the
back of the base before installing.)
Note 1: The PIR is locked to the wall plate by a spring tab that
engages a square opening in the housing base (see Diagram 3).
The PIR can only be removed by cover removal, depression of
the tab from the inside with a small-blade screwdriver and then
sliding the PIR upward.
Note 2: If the PIR is to be mounted on a flat wall without its
mounting plate, install a 3mm screw into the wall at the planned
center (side-to-side) of the PIR, 1 inch (25mm) below the
planned top of the PIR. Leave 1/8" (3mm) clearance between the
screw head and the wall. Hook the PIR on the wall screw,
puncturing the label, and insert two screws into the mounting
areas on both sides of the mirror.
C. Inverted Mounting:
If small pets have access to the area protected by the detector,
this section pertains.
• The detector may be installed approximately 3 ft to 3- 1 / 2 ft (1m)
from the floor, provided furniture or other objects do not
obscure the pattern of protection.
• The detector and wall plate must be mounted inverted (the PIR
window at the top) with the wall p!ate tilted forward
(downward). Two self-adhesive rubber spacers have been
provided to aid in tilting the wall plate.
• It must be noted that although this procedure adjusts the PIR
zones so that small animals will not be detected, a crawling
intruder will ALSO go undetected.
1. The spacers are to be used with the wall plate only when
the wide angle mirror is in use.
Mounting flat on a wall:
Assemble the two spacers, one above the other, and affix the
combination to the rear of the plate, directly in line with the
single mounting hole located at the end of the plate opposite
to the wire entry access cutout.
Corner mounting:
Affix one of the spaces to the rear surface of each of the two
corner mount tabs on the wall plate, on the end opposite to
the wire entry access cutout.
2. Follow "Normal Mounting" steps 2, 3 and 4 described
previously, but orient the wall plate so that the wire entry
access cutout in the wall plate is positioned at the bottom.
3. When the detector is mounted in an inverted position, that
portion of the detector mirror which normally provides a
downward beam of protection will now provide a beam that
points upward. This will apply to both mirrors (long range
and wide angle). If possible, install the detector so that this
now upward-pointing beam is not directed at ceiling areas
that include heating or air conditioning ducts and vents or
lighting fixtures. If these IR sources cannot be avoided, the
upward-pointing segments of each mirror should be
masked to avoid the possibility of false alarms, as indicated
in the diagrams herein.
a. Remove the mirror from the detector, referring to a
previous page for information on mirror removal.
b. Mask the appropriate portion of each mirror as shown
in the diagrams below, using masking strips supplied.
WIDE AREA
Be sure to cover only the area shown.
PATTERN
c. Replace the mirror, making sure it is securely in
position before installing the cover.
WIDE ANGLE MIRROR
D. Optional Ceiling Mounting:
The versatility of this passive infrared motion detector permits
optional ceiling mounting, using the Long-Range ("Curtain")
mirror. This will provide a 15-20 ft (4.5-6m) forward-looking
"curtain" pattern as illustrated in Diagram 4.
The mounting procedure is the same as that for "Normal Wall
Mounting" except that the unit is ceiling mounted with the
window facing toward the detection area.
E. Mirror Masking:
The masking strips that have been supplied are designed for
application in one or more mirror segments to produce a
protection pattern that suits the particular requirements of the
protected area.
sensitive adhesive strip(s) and apply over the desired mirror
3.5'
segment(s). Individual masking strips have been provided for
(1m)
10'
each of the mirror segments on the wide-angle mirror. Two strips
(3m)
3.5'
(1m)
are provided for masking multiple segments of a long-range
(curtain) mirror. Each mirror segment that is masked results in
SIDE
the elimination of one zone of protection from the coverage
VIEW
pattern. By masking appropriate segments of a mirror, you can
70'
adjust the coverage to suit the area to be protected, or to
(21.3m)
eliminate
coverage
environmental disturbances that might reduce the PIR's stability
(a heater or other heat-producing object, for example).
Some examples of protection patterns that have been modified
by use of the masking strips have been provided. Also included
are application suggestions.
Note: The 9-segment wide-angle mirror is used in all examples
shown.
WIRING CONNECTIONS
Bring both polling loop wires through the wire access hole near
the terminal block and connect to screw terminals (see Diagram
5). OBSERVE POLARITY!
Pulse Count Option:
Each detector includes Pulse Count circuitry that provides
stability in adverse environments to minimize false alarms This
circuitry is active when the switch #7 on the circuit board is set
PASSIVE INFRARED MOTION DETECTOR
LONG RANGE MIRROR
SHOWN IN
INVERTED
POSITION
MASK THIS PORTION
OF THE MIRROR WITH
MASKING STRIPS
Simply peel off the appropriate pressure-
from
areas
where
you
anticipate
N2986-1ENV4 8/99 PART OF N2986-1V4
to the PULSE COUNT position (see Diagram 5). The detector will
then normally signal an alarm within 3 to 4 steps, since the
processing logic requires more complex motion than just a
momentary event.
For long-range applications where the detector is used to protect
narrow corridors, or where single protective zones are directed
through doorways or room openings, the pulse count option must
be disabled (see Diagram 5) to provide an instant alarm
response.
SELECTING AN ID NUMBER
Make all identification number selections by arranging the
switches on the circuit board. The ID number is equal to the sum
of the switch values in the "OFF" position. Each switch has a
different value and should be set according to Table 1.
TEST PROCEDURES
IMPORTANT: Two-minute warm-up is required after applying
power. Testing should be conducted with the protected area
cleared of all people. Disarm the protective system's control
during the test procedure to prevent reporting of unwanted
alarms.
Walk-Test:
Place PULSE COUNT SW #7 to instant response, left, position.
Place WALK-TEST SWITCH #8 to walk-test, left, position (see
Diagram 5). Replace front cover and walk through protective
zones, observing that the detector's LED lights whenever motion
is detected.
The LED will only be active and should only be used during walk-
test procedures. When walk-test is completed the walk-test
switch #8 must be set to the right position (DISABLED).
The panel may be able to control the walk-test function remotely. In
order for panel to do this, walk-test switch #8 must be set to the
right position (DISABLED).
Notes: In the instant response mode, the LED stays lit for
approximately 1 to 2 seconds after detecting motion. In
the event that switch #7 is placed in the pulse count, right,
position, the LED will illuminate for up to approximately 4
seconds when the detector verifies intrusion.
Make certain to test the unit in the mode it will be used.
For example, if pulse count is to be used, then the PIR
should be walk-tested with switch 7 set to pulse count,
right, position.
The absolute range of all Passive IR units is subject to variation
because of different types of clothing, backgrounds and ambient
temperature. For this reason, ensure that the most likely intruder
routes are well within the PlR's protective zones and that walk-
testing is carried out along the routes.
MAINTAINING PROPER OPERATION
In order to maintain the detector in proper working condition, it is
important that the following be observed by the user.
1. Power should be provided at all times. The unit's
control/communicator should have standby power
available for at least 4 hours of operation during
emergencies.
2. Units should never be re-aimed or relocated without the
advice or assistance of the alarm service company.
3. The physical surroundings of the protected area
should not be changed. If furniture or stock is moved, or
air conditioning or additional heating is installed, the
system may have to be readjusted by the alarm service
company.
4. Walk-tests should be conducted frequently (at least
weekly) to confirm continued proper coverage by each
detector.
TO THE INSTALLER
Regular maintenance and inspection (at least annually) by the
installer and frequent testing by the user are vital to continuous
satisfactory operation of any alarm system.
The installer should assume the responsibility of developing and
offering a regular maintenance program to the user, as well as
acquainting the user with the proper operation and limitations of
the alarm system and its component parts. Recommendations
must be included for a specific program of frequent testing (at
least weekly) to ensure the system's operation at all times.
TROUBLESHOOTING
PROBLEM
PROBABLE CAUSE
Intermittent Alarm
Rapid
temperature
change. Check for electric
or
gas
heaters,
open
flames, electric arcs, etc.
Drafts causing drapes, light
fixtures, display materials
to move.
PIR
does
not
DC voltage supplied to
appear
to
be
detector is inadequate,
operating
intermittent,
or
polarity
reversed.
LED inoperative
SW #8 not set to walk-test.
LED malfunction. Check
for broken/shorted leads.
Repositioned furniture or
Detection Area
equipment in the protected
Changes
area.
Mounting
surface
is
unstable. A few degrees of
vertical shift can change
range substantially.
Trouble Display
Improper ID address code.
4275EX
REMEDY
Locate
source
and
reposition detector.
Eliminate
source
of
motion.
Assure that proper polarity
and adequate voltage is
supplied and that wiring is
intact (no opens or shorts)
and connection secure.
Check for presence of 8-11
VPP at terminals of unit. If
too low, polling loop run to
control may be excessive
for the wire gauge used.
Increase wire gauge to add
No. 4197 Polling Loop
Extender
module
to
location in the loop where
voltage boost is necessary
and connect it to a power
source.
Alternatively, the
detector can be tested
using a 9-volt DC source
(such as a 9-volt battery or
a 9-volt power supply).
Set SW #8 to WT position.
Return unit for service.
Caution customer about
layout
changes.
Resposition detector.
Mount on secure surface.
Set switch numbers 1-6 to
proper code.