Herunterladen Inhalt Inhalt Diese Seite drucken

LEGRAND WHAD HE 3 kVA Bedienungsanleitung Seite 32

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 51
8. Technical data
Electrical output characteristics (battery mode)
Total harmonic distortion of output voltage
Total harmonic distortion of output voltage
Batteries and Battery Charger Characteristics
Battery charger rated recharge current
Recharge time up to 90% of the total charge
Features
32
Rated output voltage
Rated output frequency
Max output current
on linear rated load
on non-linear rated load
Overload admitted
Rated battery voltage
No. of batteries
Battery type
Type of battery charger
Recharge curve
Average battery life
Signals and alarms
Communication ports
Software
Protective devices
3 101 66
3 101 67
230 V ± 1%
50 / 60 Hz ± 1%
13 A
17,3 A
115% for 2 minutes
135% 30 second
3 101 66
3 101 67
108 Vdc
144 Vdc
9
12
Maintenance-free sealed lead-acid (VRLA) 12Vdc – 9Ah
High performance PWM
Smart Charge, advanced three-stage cycle
2,5 A max
3-6 years depending on use and operating temperature
3 101 66
3 101 67
Multicolour status indicator, acoustic notification
1 RS232 port, 1 logic contact port, 1 SNMP slot for optional
interfaces
Free "UPS Communicator" software available
for the following functions:
- display of all operating and diagnostic data in case of problems;
- special function setup;
- automatic shutdown of all computers powered by the UPS
(if connected to the TCP/IP network).
A free copy of the free software can be downloaded from
http://www.ups.legrand.com
Electronics against overloads, short-circuit and excessive
battery discharge
Block of functions due to the end of autonomy
In-rush limiter on start up
EPO contact
Integrated backfeed protection
3 101 68
3 101 69
21,7 A
26 A
< 0,5%
< 3%
3 101 68
3 101 69
180 Vdc
216 Vdc
15
8 h
3 101 68
3 101 69
18

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Whad he 4 kvaWhad he 5 kvaWhad he 6 kva

Inhaltsverzeichnis