Herunterladen Diese Seite drucken

Technical Data - Niko 340-00021 Gebrauchsanleitung

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 3
340-00021 / 340-00022 / 340-00023
Read the entire manual before installing and activating the system.
1. DESCRIPTION
The power supply unit is suitable for supplying LEDs and is intended for DIN rail mounting. The output voltage
of 24V DC is stable within a narrow tolerance range, produces very little ripple and is highly efficient. The output
voltage range is adjustable (see technical data).
The total connected load may not exceed 25W (340-00021), 50W (340-00022) or 100W (340-00023). A green
LED on the unit indicates that the power supply has been correctly connected and that 24V DC is available.
The unit has a switch-on current limiter. It is protected against overload, overvoltage, overheating and short circuit.
De unit complies with safety standards (EN60950-1) and EMC standards (EN55011; EN55022 Class B; EN55024;
EN61000-3-2, EN61000-3-3).
2. FITTING AND CONNECTIONS
The DIN rail power supply unit has two outputs to which LEDs can be connected.
The unit has a width of 4.5E (25W and 50W version) or 6E (100W version) and can be installed in a DIN rail box.
The load must be connected between the '+' and '-' terminals (see fig. 1).
Fig. 1a circuit diagram 25W (340-00021) and 50W (340-00022) DIN rail LED power supply;
Fig. 1b circuit diagram 100W (340-00023) DIN rail LED power supply.
When all the connections have been correctly made and the power supply is switched on, the green LED lights up.
Installation advice:
- If you install several modules next to one another, provide a gap between them of at least 1 module using
modified blanking plates.
- The unit should ideally be installed at the bottom of the distribution box.
- Check the temperature. If the temperature in the distribution box becomes too high (max. 35°C), provide
additional ventilation to guarantee an optimum life span. Ensure the heat can be dissipated effectively from
the top of the board. If necessary, fit a fan.
- In case of higher temperatures, use the following output graphs (fig. 2a, 2b and 2c).
Fig. 2a Output graph for 340-00021
Fig. 2b Output graph for 340-00022
Fig. 2c Output graph for 340-00023

3. TECHNICAL DATA

340-00021: DIN rail LED 25W power supply
General:
- Installation: ................................................ DIN rail (4.5E)
- Dimensions: .............................................. W78 x H93 x D56 mm
- Weight: ..................................................... ±270g
- Efficiency: ................................................. 83%
- Operating temperature: .............................. -20°C – +60°C (see output graph in fig. 2a)
- Ambient temperature: ................................ T a 35°C
- Storage temperature & humidity: ................ -40°C - +85°C; 10 – 95% RH
- Protection against short circuit, overvoltage and overload (self-resetting).
- For use in an environment with non-condensing air humidity (20% - 90% RH)
Input:
- Input terminals (1 pair): .............................. 2 x 1.5mm
- Supply voltage: .......................................... 100 ~ 240V~; frequency 50 ~ 60Hz
- Input current:............................................. 0.6A/230V~; 1.1A/115V~
- Switch-on current: ..................................... cold start: 40A/230V~; 30A/115V~
Outputs:
- Output terminals (2 pairs): .......................... 2 x 1.5mm
- Adjustable output voltage range: ................. 21.6V DC – 26.4V DC
- Nominal current/output: ............................. 1.04A / 25W
- Voltage stability:......................................... ± 1%
- Ripple and noise: ....................................... 150mVp-p
- Hold-up time: ............................................ 50ms/230V~; 18ms/115V~
- SELV
340-00022: DIN rail LED 50W power supply
General:
- Installation: ................................................ DIN rail (4.5E)
- Dimensions: .............................................. W78 x H93 x D56 mm
- Weight: ..................................................... ±300g
- Efficiency: ................................................. 86%
- Operating temperature: .............................. -20°C – +60°C (see output graph in fig. 2a)
- Ambient temperature: ................................ Ta 35°C
- Storage temperature & humidity: ................ -40°C - +85°C; 10 – 95% RH
- Protection against short circuit, overvoltage and overload (self-resetting).
- For use in an environment with non-condensing air humidity (20% - 90% RH)
nv Niko sa
or 1 x 2.5mm
2
2
or 1 x 2.5mm
2
2
Industriepark West 40, BE-9100 Sint-Niklaas, Belgium — tel. +32 3 778 90 00 — fax +32 3 777 71 20 — e-mail: support@Niko.eu — www.niko.eu
Input:
- Input terminals (1 pair): .............................. 2 x 1.5mm
- Supply voltage: .......................................... 100 ~ 240V~; frequency 50 ~ 60Hz
- Input current:............................................. 1A/230V~; 1.8A/115V~
- Switch-on current: cold start:...................... 40A/230V~; 30A/115V~
Outputs:
- Output terminals (2 pairs): .......................... 2 x 1.5mm
- Adjustable output voltage range: ................. 21.6V DC – 26.4V DC
- Nominal current/output: ............................. 2.08A / 50W
- Voltage stability:......................................... ± 1%
- Ripple and noise: ....................................... 150mVp-p
- Hold-up time: ............................................ 50ms/230V~; 18ms/115V~
- SELV
340-00023: DIN rail LED 100W power supply
General:
- Installation: ................................................ DIN rail (6E)
- Dimensions: .............................................. W100 x H93 x D56 mm
- Weight: ..................................................... ±350g
- Efficiency: ................................................. 89%
- Operating temperature: .............................. -20°C – +60°C (see output graph in fig. 2a)
- Ambient temperature: ................................ Ta 35°C
- Storage temperature & humidity: ................ -40°C - +85°C; 10 – 95% RH
- Protection against short circuit, overvoltage, overheating and overload (self-resetting).
- For use in an environment with non-condensing air humidity (20% - 90% RH)
Input:
- Input terminals (1 pair): .............................. 2 x 1.5mm
- Supply voltage: .......................................... 100 ~ 240V~; frequency 50 ~ 60Hz
- Input current:............................................. 1.6A/230V~; 3A/115V~
- Switch-on current: cold start:...................... 45A/230V~; 30A/115V~
Outputs:
- Output terminals (2 pairs): .......................... 2 x 1.5mm
- Adjustable output voltage range: ................. 24V DC – 29V DC
- Nominal current/output: ............................. 4.2A/ 100W
- Voltage stability:......................................... ± 1%
- Ripple and noise: ....................................... 150mVp-p
- Hold-up time: ............................................ 80ms/230V~; 80ms/115V~
- SELV
4. WARNINGS REGARDING INSTALLATION
The installation of products that will permanently be part of the electrical installation
and which include dangerous voltages, shall be carried out by a qualified installer and
in accordance with the applicable regulations. This user manual must be presented to
the user. It should be included in the electrical installation file and it should be passed
on to any new owners. Additional copies are available on the Niko website or via Niko
customer services.
5.
CE-MARKING
This product complies with all of the relevant European guidelines and regulations. For
radio equipment Niko nv declares that the radio equipment in this manual conforms with
the 2014/53/EU directive. If applicable, the full text of the EU Declaration of Conformity
can be found on www.niko.eu.
6. ENVIRONMENT
This product and/or the batteries provided cannot be deposited in non-recyclable waste.
Take your discarded product to a recognised collection point. Just like producers and
importers, you too play an important role in the promotion of sorting, recycling and reuse
of discarded electrical and electronic equipment. To finance the rubbish collection and
waste treatment, the government levies recycling charges in certain cases (included in
the price of this product).
or 1 x 2.5mm
2
2
or 1 x 2.5mm
2
2
or 1 x 2.5mm
2
2
2
or 1 x 2.5mm
2
PM340-00021R19295