INPUT REGISTERS
Relative humidity alert
12
flag
Relative humidity range
13
limit flag
Humidity, temperature
14
sensor fault
15
Dew point level
16—40
41
Ambient light intensity
42
Active / Standby
43
Ambient light sensor fault
HOLDING REGISTERS
1
Device slave address
2
Modbus baud rate
3
Modbus parity
4
Device type
5
HW version
6
FW version
7
8
Modbus safety timeout
Modbus network resistor
9
termination (NBT)
10
Modbus registers reset
Minimum temperature
11
range
Maximum temperature
12
range
Minimum temperature
13
alert
Maximum temperature
14
alert
15—18
Minimum relative
19
humidity range
Maximum relative
20
humidity range
Minimum relative
21
humidity alert
Maximum relative
22
humidity alert
23—34
35
Active mode light level
36
Standby mode light level
37—40
41
Output 1 type (T)
42
Output 1 overwrite (T)
Output 1 overwrite value
43
(T)
MIW-RSTHX-2-DE-000 - 11 / 09 / 19
KOMBINIERTER RAUMTRANSMITTER FÜR T
UND RH
Data type
Description
Flag indicates that measured Relative humidity
is outside set alert values. Set to '1' when the
unsigned int
measured value is outside the Relative humidity
alert values defined by holding registers 21 and
22
Flag indicates that measured Relative humidity
is outside set range limit values. Set to '1' when
unsigned int
the measured Relative humidity is outside limit
range values defined by holding registers 19 and
20
Flag that shows if the communication with
unsigned int
temperature & humidity sensor is lost
signed int
Calculated dew point
Reserved, return 0
unsigned int
Measured ambient light intensity
Active or Standby indication according the
Active / Standby light level defined by holding
unsigned int
registers 35 and 36. If the measured light level
is between the two levels the indication is 0 (Low
light intensity)
Flag that shows if the communication with the
unsigned int
ambient light sensor is lost
Data type
Description
unsigned int
Modbus device address
unsigned int
Modbus communication baud rate
unsigned int
Parity check mode
Device type. Read only
unsigned int
Hardware version of the device. Read only
unsigned int
Firmware version of the device. Read only
Reserved, returns 0
Timeout setting for no Modbus communication. After
unsigned int
time runs out, output(s) is set to
Sets device as end device of the line / or not by connecting
unsigned int
NBT
Resets Modbus Holding registers to default values. When
unsigned int
finished this register is automatically reset to '0'
Minimum value of temperature range, cannot be set
unsigned int
higher than maximum temperature range minus 5°C
Maximum value of temperature range, cannot be set less
unsigned int
than minimum temperature range plus 5°C
unsigned int
Minimum temperature alarm value
unsigned int
Maximum temperature alarm value
Reserved, return 0
Minimum value of relative humidity range, cannot be set
unsigned int
higher than maximum relative humidity range minus 5%
Maximum value of relative humidity range, cannot be set
unsigned int
less than minimum relative humidity range plus 5%
unsigned int
Minimum relative humidity alarm value
unsigned int
Maximum relative humidity alarm value
Reserved, return 0
The ambient light level above which 'Active' is indicated
unsigned int
in input register 42
The ambient light level below which 'Standby' is indicated
unsigned int
in input register 42
Reserved, return 0
unsigned int
Select analogue / modulating output 1 type
unsigned int
Enables the direct control over the temperature output
Overwrite value for output 1. Active only if Holding
unsigned int
register 42 is set to 1
zurück zum Inhaltsverzeichnis
Data
0.
www.sentera.eu
Values
0 = Relative humidity
0—1
1 = Relative humidity
measurement too low/high
0 = Relative humidity range OK
0—1
1 = Relative humidity range too
0—1
-700—700
0—32.000
0 = Low light intensity
0—2
0—1
Data
Values
1—247
default: 1
0—6
default: 2
0— 2
default: 1
RSTHG-2 = 1.604
RSTHF-2 = 1.605
XXXX
0x0200 = HW version 2.0
XXXX
0x0200 = FW version 2.0
0—60
0 = no timeout
default: 0
60 = 60 minutes
0—1
0 = NBT disconnected
default: 0
0—1
default: 0
0—Max-50
default: 0
Min+50—500
default: 500
Min. temperature range
—Max. temperature alarm
default: 0
Min. temperature alarm
—Max. temperature range
default: 500
0—Max-50
default: 0
Min+50—1.000
default: 1.000
Min. relative humidity
range—Max. relative
humidity alarm
default: 0
Min. relative humidity
alarm —Max. relative
humidity range
default: 1.000
0—32.000
default: 100
0—32.000
default: 10
1—3
default: 1
0—1
default: 0
0—1.000
default: 0
measurement OK
low/high
0 = No
1 = Yes
200 = 20,0°C
1.000 = 1.000 lux
1 = Active
2 = Standby
0 = No
1 = Yes
0 = 4.800
1 = 9.600
2 = 19.200
3 = 38.400
4 = 57.600
5 = 115.200
6 = 230.400
0 = 8N1
1 = 8E1
2 = 8O1
1 = NBT connected
0 = Idle
1 = Reset Modbus
Registers
100 = 10,0°C
500 = 50,0°C
500 = 50,0°C
500 = 50,0°C
200 = 20,0 % rH
850 = 85 % rH
200 = 20,0 % rH
850 = 85 % rH
100 = 100 lux
10 = 10 lux
1 = 0—10 VDC
2 = 0—20 mA
3 = PWM
0 = Disabled
1 = Enabled
0 = 0 %
1.000 = 100 %
10 - 11