INSTRUCTION
EN
E-BACNET2-V
i
Read this instruction before installation
and wiring of the product
EXOline to BACnet converter
E-BACNET2-V is a pre-configured converter for connecting a Corri-
go E running a ventilation application version 3.0 or later to a SCADA
system. Communication with the Corrigo takes place via EXOline
RS485 and is pre-set to PLA:ELA address 254:254. Communica-
tion betweeen the converter and the SCADA system takes place via
BACnet/IP.
Technical data
Supply voltage
12...48 V DC
Power consumption
4.5 W
Dimensions (WxHxD)
77 x 111 x 26 mm
Weight
190 g
Mounting
Wall*
Ambient temperature
-10...+60°C
Ambient humidity
5...95 % RH
Storage temperature
-20...+80°C
Ethernet connections
Two, automatic change-over
10/100 Mbps
Inputs
Two RS232/422/485 (9-pole D-sub)
* DIN-mounting kit available as an accessory
Mounting
Mount the converter directly on a flat surface, e.g. using a mounting screw
(not included). A kit for DIN-mounting is also available as an option. The
transformer should preferably be mounted using a cable tie.
Black model
Wiring
Connect the RS485 cable to the S0/P1 port on the converter and to the B,
A and N terminals (50, 51 and 52) on the Corrigo. Connect E-BACNET2-
V to the local network by connecting the RJ45 cable between the ETH0/
LAN1 port of the converter and a network port. The converter may also be
connected directly to a computer, but this requires a crossover RJ45 cable
(not included).
Connect the power supply to the converter and to the Corrigo E. Please
note when wiring the supply voltage into the converter: V + is marked
while V - is entirely black.
It will take approx. one minute for the converter to start up. When the
unit is ready, the Ready light will be lit. If the Corrigo connected has the
PLA:ELA address 254:254, the converter will begin communicating. This
is indicated by the S0/P1 TX and RX lights blinking. The unit is now also
available in the BACnet network.
E-BACNET2-V
Power plug
Adapter
Ready
TX
RX
TX
RX
Blue model
S0
Corrigo E
Default parameters
BACnet Device Object Name
BACnet Device ID
Network card
Corrigo E address
Trafo
Network
(Computer)
RJ45
-
+
V- V+
ETH0
ETH1
(WAN)
(LAN)
S0
S1
RS-232/422/485
S1
E-BACNET2-V$
(where $ is replaced with the
BACnet Device ID)
The factory setting Device ID
constitutes a randomly generated
value that should be changed
during initial start-up. This
change is performed using the
configuration tool.
192.168.92.92/24
PLA = 254
ELA = 254
1

Werbung

loading

Inhaltszusammenfassung für Regin E-BACNET2-V

  • Seite 1 RS-232/422/485 Black model Blue model EXOline to BACnet converter E-BACNET2-V is a pre-configured converter for connecting a Corri- Corrigo E go E running a ventilation application version 3.0 or later to a SCADA Wiring system. Communication with the Corrigo takes place via EXOline Connect the RS485 cable to the S0/P1 port on the converter and to the B, RS485 and is pre-set to PLA:ELA address 254:254.
  • Seite 2: Troubleshooting

    IPv4 drivers. EC through product standards EN55022 class A, EN61000-3-2 class A, Click on the Refresh button in order to find the Regin units on E-BACNET2-V är en förkonfigurerad omvandlare som används för EN61000-3-3, EN55024, FCC (part 15 subpart B, CISPR 22 class A).
  • Seite 3 Inkoppling Anslut RS485-kabeln märkt E-CABLE-BACNET till S0/P1-porten på omvandlaren och till Corrigons B-, A- och N-plintar (50, 51 och 52). Anslut E-BACNET2-V till det lokala nätverket genom att koppla RJ45- Corrigo E kabeln mellan omvandlarens ETH0/LAN1-port och ett nätverksuttag. Det går också att ansluta omvandlaren direkt till en dator, men för detta krävs en korsad RJ45-kabel (ingår ej).
  • Seite 4 Produkten uppfyller kraven i EMC-direktivet 2004/108/EG genom produktstandard EN55022 klass A, EN61000-3-2 klass A, EN61000- E-BACNET2-V ist ein vorkonfigurierter Umsetzer, mit dem ein 3-3, EN55024, FCC (del 15 kapitel B, CISPR 22 klass A). Corrigo E mit Lüftungsanwendung (ab Version 3.0) an ein SCADA System angeschlossen werden kann.
  • Seite 5: Fehlerbehebung

    Dieses Produkt entspricht den Anforderungen der EMV-Richtlinie durchgeführt werden. Die Netzwerkeinstellungen müssen nicht mit Adapter 2004/108/EG durch Erfüllung der Normen EN55022 Klasse A, denen des E-BACNET2-V übereinstimmen. Die Mindest- RJ45 EN61000-3-2 Klasse A, EN61000-3-3, EN55024, FCC (Abschnitt 15 systemanforderungen bestehen aus gewöhnlichen IPv4 Treibern.
  • Seite 6: Montage

    B, A et N du Corrigo (nº 50, 51 et 52). Raccordez le câble RJ45 Entrées Deux ports RS-232/422/485 au port ETH0/LAN1 du convertisseur E-BACNET2-V ainsi qu’au port (sub D 9 pôles) réseau de l’ordinateur. Le convertisseur peut aussi être connecté direct- * Kit de montage DIN disponible en option.
  • Seite 7: Sécurité Électrique

    Cliquez sur le bouton Refresh (Actualiser) pour faire apparaître EN 55024, FCC (section 15 sous-section B, CISPR 22 classe A). les unités Regin sur le réseau. Seules les unités marquées BAC- net « Yes » peuvent être éditée dans l’outil de configuration.