ED-RU-DOS
i
Read this instruction before installation
and wiring of the product
Room unit for basic controller configuration or
enduser control
ED-RU-DOS
is an external room unit primarily intended for control of
an air handling unit, heating unit or room controller.
Perform basic controller configuration, or let the person in the room
control the room's HVAC behaviour, via a connected ED-RU... room
unit. Choose from a large selection of room units that fit your specific
needs.
Technical data
Supply voltage
24 V AC/DC
Power consumption
25 mA
Protection class
IP20
Ambient humidity
Max. 90 % RH
Ambient temperature
0...50°C
Storage temperature
-20...+70°C
Mounting
On wall or device box
Display type
Backlit LCD
Communication
EXOline
Wiring
Based on the used controller there are two different wiring options:
1. The room unit can be connected to the same supply voltage as the
controller (G and G0). Communication then takes place via EXOline
and is connected to the serial ports (RS485), A and B.
G
G0
42
A
A
B
43
B
Figure 1 Wiring
2. They can also be connected via an EDSP-K3 cable to the display port.
ED-RU-...
10 G
11
G0
EDSP-K3
42
A
43
B
Figure 2 Wiring with an EDSP-K3 cable
Terminal N and
EDSP-K3 wire color
Description
designator
10 G
Black
24 V AC supply voltage input
11 G0
White
24 V AC voltage reference
42 A
Yellow
Output signal to controller
43 B
Brown
Input signal to controller
ED-RU-DOS
The On/Off button using Application tool
Regio Eedo/Ardo provides several options to manage controller state
changes, that is changes between a comfort and an energy-saving
operational mode. For example, state changes can be managed by:
– Pressing the occupancy button on the room unit to increase the
airflow.
– Detecting presence in the room via a CO
10
detector.
24 V AC
11
The On/Off button using E-tool
The function of the On/Off button can be configured using E tool.
Setting
No function
On/Off
On/off/extended
running
When pressing the On/Off button for 10 s, the air handling unit will
stop. At the next scheduled start-up it will then start and run in mode
AUTO.
A press of the button will start the unit, making it run at normal speed
for the duration set under "extended running" (factory setting 60 min.).
Thereafter, the unit will enter into auto mode.
Increase/Decrease buttons
Enables adjusting the setpoint up or down. The maximum permissable
adjustment of the setpoint is configurable (factory setting ± 3°C).
Depending on the control mode, the setpoint buttons will adjust the
actual setpoint.
Multi-function button
The multi-function button has no function when ED-RU-DOS is
connected to a Corrigo. If the unit is connected to an EXOcompact,
however, the button can be given any desired function through the
EXO system.
sensor or a motion
2
Description
Pressing the button has no effect.
The button can be used to turn the
unit off or place it in auto mode
The button can be used to turn the
unit off or to force it to run in normal
speed for a settable duration, after
which it will enter auto mode.
1

Werbung

loading

Inhaltszusammenfassung für Regin ED-RU-DOS

  • Seite 1 24 V AC supply voltage input Multi-function button 11 G0 White 24 V AC voltage reference Technical data The multi-function button has no function when ED-RU-DOS is Supply voltage 24 V AC/DC 42 A Yellow Output signal to controller connected to a Corrigo. If the unit is connected to an EXOcompact,...
  • Seite 2 More information is available at www.regincontrols.com. Läs denna instruktion innan produkten monteras och ansluts Contact AB Regin, Box 116, 428 22 Kållered, Sweden Rumsenheter för grundläggande regulator- Tel: +46 31 720 02 00, Fax: +46 31 720 02 50 www.regincontrols.com, info@regincontrols.com konfiguration eller slutanvändarkontroll...
  • Seite 3 Lagerungstemperatur -20...+70 °C Bild 2 Verdrahtung mit einem EDSP-K3 Kabel Flervalsknappen Montage Wandmontage oder Einbaudose Flervalsknappen har ingen funktion när ED-RU-DOS är kopplad till en Display-Typ Hintergrundbeleuchtetes LCD Klemme NO und EDSP-K3 Draht Beschreibung Corrigo. Om enheten däremot ansluts till exempelvis en EXOcompact...
  • Seite 4 Betriebsmodus wirdder aktuelle Sollwert über die Sollwert-Tasten angepasst. Multifunktionstaste Die Multifunktionstaste hat keine Funktion, wenn die ED-RU-DOS- Einheit an einen Corrigo-Regler angeschlossen ist. Wenn das Gerät jedoch an einen EXOcompact-Regler angeschlossen wurde, kann der Taste des Gerätes über das EXO-System jede beliebige Funktion zugewiesen werden.

Diese Anleitung auch für:

Ed-ru-do