65 A 2 Way three-phase active power energy meter with Serial Modbus interface, Fig. 1
Description
Energy meter with serial Modbus interface (RS-485)
enables the reading of all relevant data like consumption,
current, voltage and power (active and reactive). The
reactive power (idle power) can only be read on the
Modbus interface
Technical data
■ Fig. 2
Connection
diagram
■ Fig. 3
Dimensions
■ B according to EN50470-3,
Accuracy class
1 according to IEC62053-21
■ I
Reference, Maxi-
ref
mum, initial current
■ 3 × 230/400 V
operating voltage
Tolerance –20%/+15%
■ 00000,00...999999,9 kWh
Counting range
■ Integrated Modbus interface
Ouptut
(see page with the telegram
structure)
■ Conductor cross-section 1,5–16 mm
Connections
Main circuit
screwdriver pozi no. 1, slot no.
2, torque 1,5–2 Nm
■ Conductor cross-section max. 2,5 mm
Connections
Control circuit
screwdriver pozi no. 0, slot no.
2, torque 0,8 Nm
■ −25... +55°C (noncondensing
Operating
temperature
according standard EN50470)
■ Mechanical M2
Environment
Electromagnetic E2
Indicating elements (Fig. 4)
■ Shows total consumption Tariff
T
(kWh)
total
■ Shows partial consumption , this
T
(kWh)
part.
value is resettable
■ Shows total feeding back Tariff
T
(kWh)
total
■ Shows partial feeding back,
T
(kWh)
part.
this value is resettable
■ Shows the instantaneous power
P(kW)
per phase or all phases.
Current
Current
■ Shows the voltage per phase
U(V)
■ Shows the current per phase
I(A)
■ Shows the unit kWh when the
kWh
consumption is displayed
■ For P-, U-, I- or Error display, the
L1 / L2 / L3
corresponding phase is displayed
■ In case of missing phase, the
Error
corresponding phase is addition-
ally displayed.
323007735-001
= 10 A, I
= 65 A, I
40 mA
=
max
st
, 50 Hz
AC
= consumption (pos.)
= feeding back (neg.)
Notes before connecting
1. Do not connect L1, L2 or L3 to N
2. In order to avoid moisture in the meter due to
condensate build-up, acclimatise the meter at room
temperature for about half an hour before connecting.
3. N must always be connected.
Attention!
These devices must only be installed by a professional
electrician, otherwise there is the risk of fire or the risk
of an electric shock.
Operation of the LCD display
See page with LCD menu navigation
Installation instructions
The three-phase energy meter can be attached to a
35 mm rail (EN60715TH35).
The meter can be used only in installation cabinets.
,
2
Method of operation (Pic. 5)
,
2
Energy is added as indicated by the arithmetic operator.
Positive output in the meter indicates that energy is being
supplied, while negative output indicates that energy is
being delivered.
Declaration of Conformity CE
We, Finder Gmbh herewith declare, on our own respon-
sibility that the products:
■ 7E.46.8.400.0204
■ 7E.46.8.400.0214
which this certificate refer to, are in accordance with
the directive 2004/22/EG (MID) and the following
standards:
■ EN50470 parts 1 and 3 (electronic meter), of
October 2006.
The following energy meters are approved for energy
billing:
7E.46.8.400.0214
Trebur, 01.03.2015
Conformity Assessment Body:
METAS-Cert, Nr. 1259
CH-3003 Bern-Wabern
Signed: Manfred Cloot, Head of Technic
03.2015