Differential pressure switch for air and neutral
gases
DTV...X is a differential pressure switch for supervising air handling
units, fans, fi lters or to control defrosting functions.
Technical data
Relay output
Max. 1 A (0.4 A), 250 V AC, change-over
contact
Cable connection
AMP fl at plug, 6.3 x 0.8 mm in
accordance with DIN 46244.
Cable conduit with cable strain relief.
Pressure connection
Connection pipes for 6 mm tube, P1 (+)
connects to higher pressure, P2 (-) to
lower pressure
Ambient temperature
-20...+85°C
Storage temperature
-40...+85°C
Maximum diff. pressure
10 kPa (all models)
Material
Sensor housing
Polystyrene
Membrane
Silicone
Mounting bracket (optional)
Galvanized stainless steel with two
mounting holes (Ø 5 mm,
cc 40 mm)
Protection class
IP54
Weight
0.12 kg
Installation
Mount the pressure transmitter close to the application to be monitored.
An optional mounting bracket can be used, if desired (see below). Select
suitable holes and fasten the bottom plate on the wall or in a connection
box, so that the arrows on the bottom plate point upwards.
The vertical mounting position, as shown in the leftmost illustration, is the
recommended one. If the pressure switch is mounted with its lid facing up,
as in the middle picture, the change-over point will be 11 Pa higher than
the setpoint. Conversely, mounting the switch with the lid facing down will
instead lower the setpoint by 11 Pa.
Function
The pressure connected to the high pressure point inlet (P1) is compared
to the low pressure connected to P2. When the differential pressure
exceeds the setpoint value, the contact will close or open.
When the pressure switch is used to supervise a fan, it is possible to
leave the P2 pressure connection (for atmospheric pressure) discon-
nected.
P2
P1
P1 = Connection of higher pressure
P2 = Connection of lower pressure
DTV...X
2 NO
3 COM
1 NC
P
1 = Closing contact
2 = Operating contact
3 = Power supply line
Setpoint value and setting
The setpoint value is set using a knob under the lid, with the setpoint
value visible through the lid. The lid is secured with a single screw to
facilitate mounting and service.
The device hysteresis is pre-set upon delivery.
NOTE: Do not turn the setting knob to the area marked in black!
Low Voltage Directive (LVD) standards
This product conforms to the requirements of the European Low Volt-
age Directive (LVD) 2006/95/EC.
RoHS
This product conforms to the Directive 2011/65/EU of the European
Parliament and of the Council.
Contact
AB Regin, Box 116, 428 22 Kållered, Sweden
Tel: +46 31 720 02 00, Fax: +46 31 720 02 50
www.regincontrols.com, info@regin.se
1

Werbung

loading

Inhaltszusammenfassung für Regin DTV...X Serie

  • Seite 1 fi lters or to control defrosting functions. AB Regin, Box 116, 428 22 Kållered, Sweden When the pressure switch is used to supervise a fan, it is possible to...
  • Seite 2 Reläutgång Max. 1 A (0,4 A), 250 V AC, Kontakt växlande kontakt AB Regin, Box 116, 428 22 Kållered, Sweden Kabelanslutning Platt AMP-kontakt, 6,3 x 0,8 mm enligt P1 = Högtrycksanslutning Tel: +46 31 720 02 00, Fax: +46 31 720 02 50 DIN 46244.
  • Seite 3 Enteisungsfunktion. Kontaktadresse Der Druck, der am Überdruckeinlass (P1) anliegt, wird mit dem Druck am Regin Controls Deutschland GmbH, Haynauer Str. 49, 12249 Berlin, Unterdruckeinlass (P2) verglichen. Wenn der Differenzdruck vom Sollwert Technischen Daten abweicht, wird der Kontakt geschlossen oder geöffnet.