Leister CSS Bedienungsanleitung Seite 20

Vorschau ausblenden Andere Handbücher für CSS:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

20
Out
Output settings
Select reference
signal for
alarm 1
Default: 0
Select reference
signal for
alarm 2
Default: 0
Alarm type 1
Default: 0
Alarm type 2
Default: 0
Out 1
Allocation of
Default: 2
reference signa
Out 2
Allocation of
Default: 5
reference signal
Out 3
Allocation of
Default: 3
reference signal
Fault action (sets state in case of
probe fault)
Default: 0
Err, Sbr
Out W
Assignment of signal or reference
value
Default: 5
Protection code
Pro
(PAS 99)
Out Menu
AL.1.r, AL.2.r
AL.x.r
Variable to be compared
0
PV (Process variable)
1
SSP (active setpoint)
2
PV (process variable)
AL.1.t, AL.2.t
AL.x.t
Direct (high limit)
Absolute or
Inverse (low limit)
relative to
active setpoint
0
direct
absolute
1
inverse
absolute
2
direct
relative
3
inverse
relative
4
direct
absolute
5
inverse
absolute
6
direct
relative
7
inverse
relative
+8 to disable on power up until first interception
+16 to latch alarm
+ 32 Hys becomes delay time when alarm trips (0...999 sec.) (excluding symmetrical absolute)
+ 64 Hys becomes delay time when alarm trips (0...999 min.) (excluding symmetrical absolute)
rL.o.1, rL.o.2, rL.o.3, rL.o.4
Val
Function of main output relay/logic (OUT1)
0
HEAT (control output for heating)
1
COOL (control output for cooling)
2
AL1 - alarm 1
3
AL2 - alarm 2
4
AL3 - alarm 3
5
AL.HB - alarm HB
6
LBA - alarm LBA
7
IN1 - repetition of logic input
8
Repeat but key (if but = 8)
9
AL1 or AL2
10
AL1 or AL2 or AL3
11
AL1 and AL2
12
AL1 and AL2 and AL3
13
AL1 or ALHB
14
AL1 or AL2 or ALHB
15
AL1 and ALHB
16
AL1 and AL2 and ALHB
+ 32 for denied logic level at output, except codes 0...1 with continuous output
_rEL.
Alarm
Alarm
1
2
0
OFF
OFF
1
ON
OFF
2
OFF
ON
3
ON
ON
4
OFF
OFF
5
ON
OFF
6
OFF
ON
7
ON
ON
Val
Reference value
0
PV - process variable
1
SSP - active setpoint
2
SP - local setpoint
3
-
4
Deviation (SSP-PV)
5
HEAT (*)
6
COOL (*)
7
AL1 (alarm point)
8
AL2 (alarm point)
9
AL3 (alarm point)
10
-
11
Value acquired from serial line (*)
16 for code 0 if input is in error status Err – Sbr output assumes minimum
trimming value.
Prot menu (PAS)
Prot
Display
0
SP, In2, alarms, OuP, INF
1
SP, In2, alarms, OuP, INF
2
SP, In2, OuP, INF
+ 4
to disable InP, Out
+ 8
to disable CFG, Ser,
+ 16 to disable SW "power-up - power down"
+ 32 disable manual power latching
+ 64 to disable manual power modification
+128 enables full configuration
Reference setpoint
AL
AL (only absolute)
AL (only relative and
referred to SP1 with
multiset function)]
Normal
Symmetrical
(window)
normal
normal
normal
normal
symmetrical
symmetrical
symmetrical
symmetrical
Alarm
3
OFF
OFF
OFF
OFF
ON
ON
ON
ON
Modification
SP, alarms
SP
20