Assembly and operating instructions Type ALD1D5FM
32 A Single Phase active power energy meter with M-Bus interface, Pic. 1
Description
Energy meter with M-Bus interface enables the reading of
all relevant data like meter reading, electricity, voltage,
power (active and reactive).
Technical data
Connection
Pic. 2
■
diagram
Dimensions
Pic. 3
■
Accuracy class
B, according to EN50470-3,
■
Cl. 1 according to IEC62053-21
Reference, Maxi-
I
= 5 A, Im
ref
■
mum, initial current
operating voltage
230 V
■
Tolerance −20%/+15%
Counting range
00000,00...999999,9 kWh
■
Connections
Conductor cross-section max. 6 mm
■
Main circuit
Screwdriver Pozi No. 1, slotted
No. 1, breakaway torque 1,2 Nm
Connections
Conductor cross-section max. 2,5 mm
■
Control circuit
Screwdriver Pozi No. 0, slotted
No. 1, breakaway torque 0,5 Nm
Operating
−10... +55°C (noncondensing
■
temperature
according standard EN50470)
Indicating elements
(Pic. 4)
T total (kWh)
Indicates the total consumption
■
T part (kWh)
Indicates the partial consumption.
■
This value can be reset
P (kW)
Indicates the instantaneous power
■
U (V)
Indicates the voltage
■
I (A)
Indicates the current
■
2000 pulses/kWh
Pulsates according to the amount
■
of used power. Error indication
(line 1L/2L inverted) with pulse of
600/600 ms.
4 319 5112 0
= 32 A, Ist
20 mA
ax
=
, 50 Hz
AC
07.2011
Notes before connecting
In order to avoid moisture in the meter due to condensate
build-up, acclimatise the meter at room temperature for
about half an hour before connecting.
Attention!
These devices must only be installed by a professional
electrician, otherwise there is the risk of fire or the risk
of an electric shock.
Operation of the LCD display
See page with LCD menu navigation.
Installation instructions
,
2
The energy meter can be attached to a 35 mm rail
(EN60715TH35).
,
2
The meter can be used only in installation cabinets.
Declaration of Conformity CE
We, Saia-Burgess Controls Ltd., CH 3280 Murten
(Switzerland),herewith declare, on our own responsibil-
ity that the products:
ALD1D5FM00A3A00
■
which this certificate refer to, are in accordance with
the following standards:
EN50470 parts 1 and 3 (electronic meter), of
■
October 2006.
Directive 2004/22/EG of the European.
■
parliament and of the council regarding measuring
instruments.
• Annex I, essential requirements.
• Annex MI-003, active electrical energy meters.
ESD on equipment side: 13 kV.
EC - Declaration of Conformity: 2011
Saia-Burgess Controls AG
Conformity Assessment Body:
Zertifizierungstelle METAS-Cert, Nr. 1259
CH-3003 Bern-Wabern
Signed:
Jean-Paul Costa, Head of development
Subject to change without notice
English