Herunterladen Diese Seite drucken

brennenstuhl PRCD-S IP 54 Bedienungsanleitung Seite 2

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

067716 BA_Personen-Schutzverteiler PRCD-S.qxp 24.08.16 11:38 Seite 2
Portable Residual Current Device-Switched
PRCD-S IP 54
Description
The PRCD-S residual current monitoring device is used as a distributor for, amongst other things,
small construction sites in accordance with trade association requirements. It increases operating
safety at the construction site by providing additional monitoring of the fault current and the
protective earth conductor when the distributor is connected to a TN-type supply grid.
Error Conditions
The PRCD-S residual current monitoring device recognises the following errors on the supply end:
external or neutral conductor interrupted,
not connected
external and PE conductor switched
PE conductor interrupted, not connected
PE conductor interrupted during operation
PE conductor carries dangerous voltage
undervoltage
Specifications
Nominal voltage
Nominal current
System of protection
Nominal residual current
Ambient temperature (storage)
Ambient temperature (operation)
Relative humidity
Protection class
Overvoltage category
Indicators
Max. insulation resistance for detecting
dangerous voltage at PE
Notes
1. The PRCD-S residual current monitoring device is a distributor for small construction sites
based on E DIN IEC 62335 and the requirements of BGI 608 of the Energy Textile Electrics pro-
fessional association. The trade association recommends SPE-PRCDs as an effective protection
for small construction sites and portable electrical appliances; the residual current monitoring
device serves as a distributing point for small construction sites in accordance with BGI.
2. These residual current monitoring devices are subject to repeat tests and one-time tests
(after each modification) in accordance with German trade association regulation BGV A3;
because they use PE monitoring and separation, the protective conductor current is measured
instead of insulation resistance in accordance with VDE 0702-1, section 4.3.4.
All repeat and one-time tests must include a functional test that comprises the detection
of all error conditions (see above).
The ground fault circuit interrupter must be tested regularly in accordance with its label.
3. The standard rules of electrical engineering must be observed.
4. Subject to technical modifications without prior notice.
Dimensions
Note: Actual product design and layout may vary
Assembly
Ground fault circuit interrupter
Protective earth monitoring device
TEST
Note: Actual product design and layout may vary
switch-on not possible
switch-on not possible
switch-on not possible
automatic power shut-off
no automatic reclosing
switch-on not possible
automatic power shut-off
no automatic reclosing
see rating plate
see rating plate
see rating plate
see label on ground fault circuit interrupter
–30 to +85 ºC
–20 to +40 °C
10 - 90% non-condensing
I
II
LED lights up when PRCD-S is on
28 MΩ
430 ± 1 mm
START
Initial Operation
1. Connect the PRCD-S to the supply system
2. Test the ground fault circuit interrupter:
Test the protective earth monitoring device
3. Press START whilst touching the sensor with your bare hand
4. PRCD-S switches on if
5. Switch off:
How to Detect Dangerous Voltage on the PE Conductor
Installation errors
L
RCD
N
PE
R
earthing resistance
E
R
insulation resistance ground-earth
ISO
R
insulation resistance body-ground
S
R
body resistance
B
R
touch resistance
H
R
E
R
ISO
Dangerous voltage on the PE conductor (e.g., because of an installation error) is detected by
measuring the touch current generated by the difference of potential between the PE connection of
the PRCD-S and the on-site protective earth conductor. The principle of measurement used is similar
to that of a phase comparator. Voltage up to a total resistance R
28 MΩ is considered dangerous; the touch current for R
Standard Values
R
0 - 1.6 kΩ (VDE 0100-410)
E
R
An electrically isolating floor as defined in VDE 0100-410 has an R
ISO
(for nominal voltages up to 500 V) or more than 100 kΩ (nominal voltages > 500 V); under
those conditions it is assumed that there is no
DIN EN 61010-1: 2 kΩ (hand-foot, dry), 875 Ω (hand-foot, damp)
risk of electrical shock if someone touches a dangerous live conductor.
R
B
For very low body voltages up to 100 kΩ
R
+R
0 - > 10 MΩ
S
H
Depends on clothing, shoes, skin humidity, etc.
The START button must always be pressed with a bare hand because otherwise
it is difficult or even impossible to recognise dangerous voltage on the
PE conductor.
How to Test the "Detect Dangerous Voltage on PE" Feature
A suitable isolating transformer must be used to avoid endangering the person carrying out the test.
Basic Test Setup
230 V ~
L
L'
N
N'
230 V ~
The PE contact of the plug must be connected to L'!
The residual current monitoring device must not switch on when the START button is touched
with the test prod!
Declaration of conformity
The declaration of conformity has been lodged with the manufacturer.
Disposal
Do not dispose of electrical devices with household rubbish!
In accordance with European Directive 2012/19/EU regarding electrical and electronic
devices must be collected separately and sent in for recycling.
Please contact your local authorities for available disposal options for your worn-out device.
Hugo Brennenstuhl GmbH & Co. KG · Seestraße 1-3 · D-72074 Tübingen
H. Brennenstuhl S.A.S. · 4 rue de Bruxelles · F-67170 Bernolsheim
lectra-t ag · Blegistrasse 13 · CH-6340 Baar
www.brennenstuhl.com
see label
1. switch the ground fault circuit interrupter on
2. press START
the PRCD-S switches on
3. press TEST
the PRCD-S switches off
1. there are no errors in the power supply wiring
and
2. the protective earth conductor does not
carry a dangerous voltage
LED lights up
1. pull mains plug
or
2. press TEST
R
H
R
B
R
S
Σ
= 2 kΩ ( RB only) is less than 500 μA.
(= R
+ R
+ R
+ R
+ R
) of up to
E
ISO
S
B
H
Σ
of more than 50 kΩ
ISO
START
Test prod

Werbung

loading