Group address Table on two levels:
KNX 2 Level Structure
Main Groups
UG
0-15 (S1)
0-511
0-15 (S1)
511-1023
0-15 (S1)
1024-1535
0-15 (S1)
1536-1543
0-15 (S1)
1544-1551
0-15 (S1)
1552
0-15 (S1)
1553
0-15 (S1)
1554
0-15 (S1)
1555
0-15 (S1)
1556
Value
DMX512
Sequence
Chan-
Nr.
nel Nr.
0..255 001-512
-
0..255 001-512
-
-7..+7
001-512
-
0/1
ALL
0/7
0/1
ALL
0/7
0/1
ALL
-
0..255 ALL
-
0..7
ALL
-
0..7
ALL
-
0/1
ALL
-
KNX-DMX Gate-
Detail
way Function
DPT 5.001 trans-
1 Byte value is stored
mits 1byte value
into the corresponding
(Absolute value)
DMX-Channel directly
DPT 1.001 value
When a 1 is received
transmission
the value stored in
sequence Nr. 8 is sent
to the correspond-
ing DMX-Channel
When a 0 is received
the DMX-Channel
is turned off.
DPT 3.007 value
Relatively lighter or
transmission
darker dimming than
the current level
DPT 1.001 value
The selected sequence
transmission
values of all 512 chan-
Access saved
nels are transmitted
sequences
on the DMX512 bus
DPT 1.001 value
All current DMX values
transmission
in channels 1-512 are
Save the new
stored in the selected
sequence
sequence position
DPT 1.001 value
All 512 channels
transmission
display 100% when
All channels
1 is transmitted, 0%
central on
when 0 is transmitted
DPT 5.001 value
Repetition rate
transmission
of 10msec
Repetition rate
Value default 3
parameters
DPT 3.007 value
Dim repitition value
transmission
Value Default 15=1%
Set downward
dimming curve
DPT 3.007 value
Dim repitition value
transmission
Value Default 15=1%
Set upward
dimming curve
DPT 1.001 value
Disables auto-
transmission
matic dimming
Deactivate auto-
when value = 0
matic dimming