Product information
Chain actuator type EA-K 24E-L
Please take notice
To avoid damage
about the content of
and injury!
this manual!
Remote controlled electrical drives for smoke and heat ventilation and daily ventilation.
Suitable with or without control panels from
Nominal force (pull):
Produkt
Description
Nominal force (push):
Stroke length*:
Speed with nominal load :
Voltage:
Technical
Data
Current:
Switch on duration
Overload protection:
Cut off:
Protection class:
Housing:
Accessories (included in delivery):
*Optional: stroke limiting ex works (see the data on the type plate).
Dimension of current supply has to be suitable for this actuator. Please take notice of the
voltage and current datas on the data plate. Please check all cables, especially cable
cross section, before putting into operation.
Please check complete system before connect to the mains. The chain actuator is
equiped with internal overload cut off and end switches.
Electrical
Connection
Cable cross section [mm²] = 0,019 x number of actuators x current of actuator [A] x
cable length [m] (Transformer - primary voltage of 230 V and temperature 25° C)
3
Installation at a bottom - hinged wing inwards opening
Chain actuator
mounted on the
wing frame
Assembly
accessories
Overlapping of the wing 0 - 12 mm (when the over-
lapping 13 - 22 mm then use distance blocks)
Installation at a bottom - hinged wing inwards opening
with low wing height
Chain actuator
mounted on the
wing frame
kiko/g
The function of the actuator must be tested periodically by the customer. In case of defect
installer has to be informed at once. Please change defect parts immediately with origine
parts. Actuator to be opened only by the manufacturer.
Material defects:
Maintenance
The device must be used as normally intended. The duration of the operating time must
be observed, please inquire in case of doubt. The device is subject to natural wear and
tear. In case of material defect claims, these shall be asserted in writing, stating the
source of supply of the device. Prescribed time limits and further provisions with regard to
claims for material defects exclusively correspond with our General Terms and
Conditions (download:
www.simon-rwa.de
mail to
info@simon-rwa.de
Important: Please consider VDE 0833 for hazard alert systems, VDE 0100 for
electrical system, DIN 18232 for SHEV-systems, the commandments of the local
fire department and of the EVU for the mains connection as well as VBG 4 and ZH
1/494.
Please consider: Force operated windows may not be located within the reaching
Attention
area of hands. Bruising danger! The commandments (ZH 1/494) of the assosiation
of commercial and industrial workers' compensation insurance carriers have to be
considered!
Attention: The chain is operated by an electric actuator. Don't grasp into the chain
or the wing during operation!
Please keep the product
information for later use
(e.g.maintenance)
Systeme.
SIMON RWA
300 N
150 N at 260 mm Stroke
100 N at 380 mm Stroke
380/260 mm reversible
20 mm/s
24 V DC
1,0 A
20% ED
load depending cut off
End switch
IP 50
aluminium, EV1 anodized
standard mounting brackets
Chain actuator
mounted on the
blind frame
SKI/A (K)
Installation at a top - hung
wing
Chain actuator
mounted on the
blind frame
Overlapping of the wing
0 - 12 mm (when the over-
lapping 13 - 22 mm then
use distance blocks)
, or they may be requested by sending an e-
, or by phone +49 851 988700).
2
Parallel connection:
The actuators run concurrently, the current supply and the cable cross section have to be
adapted to the systems total current.
Attention:Do not earth electrical connection.
Please take notice of actuator voltage, only 24V DC!
Electrical
Switch of at 1,0 A
Connection
Open: 1 (*S) = +
Close: change
+ (-)
- (+)
The circuit diagram is valid by delivery with a connection cable factory - provided.
Switch of at 1,0 A
Open: 1 (*S) = +
Close: change
+ (-)
- (+)
Installation of smoke and heat vent systems only by specialists authorized from SIMON
RWA Systeme GmbH.
At bottom - hung wings a stay with enough stroke has to be assemble. See that the
actuator is installed on the window or rather on the wing frame durable and that the
Assembly
installation is construed for the actuators force.
accessories
Please make sure that the chain actuator switchs off by limit switch at its end position. For
"Close" the limit switch can be fixed by moving the eyescrew on the end of the chain If end
switch will not be arrived the actuator can be damaged.
Attention:
- the minimum height of the wings: at top - hung wings, threefold
- Stroke change (260 / 380 mm) only when the status is dead!
4
Chain actuator
According to the disposal law "ElektroG", this device must be disposed properly at the end
mounted on the
of its life time.
blind frame
Disposal
SKI/V1
EC-Manufacturer's declaration
We hereby declare, that the product listed below duet to its conception and design and
in the make, issued by us is, according to the enclosed notes on operation and
mounting, designed to be inserted into a machine respectively installation. Its initial
operation is prohibited until the machine or the installation, into which the mentioned
part is to be mounted, fully complies with the EC-regulation 89/392/EEC changed by
91/368/EEC and 89/336/EEC changed by 93/31/EEC and 73/23/EEC.
Any adaptions or alterationof which may be made to the product, without the prior consent
of SIMON RWA Systeme , will make this declaration
Denomination: chain actuator type EA-K 24 E-L
For manufacturing or order number please see type plate
We certify conformity with applicable EC-regulations of the product stated above.
89/336/EEC changed by 92/31/(EEC), 89/392/EEC changed by 91/368/EEC, 73/23/EEC,
EN50081-1, EN50082-1, EN 55014, DIN EN292/1 and EN292-2
For delivered respectively not ready-mounted or not yet operated components of an
electrical smoke and heat vent system with a manufacturer's declaration according to EC-
machine regulation the customer will be liable for proper mounting and initial operation as
well as for drawing up of the declaration of conformity according to EC-regulations.
This declaration certifies compliance with the regulations mentioned, however does not
include an assurance of specific characteristics.
Please comply with notes on security mentioned in the instructions.
Passau, 06-03-15
The management
M
24 V DC
1
2
3
3 (*O) = -
2
is used for signals - do not connect from different actuators
M
24 V DC
1
2
3
3 (*O) = -
is used for signals - do not connect from different actuators
2
* In connection with electric control units SIMON RWA Systeme!
at bottom - hung wings, twofold
(according to article 4 section 2 EC-regulation 89/392/EEC)
Switch of at 1,0 A
M
24 V DC
1
2
3
Open: 1 (*S) = +
3 (*O) = -
Close: change
Switch of at 1,0 A
M
24 V DC
1
2
3
Open: 1 (*S) = +
3 (*O) = -
Close: change