USER INSTRUCTIONS
English
Repeater Power Supply
GC 52100
Read these instructions before using the product and retain for future information.
GC 52100
► Before Startup
When operating the signal converter, certain parts
of the module can carry dangerous voltage!
Ignoring the warnings can lead to serious injury
and/or cause damage!
The signal converter should only be installed and
put into operation by qualified staff. The staff must
have studied the warnings in these operating
instructions thoroughly.
The signal converter may not be put into operation if
the housing is open.
In
applications
with
high
operating
voltages
sufficient distance and isolation as well as shock
protection must be ensured.
Safe and trouble-free operation of this device can
only be guaranteed if transport, storage and
installation are carried out correctly and operation
an maintenance are carried out with care.
Appropriate safety measures against electrostatic
discharge (ESD) should be taken during range
selection and assembly on the transmitter.
► Short description
The Repeater Power Supply supplies the transmitter with power and
transmits the current or voltage measuring signal with high accuracy
galvanic isolated to the output. Alternative the measuring input
accepts active signals from 4-wire transmitters.
The input and output range can be easily set by using DIP switch.
Due to the calibrated range selection no further adjustment is
necessary.
The 3-way isolation guarantees reliable decoupling of the sensor
circuit from the processing circuit and prevents linked measurement
circuits from influencing each other. The Protective Separation with
high isolation level
provides protection for personnel
downstream devices against impermissibly high voltage.
The auxiliary power can either be supplied via the connection
terminals or via the In-Rail-Bus connector (see accessories).
► Functioning
The input signal is modulated and then electrically decoupled using
a transformer. The isolated signal is then made available at the
output, demodulated, filtered and amplified.
► Settings
Set the input and output ranges with DIP switch as indicated in the
following table:
S1-
Input
Output
1
2
3
4
0 ... 20 mA
4 ... 20 mA
0 ... 20 mA
0 ... 10 V
0 ... 10 V
2 ... 10 V
0 ... 20 mA
4 ... 20 mA
4 ... 20 mA
2 ... 10 V
0 ... 10 V
2 ... 10 V
Factory settings: all switches in position OFF
► Mounting, Electrical Connection
The repeater power supply is mounted on standard 35 mm DIN rail.
Terminal assignments
1
Transmitter Supply Tx +
5
Output +
2
Input I +
6
Output −
3
Input GND
7
Power supply +
4
Input U +
8
Power supply −
► Technical Data
Input
Voltage
Input signal
0 ... 10 V
2 ... 10 V
(calibrated switchable)
Input resistance
≥ 100 kΩ
Overload
≤ 30 V
Transmitter supply (Tx)
17 V (open circuit / short circuit < 22 V / 35 mA)
Output
Voltage
Output signal
0 ... 10 V
(calibrated switchable)
2 ... 10 V
Load
≤ 5 mA (2 kΩ @ 10 V)
Linear transmission range
-1 to +110 %
Residual ripple
< 10 mV
rms
and
General data
Transmission error
< 0.1 % full scale
1)
Temperature coefficient
< 100 ppm/K
Cut-off frequency -3 dB
100 Hz
Response time T
7 ms
99
Test voltage
3 kV, 50 Hz, 1 min.
Input against output against power supply
2)
Working voltage
600 V AC/DC for overvoltage category II and
(Basic insulation)
contamination class 2 acc. to EN 61010-1
Protection against
Protective Separation by reinforced insulation acc.
dangerous body
to EN 61010-1 up to 300 V AC/DC for overvoltage
2)
currents
category II and contamination class 2 between
input and output and power supply.
Ambient temperature
Operation
-25 °C to +70 °C (-13 to +158 °F)
Transport
-40 °C to +85 °C (-40 to +185 °F)
and storage
Power supply
24 V DC
16.8 V ... 31.2 V, approx. 1.3 W
3)
EMC
EN 61326-1
Construction
6.2 mm (0.244'') housing, protection type: IP 20
mounting on 35 mm DIN rail acc. to EN 60715
5
6
Connection
Solid:
(captive plus-minus
Fine-stranded:
clamp screws)
Stripped length: 6-8 mm / 0.28 in
Screw terminal torque 0.8 Nm / 7 lbf in
Weight
Approx. 70 g
1) Average TC in specified operating temperature range
2) As far as relevant the standards and rules mentioned above are considered
by development and production of our devices. In addition relevant assembly
rules are to be considered by installation of our devices in other equipment.
For applications with high working voltages, take measures to prevent
accidental contact and make sure that there is sufficient distance or insulation
between adjacent situated devices.
● = on
3) Minor deviations possible during interference
► Block Diagram
► Order Information
Current
Product
0 ... 20 mA
4 ... 20 mA
Repeater Power Supply
≤ 25 Ω
≤ 50 mA
Repeater Power Supply
In-Rail-Bus for power supply
Current
0 ... 20 mA
4 ... 20 mA
► Dimensions
≤ 12 V (600 Ω @ 20 mA)
ZERO
SPAN
2
2
0.5 mm
- 4 mm
/ AWG 20-12
2
2
0.5 mm
- 2.5 mm
/ AWG 20-14
WARRANTY
Régulateurs GEORGIN hereby warrants that the Product will
be free from defects in materials or workmanship for a period
of five (5) years from the date of delivery ("Limited
Warranty"). This Limited Warranty is limited to repair or
replacement at GEORGIN's option and is effective only for
the first end-user of the Product. This Limited Warranty
applies only if the Product:
1. is installed according to the instructions furnished by
GEORGIN;
2. is connected to a proper power supply;
3. is not misused or abused; and
4. there is no evidence of tampering, mishandling, neglect,
accidental damage, modification or repair without the
approval of GEORGIN or damage done to the Product by
anyone other than GEORGIN.
Subject to change!
Régulateurs GEORGIN
14-16 Rue Pierre Sémard
92320 - Châtillon
FRANCE
Téléphone :
Fax :
E-mail :
regulateurs@georgin.com
Internet : www.gorgin.com
Input / Output
Order No.
calibrated
GC 52100 S
switchable
calibrated
GC 52100 B
switchable
+33 1 46 12 60 00
+33 47 35 93 98