Herunterladen Inhalt Inhalt Diese Seite drucken

Emerson FB2200 Anleitung Seite 6

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 9
Safe Use Instructions – Emerson FB2200
Part D301801X012
September 2018
2. The FB2200 mounts on a two-inch pipe or pole (see
Figure
7) or can be wall- or panel-mounted using the
four holes in the case and suitable attachments.
Figure 7. FB2200 (Aluminum Enclosure) on Pipe Mount
Grounding
Open the front door of the FB2200 as detailed in either
Chapter 2 of the Emerson FB2200 Flow Computer
Instruction Manual (part D301784X012) or in the
Emerson FB2200 Flow Computer Quick Start Guide (part
D301788X012).
If your company has no specific grounding
requirements, install the FB2200 as a "floating"
(unconnected to ground) system using the ground lug
and routing the ground wire through one of the conduit
fittings. Otherwise, follow your company's specific
grounding practices. However, if you are making a
connection between a grounded device and an EIA-232
(RS-232) port, ground the FB2200's power supply.
If you must ground the equipment, observe the
following guidelines:
When the equipment uses a DC voltage source,
the grounding system must terminate at the
service disconnect. All equipment grounding
conductors–including wire or conduit carrying the
power supply conductors–must provide an
uninterrupted electrical path to the service
disconnect.
Improper grounding or poor grounding practices
can often cause problems, such as introducing
ground loops into the system. Properly grounding
the FB2200 helps to reduce the effects of electrical
noise on the unit's operation and protects against
lightning. Install a surge protection device at the
service disconnect on DC voltage source systems
to protect the installed equipment against
lightning and power surges.
Ensure that the flow computer's ground is
separate from the cathodic protection ground.
4
The grounding installation method for the FB2200
depends on whether the pipeline has cathodic
protection. On pipelines with cathodic protection,
electrically isolate the FB2200 from the pipeline. All
earth grounds must have an earth-to-ground rod or
grid impedance of 25 ohms or less, as measured with
a ground system tester.
Wiring to Power
Wire the FB2200 through the conduit fittings on the
bottom of the housing. The terminal blocks accept wiring
2mm in diameter/3mm
2
the removable block compression terminals:
Bare the end (6mm maximum) of the wire.
Insert the bared end of the wire into the clamp
beneath the termination screw.
Tighten the screw.
Expose a minimum of bare wire to prevent short circuits.
Allow some slack when making connections to prevent
strain.
Connect the power wiring. Review the power wiring
descriptions in Chapter 2 of the Emerson FB2200 Flow
Computer Instruction Manual (part D301784X012).
Verify the hook-up polarity is correct.
To make DC power supply connections:
Remove the terminal block connector from the
socket.
Insert each bare wire end into its appropriate
connector and secure the wire (see
Plug the terminal block connector back into the
socket.
Figure 8. Wiring to DC Power Supply
Refer to the Emerson FB2200 Flow Computer Quick Start
Guide (part D301788X012) for detailed instructions on
connecting the battery.
Wiring to Communications & I/O
Connect the wiring to the terminal blocks on the I/O and
communications modules. Refer to either Section 2.8 in
Chapter 2 of the Emerson FB2200 Flow Computer
www.Emerson.com/RemoteAutomation
or smaller. To connect the wire to
Figures 7
and 8).

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis