INSTALLATION NOTES
General information
These installation notes explain only the wiring arrangement for
this module. Further descriptions and safety-relevant data are to
be inferred from the appropriate manuals.
Mounting
The DeviceNet FD67NDNM127804 bus node can be mounted
directly onto a base plate or on to a machine (first remove the cap)
by means or two fixing holes in the housing of the base module.
Please ensure that the mounting surface has no unevenness,
which could put a strain on the module housing. The module
mounting requires two screws Ø 4 mm and two washers. The
spacing of the fixing holes is 125 ± 0,5 mm.
Torque of the M4 screws : 2 ± 0,5Nm.
Provide for an adequate cable relief clamp.
Make a short (max. 20 cm) and low-impedance ground connection
to the housing cap (screw accessible from underneath) with the
ground cable.
!
1 Screw for the ground connection in the cap
Torque of the M3 screw: 1,2 ± 0,2 Nm
The cap shall only be removed while the module is not under
voltage. This will not affect the DeviceNet operation.
Torque of the screws in the cap: 1,0 ± 0,2 Nm.
Station address
The station address is set by means of two BCD selectors located
under the cap. The decimal coded address is directly set by the two
selectors.
1 Switch off the power
2 Open the cap
3 Set the address
4 Set the baud rate
5 Close the cap
6 Switch on the power supply
Addresses can be set between 00 and 63.
Address > 63 means MAC-ID 63 operation.
FD67NDNM127804
Baud rate
The baud rate is set by means of the DR switch.
0
125 kBit/sec
1
250 kBit/sec
2
500 kBit/sec
>2 125 kBit/sec
Baud rate setting > 2 means 125 kBit/s operation.
Power supply connection
The mains voltage is connected to the module by means of a 7/8"
5-pole connector.
Contact assignments:
1
GND
2
GND
3
PE
4
24 V Sensor supply
5
24 V Actuator supply
The max. admissible current per pin is 9 A.
This shall be observed if standard cables are used.
DeviceNet connection
The DeviceNet cable is connected to the bus node by means of a
M12 connector. Connect also the terminal resistor by screwing a
bus terminal resistance (FD67L) at the end of the bus.
Please observe the ODVA instructions.
1
Shield
2
24 V Service voltage
3
GND
4
CAN_HIGH
5
CAN_LOW
DeviceNet configuration
A EDS file is required to configure the bus node by means of a
configuration software. You can find the EDS file under:
NA
NA
x10
x1
Module connection
Modules can be connected directly to the bus node via the internal
DR
system connection.
M12 sockets that are not used must be closed by means of a blind
plug (FD67BLKM120000)
Torque : 0,6+0,1 Nm.
2
1
3
4
5
BUS IN
BUS OUT
3
3
5
5
4
2
2
1
1
http://www.norgren.com
>>
Use exclusively Norgren cables for the internal system
connection.
The max. admissible current per pin is 4 A.
Indicators
The bus node has integrated LED indication which shows the
status of the system and the connected modules.
LED
Colour
Signification
U
green (on)
• Communication with the bus node o.k.
S
• Bus electronics and sensor supply present
green (blinking)
• Initialisation
• No data exchange
red
Sensor undervoltage or short-circuit
U
green
Actuator supply present
A
red
Actuator undervoltage or short-circuit
off
• No supply for actuators
M
green
Module status o.k.
S
off
Initialisation not yet completed
0 = Pin 4
off
Not online, no further bus elements
1 = Pin 2
red (blinking)
Connection timeout to Master
green (blinking)
Online, but no connection to the Master
red
Bus error / Dop-Mac error
green
Online and connection to the Master
Module data
ODVA – Vendor ID:............42
Product Code ...................564
Part Number ....................FD67NDNM127804
When handling the modules, the users must be free of electrostatics.
4
Provide for appropriate interference suppression
measures when using the device in the vicinity
of residential areas.
Good chemical and oil resistance.
When using aggressive mediums,
material resistance based on
application must be checked.
In order not to damage
the contacts, it is
advisable to cut the
modules from the
bus node while
they are not under
voltage.
FD67NDNM127804
FD67NDNM127804
11/03

Werbung

loading

Inhaltszusammenfassung für Norgren Herion FD67NDNM127804

  • Seite 1 The bus node has integrated LED indication which shows the >2 125 kBit/sec status of the system and the connected modules. The DeviceNet FD67NDNM127804 bus node can be mounted Colour Signification Baud rate setting > 2 means 125 kBit/s operation.
  • Seite 2 BUS IN BUS OUT Gerätenr ………………....... 7 Dez. 24 V Betriebsspannung Anzugsdrehmoment der M3 Schraube: 1,2 ± 0,2 Nm Produktname………………....FD67NDNM127804 CAN_HIGH Die Haube darf nur Spannungsfrei demontiert werden. Der Gute Chemikalien- und Ölbeständigkeit. CAN_LOW laufende DeviceNet Betrieb wird dadurch nicht beeinträchtigt.