RESI-1RS232-
ETH
RESI Informatik & Automation GmbH, Altenmarkt 29, A-8551 Wies, Austria, Tel: +43-316-262062-0, Fax: +43-316-262062-66, Email: help@RESI.cc URL: www.RESI.cc
IMPORTANT: Before you start with the installation of the product, read the attached IMPORTANT SECURITY NOTES very carefully and follow all the herein given information very accurate!
Description:
Ethernet gateway RS232-SOCKET, bidirectional transport of plain socket data to serial RS232 interface, MODBUS/TCP to MODBUS/RTU converter,Size (LxBxH):35.8x90x58mm,Power supply:12-48V=,Power
consumption:0.8W,Housing:2MU,Mounting:mountable onto a EN50022 DIN rail,Ceritification:CE,TARIC number:8538 90 91
Manual:
Read the actual manual for our product very carefully! You will find both things on our homepage
FACTORY SETTINGS:
Unit ID for configuration:
254
IP address:
192.168.0.199
IP mask:
255.255.255.0
Socket:
1024
User name:
RESI
Password:
RESI
Serial line:
9600bd, keine Parität, 8,1
www.RESI.cc
CLAMPS/LEDS RESI-1RS232-ETH
L+
Power supply
M-
L+: 12-48Vdc
M-: Ground
ETHERNET
Ethernet
connection
for
transparent
MODBUS/TCP
or
internet
10M/100Mbit adaptive, support AUTO–MDIX
TX
Interface to serial RS232 line
RX
TX: data transmit signal
GND
RX: data receive signal
GND: ground for serial RS232 line
STATE
State-LED, flashes, when converter is ok
flash rhythm is 1s in normal mode and 0,1s in
configuration mode
RS232
Whenever there is a data flow on the serial
line, this LED flashes for a short time
HOST
HOST-LED, flashes, when host sends/receive
MODBUS/TCP telegrams
CFG
Factory config LED: In normal mode this LED
flashes in the same way like the STATE LED. If
CFG switch=ON while rebooting, the STATE
LED is always ON and this LED flashes slowly.
When this process is finished, both LED blink
very fast.
LINK
This LED is on if Ethernet port is connected
correctly to network
DATA
The LED shows the data flow on the Ethernet
port
DIP Switch
Description
Function
=ON: while restarting the module, the module switches to STATIC IP
FUNC1
configuration with the standard IP settings:
IP address:
192.168.0.199
or
IP mask:
255.255.255.0
Gateway:
192.168.0.1
access.
=OFF: the current configured IP settings are used
Function
=ON: while restarting the module, the module switches to DHCP IP
FUNC2
configuration.
=OFF: the current configured IP settings are used
Mode
Selects a operation mode for factory reset:
MODE
=OFF: While factory reset, the unit is configured to transparent socket
mode
=ON: While factory reset, the unit is configured to MODBUS/TCP to
MODBUS/RTU conversion mode
Factory config
=ON: while restarting the module, the module restores the factory
CFG
defaults for the system. Wait for approx. 30 seconds until the
STATE+CFG LED flashes very fast. Then reset the DIP switch. The
module will restart automatically
=OFF: nothing happens
HINT
After changing the DIP switches the converter reboots immediately,
so no power off or on is necessary. After reboot all the LEDs are on
for half a second to signal the power on sequence.
Technical Conditions
Operating temperature
0...60°C
Storage temperature
-20..+80°C
Humidity
25..90 %rH not condensing
Power supply
12...48Vdc +/-10%
Power consumption
<0.8W
Clamps
Tightening torque max. 0.5Nm
Clamp Wire cross section
max. 1.5mm²
Dimension (LxWxH)
35.8x90x58mm
Weight
90g
Protection class
IP20
Conformity
CE
EN