7.17.2 How to READ program PATTERN
▶ Below describes process step to read programmed PATTERN profile in TEMP2520.
Above process step ① ~ ⑤ is used to read 'ONE SEGMENT'profile among all in programmed pattern.
To read many segments, reiterate ① ~ ⑤ process step by changing segment number.
Setting '0'in D2102 at process step ② will read profile in D2145~D2167.
2nd Edition of TEMP2020_Series IM : Apr. 2014
① Write PATTERN number to read profile in D2101
Write SEGMENT number to read profile in D2102
③ Write READ TRIGGER('2') in D2107
④ Stay until reading D2108 response DONE('1')
⑤ Reads profile(TSP of temp.& humi. process time etc.)in D2126~D2141
Page 51 / 69