01/11 MN03402003Z-DE/EN
Handbuch/Manual
ersetzt/replaces 04/06 AWB1210-1458D/GB
Motorschutzschalter PKZM0/XTPR...BC1
Überlastüberwachung von Ex e-Motoren
Motor-protective circuit-breaker PKZM0/XTPR...BC1
Overload monitoring of Ex e motors

Werbung

Kapitel

Inhaltsverzeichnis
loading

Inhaltszusammenfassung für Eaton PKZM0-0,4/XTPRP40BC1

  • Seite 1 01/11 MN03402003Z-DE/EN Handbuch/Manual ersetzt/replaces 04/06 AWB1210-1458D/GB Motorschutzschalter PKZM0/XTPR…BC1 Überlastüberwachung von Ex e-Motoren Motor-protective circuit-breaker PKZM0/XTPR…BC1 Overload monitoring of Ex e motors...
  • Seite 2 Gefahr! Danger! Gefährliche Dangerous elektrische electrical Spannung! voltage! Vor Beginn der Installationsarbeiten Before commencing the installation • Gerät spannungsfrei schalten • Disconnect the power supply of the device. • Gegen Wiedereinschalten sichern • Ensure relosing interlock that devices cannot be accidentally restarted. •...
  • Seite 3 01/11 MN03402003Z-DE/EN Überblick/Overview Motorschutzschalter PKZM0/XTPR…BC1 PKZM0/XTPR…BC1 motor-protective circuit-breakers Anhang/Appendix...
  • Seite 4: Inhaltsverzeichnis

    01/11 MN03402003Z-DE/EN Inhalt Zu diesem Handbuch Zielgruppe Abkürzungen und Symbole Änderungsprotokoll Motorschutzschalter PKZM0/XTPR…BC1 Vorwort Geräteübersicht Gerätebeschreibung – Überlastschutz mit Motorschutzschaltern – Strombereiche der Motorschutzschalter PKZM0/XTPR…BC1 – Temperaturkompensation – Phasenausfall – Wiedereinschaltung – Testfunktion Projektierung Überlastüberwachung von Ex e-Motoren Einstellung der Überstromschutzeinrichtung Kurzschluss-Schutz der Motorschutzschalter Zulassungen Installation...
  • Seite 5 01/11 MN03402003Z-DE/EN Inhalt Anhang/Appendix Typenschild/Rating plate PKZM0/XTPR…BC1 Auslösekennlinien/Tripping characteristics PKZM0/XTPR…BC1 – PKZM0-0,16/XTPRP16BC1 – PKZM0-0,25/XTPRP25BC1 – PKZM0-0,4/XTPRP40BC1 – PKZM0-0,63/XTPRP63BC1 – PZKM0-1/XTPR001BC1 – PKZM0-1,6/XTPR1P6BC1 – PKZM0-2,5/XTPR2P5BC1 – PKZM0-4/XTPR004BC1 – PKZM0-6,3/XTPR6P3BC1 – PKZM0-10/XTPR010BC1 – PKZM0-12/XTPR012BC1 – PKZM0-16/XTPR016BC1 – PKZM0-20/XTPR020BC1 – PKZM0-25/XTPR025BC1 – PKZM0-32/XTPR032BC1 EG-Konformitätserklärung/Declaration of...
  • Seite 6: Zu Diesem Handbuch

    01/11 MN03402003Z-DE/EN Zu diesem Handbuch Das vorliegende Handbuch gilt für Motorschutzschalter PKZM0/XTPR…BC1. Dieses Handbuch beschreibt die Überlastüberwachung zum Schutz von Motoren in explosiongefährdeten Bereichen (Ex e-Bereichen). Zielgruppe Dieses Handbuch richtet sich an Fachpersonal, das den Motorschutzschalter installiert, in Betrieb nimmt und wartet. Abkürzungen und Symbole In diesem Handbuch werden Abkürzungen und Symbole eingesetzt, die folgende Bedeutung haben: Ex e...
  • Seite 7: Änderungsprotokoll

    Änderungen ergeben. Redaktions- Seite Stichwort geän- ent- datum dert fällt 01/11 allg. Aufnahme der Eaton-Typen allg. EEx e (jetzt: Ex e) Hinweis auf zusätzliche Maßnahmen bei Motoren in explosionsgefährdeten Staub-Luft-Gemischen 7, 16 EG-Baumusterprüfbescheinigungs- Nummer Typenschild/Rating plate EG-Konformitätserklärung/ Declaration of CE Conformity 04/06 Abschnitt „Einstellungen“...
  • Seite 8 01/11 MN03402003Z-DE/EN Änderungsprotokoll Redaktions- Seite Stichwort geän- ent- datum dert fällt Tabelle 4: „Leistungsdaten Nordame- rika der einzelnen Typen“ Tabelle 5 „Weitere Leistungsdaten der einzelnen Typen“ Typ „PKZM0-12/XTPR012BC1“ Typ „PKZM0-32/XTPR032BC1“ „EG-Konformitätserklärung/Declara- tion of CE Conformity (Doc. No.: K 000311)“ 05/02 –...
  • Seite 9 01/11 MN03402003Z-DE/EN...
  • Seite 10: Vorwort

    01/11 MN03402003Z-DE/EN Motorschutzschalter PKZM0/XTPR…BC1 Vorwort Für den Schutz von Motoren in explosionsgefährdeten Bereichen gelten zusätzlich zu den Vorschriften nach EN 60079-14 und VDE 0165 Teil 1 separate Vorschriften für die entsprechenden Zündschutzarten. Für Motoren in der Zündschutzart „e“ „Erhöhte Sicherheit“ verlangt die Vorschrift EN 50019 zusätzliche Maßnahmen.
  • Seite 11: Geräteübersicht

    01/11 MN03402003Z-DE/EN Motorschutzschalter PKZM0/ XTPR…BC1 Geräteübersicht Abbildung 1: Motorschutzschalter PKZM0/XTPR…BC1 a Stromeinstellscheibe Motorstrom b Testeinrichtung Gerätebeschreibung Überlastschutz mit Motorschutzschaltern Die Motorschutzschalter PKZM0/XTPR…BC1 sind dreipolige elektromechanische Motorschutzschalter mit Bimetallen zur Überlastüberwachung. Bei einer Überlastauslösung schaltet der Motorschutz- schalter PKZM0/XTPR…BC1 allpolig den Hauptstromkreis ab.
  • Seite 12 01/11 MN03402003Z-DE/EN Gerätebeschreibung Strombereiche der Motorschutzschalter PKZM0/XTPR…BC1 Die PKZM0/XTPR…BC1 werden mit Hilfe einer Stromein- stellscheibe a (a Abb. 1 auf Seite 8) auf den Motor- nennstrom eingestellt. Mit 15 verschiedenen Typen können Motoren von 0,1 bis 32 A Motornennstrom überwacht werden (a Tabelle 1). Tabelle 1: Strombereiche der PKZM0/XTPR…BC1 Strombereich I...
  • Seite 13: Motorschutzschalter Pkzm0/Xtpr

    01/11 MN03402003Z-DE/EN Motorschutzschalter PKZM0/ XTPR…BC1 Temperaturkompensation Zwei Parameter beeinflussen die Ausbiegung der Bimetalle. Zum einen ist das die Wärme, die proportional zum fließendem Strom erzeugt wird, und zum anderen ist das der Einfluss der Umgebungstemperatur. Der Einfluss der Umgebungstemperatur wird mit Hilfe eines zusätzlichen Bimetalls, das nicht vom Motorstrom durchflossen wird, im Temperaturbereich von -5 bis +40 °C kontinuierlich durch Korrektur des Auslöseweges selbsttätig kompensiert.
  • Seite 14: Wiedereinschaltung

    01/11 MN03402003Z-DE/EN Gerätebeschreibung Soll mit dem PKZM0/XTPR…BC1 ein Wechselstrommotor oder ein Gleichstrommotor überwacht werden, muss der Strom über alle drei Strombahnen geführt werden, um Frühauslösungen zu vermeiden. Abbildung 4: Verdrahtung des Motorschutzschalters für den Schutz von Wechselstrom- oder Gleichstrom- motoren (Reihenschaltung der Bimetallauslöser) (a Abschnitt „Auslösekennlinien/Tripping characteristics PKZM0/XTPR…BC1“...
  • Seite 15 01/11 MN03402003Z-DE/EN...
  • Seite 16: Projektierung

    01/11 MN03402003Z-DE/EN Projektierung Überlastüberwachung von Durch besondere konstruktive Maßnahmen erreicht man bei Ex e-Motoren Motoren die Zündschutzart Ex e. Die Motoren werden auf Basis der höchst zulässigen Oberflächentemperaturen Temperaturklassen zugeordnet. Zusätzlich wird die Erwär- mungszeit t und das Verhältnis Anlaufstrom zu Nennstrom bestimmt und auf dem Motor angegeben.
  • Seite 17: Kurzschluss-Schutz Der Motorschutzschalter

    01/11 MN03402003Z-DE/EN Projektierung Beispiel: I = 6, t = 10 s PKZM0-.../ XTPR...BC1 3-phasig 2-phasig Abbildung 5: Auslösekennlinie des Motorschutzschalters Der Motor wird zuverlässig geschützt. Kurzschluss-Schutz der Die folgende Tabelle 2 zeigt das Kurzschlussausschaltver- Motorschutzschalter mögen der Motorschutzschalter PKZM0/XTPR…BC1. Zur Erhöhung des Schaltvermögens auf 100 kA können Sicherungen vorgeschaltet werden.
  • Seite 18 01/11 MN03402003Z-DE/EN Kurzschluss-Schutz der Motor- schutzschalter Tabelle 2: Schaltvermögen PKZM0/XTPR…BC1 mit Zuordnungsart „1“ und „2“ 230 V 400 V 440 V 500 V 690 V [kA] [kA] [kA] [kA] [kA] 0,16 – 1 Kein vorgeschaltetes Schutzorgan notwendig, da eigenfester Bereich (150 kA) N Nicht erforderlich 1) Bemessungsdauerstrom I 2) Bedingter Bemessungskurzschlussstrom I...
  • Seite 19: Zulassungen

    01/11 MN03402003Z-DE/EN Projektierung Zulassungen Der Motorschutzschalter PKZM0/XTPR…BC1 ist nach der Vorschrift IEC EN 60947 Niederspannungsschaltgeräte gebaut und erfüllt die Forderungen nach der Richtlinie 94/9/EG (ATEX 100a) zum Schutz von Ex e-Motoren. Außerdem können nach EN 50281-1-1 und EN 50281-1-2 Motoren in den Zonen 21 und 22 (Bereiche mit brennbarem Staub) geschützt werden.
  • Seite 20: Installation

    01/11 MN03402003Z-DE/EN Installation Hinweise zur Installation Bei der mechanischen und elektrischen Installation ist die Montageanweisung IL03407011Z (frühere Bezeichnung AWA1210-1925) auf der Innenseite der Kartonverpa- ckung zu beachten. Gefahr! Rücksetzungen dürfen manuell vor Ort oder durch geschultes Personal in der Leitwarte vorgenommen werden.
  • Seite 21 01/11 MN03402003Z-DE/EN Installation Montieren Sie den Motorschutzschalter nur wie in Abb. 7 dargestellt. Abbildung 7: Zugelassene Einbaulagen für Motorschutzschalter PKZM0/XTPR…BC1 Verdrahten Sie die Motorleitungen. > > > > > > Abbildung 8: Hauptstromverdrahtung Folgende maximale Leitungsquerschnitte sind möglich. Tabelle 3: Maximale Leitungsquerschnitte der Motorzuleitungen 1 - 6 mm 1,7 Nm...
  • Seite 22: Geräte Betreiben

    01/11 MN03402003Z-DE/EN Geräte betreiben Einstellungen Vor der Erstinbetriebnahme des Motorschutzschalters muss der Motornennstrom mit Hilfe der Stromeinstellscheibe a am PKZM0/XTPR…BC1 eingestellt werden (a Tabelle 1 auf Seite 9). Test Der Motorschutzschalter verfügt über eine Testeinrichtung b (a Abbildung 1 auf Seite 8). Wird diese Testeinrichtung bei eingeschaltetem Motorschutzschalter mittels eines Schraubendrehers betätigt, löst der PKZM0/XTPR…BC1 aus und alle Hauptkontakte werden geöffnet.
  • Seite 23 01/11 MN03402003Z-DE/EN...
  • Seite 24 01/11 MN03402003Z-DE/EN Contents About this manual Target group Abbreviations and symbols List of revisions PKZM0/XTPR…BC1 motor-protective circuit-breakers Foreword Device overview Description of device – Overload protection with motor-protective circuit-breakers – Current ranges of the PKZM0/XTPR…BC1 motor-protective circuit-breakers – Temperature compensation –...
  • Seite 25 01/11 MN03402003Z-DE/EN Contents Anhang/Appendix Typenschild/Rating plate PKZM0/XTPR…BC1 Auslösekennlinien/Tripping characteristics PKZM0/XTPR…BC1 – PKZM0-0,16/XTPRP16BC1 – PKZM0-0,25/XTPRP25BC1 – PKZM0-0,4/XTPRP40BC1 – PKZM0-0,63/XTPRP63BC1 – PZKM0-1/XTPR001BC1 – PKZM0-1,6/XTPR1P6BC1 – PKZM0-2,5/XTPR2P5BC1 – PKZM0-4/XTPR004BC1 – PKZM0-6,3/XTPR6P3BC1 – PKZM0-10/XTPR010BC1 – PKZM0-12/XTPR012BC1 – PKZM0-16/XTPR016BC1 – PKZM0-20/XTPR020BC1 – PKZM0-25/XTPR025BC1 – PKZM0-32/XTPR032BC1 EG-Konformitätserklärung/Declaration of...
  • Seite 26: About This Manual

    01/11 MN03402003Z-DE/EN About this manual This manual applies to the PKZM0/XTPR…BC1 motor-protective circuit-breakers. It describes the overload monitoring system for the protection of motors operating in potentially explosive atmospheres (Ex e areas). Target group This manual is aimed at specialist personnel who are responsible for the installation, commissioning and maintenance of the motor protective circuit breaker.
  • Seite 27: List Of Revisions

    Page Key word Modi- date fica- leted tion 01/11 General Inclusion of Eaton models General EEx e (now: Ex e) Notes about additional measures for motors in explosive dust–air mixtures 27, 36 EC prototype test certification numbers Typenschild/Rating plate EG-Konformitätserklärung/...
  • Seite 28 01/11 MN03402003Z-DE/EN List of revisions Publication Page Key word Modi- date fica- leted tion table 4: “Rating data of the individual types for North America” table 5 “Further rating data of the individual types” Part no.„PKZM0-12/XTPR012BC1“ Part no.„PKZM0-32/XTPR032BC1“ „EG-Konformitätserklärung/Declara- tion of CE Conformity (Doc. No.: K 000311)“...
  • Seite 29 01/11 MN03402003Z-DE/EN...
  • Seite 30: Motor-Protective Circuit-Breakers

    01/11 MN03402003Z-DE/EN PKZM0/XTPR…BC1 motor-protective circuit-breakers Foreword In addition to the degree of protection specified in the stan- dards EN 60079-14 and VDE 0165 Part 1, further provisions have been made to ensure safety from ignition for motors operated in potentially explosive atmospheres. EN 50019 prescribes additional measures to be taken for the operation motors with “increased safety”...
  • Seite 31: Device Overview

    01/11 MN03402003Z-DE/EN PKZM0/XTPR…BC1 motor- protective circuit-breakers Device overview Figure 1: PKZM0/XTPR…BC1 motor-protective circuit-breakers a Motor current dial b Testing element Description of device Overload protection with motor-protective circuit-breakers The PKZM0/XTPR…BC1 series are 3-phase electromechan- ical motor-protective circuit-breakers with bimetallic release for overload monitoring.
  • Seite 32 01/11 MN03402003Z-DE/EN Description of device Current ranges of the PKZM0/XTPR…BC1 motor- protective circuit-breakers The rated motor current is set on the PKZM0/XTPR…BC1 units by means of a current dial a (a fig. 1, page 28). 15 different types are available for monitoring motors with a rated current from 0.1 to 32 A (a table 1).
  • Seite 33: Temperature Compensation

    01/11 MN03402003Z-DE/EN PKZM0/XTPR…BC1 motor- protective circuit-breakers Temperature compensation Two parameters influence the deflection of the bimetallic releases. There is for one the heat which is generated in proportion to the current flow, and secondly, the influence of the ambient air temperature. The influence of the ambient air temperature is automatically compensated within a temperature range from –5 to +40 °C by means of an addi- tional current-free bimetallic release that continuously...
  • Seite 34: Restarting

    01/11 MN03402003Z-DE/EN Description of device When a PKZM0/XTPR…BC1 is to be used for monitoring an AC or DC motor, the current must flow across all three current paths in order to avoid early tripping. Figure 4: Wiring of the motor-protective circuit-breaker for the protection of AC or DC motors (bimetallic release switched in series) (a section "Auslösekennlinien/Tripping characteristics...
  • Seite 35 01/11 MN03402003Z-DE/EN...
  • Seite 36: Engineering

    01/11 MN03402003Z-DE/EN Engineering Overload monitoring of The Ex e protection of motors is achieved by means of Ex e motors special design measures. The motors are assigned to temper- ature classes on the basis of the highest permissible surface temperatures. The temperature rise time t and the ratio between startup current and rated operational current I are calculated in addition and specified on the rating plate of...
  • Seite 37: Short-Circuit Protection Of The Motor-Protective Circuit-Breakers

    01/11 MN03402003Z-DE/EN Engineering Example: I = 6, t = 10 s PKZM0-.../ XTPR...BC1 3-phase 2-phase 1.5 2 8 10 15 20 Rated current Figure 5: Tripping characteristic for motor-protective circuit-breaker The motor is reliably protected. Short-circuit protection of The following table 2 shows the short-circuit breaking the motor-protective capacity of the PKZM0/XTPR…BC1 motor-protective circuit-breakers...
  • Seite 38 01/11 MN03402003Z-DE/EN Short-circuit protection of the motor-protective circuit- breakers Table 2: Switching capacity of PKZM0/XTPR…BC1 with type of coordination "1" and "2" 230 V 400 V 440 V 500 V 690 V [kA] [kA] [kA] [kA] [kA] 0.16 – 1 No upstream protective device required, as it is the auto-protected range (150 kA) N Not required...
  • Seite 39: Approvals

    01/11 MN03402003Z-DE/EN Engineering Approvals The PKZM0/XTPR…BC1 motor-protective circuit-breaker is compliant with IEC/EN 60947 regulations for low-voltage switchgear and fulfils the requirements of the 94/9/EC (ATEX 100a) directives for the protection of Ex e motors. They can also be used for the protection of motors in accor- dance with EN 50281-1-1 and EN 50281-1-2 motors in Zones 21 and 22 (areas with flammable dust).
  • Seite 40: Installation

    01/11 MN03402003Z-DE/EN Installation Installation Instructions The mechanical and electrical instructional leaflet IL03407011Z (previous description AWA1210-1925) on the inside of the cardboard package must be observed. Danger! Resets may be carried out at the installation or by trained personnel in the control room. Fitting the device f 15 mm (0.59")
  • Seite 41 01/11 MN03402003Z-DE/EN Installation Mount the motor protective circuit breaker only as shown in fig. 7. Figure 7: Approved mounting positions of the PKZM0/ XTPR…BC1 motor-protective circuit-breakers Wire the motor cables. > > > > > > Figure 8: Main circuit wiring The following maximum cable cross sections are possible.
  • Seite 42: Using The Device

    01/11 MN03402003Z-DE/EN Using the device Settings The rated motor current must be set on PKZM0/XTPR…BC1 by means of the current dial a (a table 1, page 29) prior to initial commissioning of the motor-protective circuit- breaker. Test The motor-protective circuit-breaker is equipped with a testing feature b (a figure 1, page 28).
  • Seite 43 01/11 MN03402003Z-DE/EN...
  • Seite 44: Anhang/Appendix

    01/11 MN03402003Z-DE/EN Anhang/Appendix Typenschild/Rating plate PKZM0/XTPR…BC1 SEE DIAL FOR 115 200 230 460 575 V MOTOR FULL- LOAD AMPS – 3 PH BREAK ALL LINES TRIP RATING 1 PH 125 % OF – – DIAL SETTING = 6000 V MAX. RMS SYM AMPS MAX.
  • Seite 45 01/11 MN03402003Z-DE/EN Anhang/Appendix Tabelle/Table 4: Leistungsdaten Nordamerika der einzelnen Typen/ Rating data of the various types for North America Type PK(Z)M0-…(-T) / XTPR…BC1 0,16 / P16 – – – 0,25 / P25 0,4 / P40 0,63 / P63 1 / 001 1,6 / 1P6 A/aj 2,5 / 2P5...
  • Seite 46: Auslösekennlinien/Tripping Characteristics

    01/11 MN03402003Z-DE/EN Auslösekennlinien/Tripping characteristics PKZM0/ XTPR…BC1 Tabelle/Table 5: Weitere Leistungsdaten der einzelnen Typen/ Further rating data of the individual types Type PK(Z)M0-…(-T) / XTPR…BC1 0,16 / P16 0.16 0,25 / P25 0.25 0,4 / P40 0,63 / P63 0.63 1 / 001 1,6 / 1P6 2,5 / 2P5 4 / 004...
  • Seite 47: Pkzm0-0,16/Xtprp16Bc1

    01/11 MN03402003Z-DE/EN Anhang/Appendix PKZM0-0,16/XTPRP16BC1 Bereich/Range 0.1 - 0.16 A (NM - HM) Umgebungstemperatur/Ambient temperature 20 °C Auslöseklasse/Tripping class 10 A Toleranzbereich/Tolerance range g 20 % Einstellung/ Auslösezeit/Tripping time t [s] Setting 3-phase a 2-phase c 3-phase b 2-phase d 3 x I 11.8 7.2 x I...
  • Seite 48: Auslösekennlinien/Tripping Characteristics Pkzm0/Xtpr

    01/11 MN03402003Z-DE/EN Auslösekennlinien/Tripping characteristics PKZM0/ XTPR…BC1 6 7 8 9 10 Abbildung/Figure 10: PKZM0-0,16/XTPRP16BC1...
  • Seite 49: Pkzm0-0,25/Xtprp25Bc1

    01/11 MN03402003Z-DE/EN Anhang/Appendix PKZM0-0,25/XTPRP25BC1 Bereich/Range 0.16 - 0.25 A (NM - HM) Umgebungstemperatur/Ambient temperature 20 °C Auslöseklasse/Tripping class 10 A Toleranzbereich/Tolerance range g 20 % Einstellung/ Auslösezeit/Tripping time t [s] Setting 3-phase a 2-phase c 3-phase b 2-phase d 3 x I 20,5 19.7 11.3...
  • Seite 50 01/11 MN03402003Z-DE/EN Auslösekennlinien/Tripping characteristics PKZM0/ XTPR…BC1 6 7 8 9 10 Abbildung/Figure 11: PKZM0-0,25/XTPRP25BC1...
  • Seite 51: Pkzm0-0,4/Xtprp40Bc1

    01/11 MN03402003Z-DE/EN Anhang/Appendix PKZM0-0,4/XTPRP40BC1 Bereich/Range 0.25 - 0.4 A (NM - HM) Umgebungstemperatur/Ambient temperature 20 °C Auslöseklasse/Tripping class 10 A Toleranzbereich/Tolerance range g 20 % Einstellung/ Auslösezeit/Tripping time t [s] Setting 3-phase a 2-phase c 3-phase b 2-phase d 3 x I 12.5...
  • Seite 52 01/11 MN03402003Z-DE/EN Auslösekennlinien/Tripping characteristics PKZM0/ XTPR…BC1 6 7 8 9 10 Abbildung/Figure 12: PKZM0-0,4/XTPRP40BC1...
  • Seite 53: Pkzm0-0,63/Xtprp63Bc1

    01/11 MN03402003Z-DE/EN Anhang/Appendix PKZM0-0,63/XTPRP63BC1 Bereich/Range 0.4 - 0.63 A (NM - HM) Umgebungstemperatur/Ambient temperature 20 °C Auslöseklasse/Tripping class 10 A Toleranzbereich/Tolerance range g 20 % Einstellung/ Auslösezeit/Tripping time t [s] Setting 3-phase a 2-phase c 3-phase b 2-phase d 3 x I 22.5 14.3 7.2 x I...
  • Seite 54 01/11 MN03402003Z-DE/EN Auslösekennlinien/Tripping characteristics PKZM0/ XTPR…BC1 6 7 8 9 10 Abbildung/Figure 13: PKZM0-0,63/XTPRP63BC1...
  • Seite 55: Pzkm0-1/Xtpr001Bc1

    01/11 MN03402003Z-DE/EN Anhang/Appendix PZKM0-1/XTPR001BC1 Bereich/Range 0.63 - 1 A (NM - HM) Umgebungstemperatur/Ambient temperature 20 °C Auslöseklasse/Tripping class 10 A Toleranzbereich/Tolerance range g 20 % Einstellung/ Auslösezeit/Tripping time t [s] Setting 3-phase a 2-phase c 3-phase b 2-phase d 3 x I 26.5 17.5 7.2 x I...
  • Seite 56 01/11 MN03402003Z-DE/EN Auslösekennlinien/Tripping characteristics PKZM0/ XTPR…BC1 6 7 8 9 10 Abbildung/Figure 14: PZKM0-1/XTPR001BC1...
  • Seite 57: Pkzm0-1,6/Xtpr1P6Bc1

    01/11 MN03402003Z-DE/EN Anhang/Appendix PKZM0-1,6/XTPR1P6BC1 Bereich/Range 1 - 1.6 A (NM - HM) Umgebungstemperatur/Ambient temperature 20 °C Auslöseklasse/Tripping class 10 A Toleranzbereich/Tolerance range g 20 % Einstellung/ Auslösezeit/Tripping time t [s] Setting 3-phase a 2-phase c 3-phase b 2-phase d 3 x I 17.7 15.9 7.2 x I...
  • Seite 58 01/11 MN03402003Z-DE/EN Auslösekennlinien/Tripping characteristics PKZM0/ XTPR…BC1 6 7 8 9 10 Abbildung/Figure 15: PKZM0-1,6/XTPR1P6BC1...
  • Seite 59: Pkzm0-2,5/Xtpr2P5Bc1

    01/11 MN03402003Z-DE/EN Anhang/Appendix PKZM0-2,5/XTPR2P5BC1 Bereich/Range 1.6 -2.5 A (NM - HM) Umgebungstemperatur/Ambient temperature 20 °C Auslöseklasse/Tripping class 10 A Toleranzbereich/Tolerance range g 20 % Einstellung/ Auslösezeit/Tripping time t [s] Setting 3-phase a 2-phase c 3-phase b 2-phase d 3 x I 21.5 7.2 x I...
  • Seite 60 01/11 MN03402003Z-DE/EN Auslösekennlinien/Tripping characteristics PKZM0/ XTPR…BC1 6 7 8 9 10 Abbildung/Figure 16: PKZM0-2,5/XTPR2P5BC1...
  • Seite 61: Pkzm0-4/Xtpr004Bc1

    01/11 MN03402003Z-DE/EN Anhang/Appendix PKZM0-4/XTPR004BC1 Bereich/Range 2.5 - 4 A (NM - HM) Umgebungstemperatur/Ambient temperature 20 °C Auslöseklasse/Tripping class 10 A Toleranzbereich/Tolerance range g 20 % Einstellung/ Auslösezeit/Tripping time t [s] Setting 3-phase a 2-phase c 3-phase b 2-phase d 3 x I 22.1 29.5 7.2 x I...
  • Seite 62 01/11 MN03402003Z-DE/EN Auslösekennlinien/Tripping characteristics PKZM0/ XTPR…BC1 6 7 8 9 10 Abbildung/Figure 17: PKZM0-4/XTPR004BC1...
  • Seite 63: Pkzm0-6,3/Xtpr6P3Bc1

    01/11 MN03402003Z-DE/EN Anhang/Appendix PKZM0-6,3/XTPR6P3BC1 Bereich/Range 4 - 6.3 A (NM - HM) Umgebungstemperatur/Ambient temperature 20 °C Auslöseklasse/Tripping class 10 A Toleranzbereich/Tolerance range g 20 % Einstellung/ Auslösezeit/Tripping time t [s] Setting 3-phase a 2-phase c 3-phase b 2-phase d 3 x I 22.5 32.5 7.2 x I...
  • Seite 64 01/11 MN03402003Z-DE/EN Auslösekennlinien/Tripping characteristics PKZM0/ XTPR…BC1 6 7 8 9 10 Abbildung/Figure 18: PKZM0-6,3/XTPR6P3BC1...
  • Seite 65: Pkzm0-10/Xtpr010Bc1

    01/11 MN03402003Z-DE/EN Anhang/Appendix PKZM0-10/XTPR010BC1 Bereich/Range 6.3 - 10 A (NM - HM) Umgebungstemperatur/Ambient temperature 20 °C Auslöseklasse/Tripping class 10 A Toleranzbereich/Tolerance range g 20 % Einstellung/ Auslösezeit/Tripping time t [s] Setting 3-phase a 2-phase c 3-phase b 2-phase d 3 x I 31.5 20.5 17.5...
  • Seite 66 01/11 MN03402003Z-DE/EN Auslösekennlinien/Tripping characteristics PKZM0/ XTPR…BC1 6 7 8 9 10 Abbildung/Figure 19: PKZM0-10/XTPR010BC1...
  • Seite 67: Pkzm0-12/Xtpr012Bc1

    01/11 MN03402003Z-DE/EN Anhang/Appendix PKZM0-12/XTPR012BC1 Bereich/Range 8 - 12 A (NM - HM) Umgebungstemperatur/Ambient temperature 20 °C Auslöseklasse/Tripping class 10 A Toleranzbereich/Tolerance range g 20 % Einstellung/ Auslösezeit/Tripping time t [s] Setting 3-phase a 2-phase c 3-phase b 2-phase d 3 x I 27.3 20.8 24.5...
  • Seite 68 01/11 MN03402003Z-DE/EN Auslösekennlinien/Tripping characteristics PKZM0/ XTPR…BC1 6 7 8 9 10 Abbildung/Figure 20: PKZM0-12/XTPR012BC1...
  • Seite 69: Pkzm0-16/Xtpr016Bc1

    01/11 MN03402003Z-DE/EN Anhang/Appendix PKZM0-16/XTPR016BC1 Bereich/Range 10 - 16 A (NM - HM) Umgebungstemperatur/Ambient temperature 20 °C Auslöseklasse/Tripping class 10 A Toleranzbereich/Tolerance range g 20 % Einstellung/ Auslösezeit/Tripping time t [s] Setting 3-phase a 2-phase c 3-phase b 2-phase d 3 x I 22.5 19.5 7.2 x I...
  • Seite 70 01/11 MN03402003Z-DE/EN Auslösekennlinien/Tripping characteristics PKZM0/ XTPR…BC1 6 7 8 9 10 Abbildung/Figure 21: PKZM0-16/XTPR016BC1...
  • Seite 71: Pkzm0-20/Xtpr020Bc1

    01/11 MN03402003Z-DE/EN Anhang/Appendix PKZM0-20/XTPR020BC1 Bereich/Range 16 - 20 A (NM - HM) Umgebungstemperatur/Ambient temperature 20 °C Auslöseklasse/Tripping class 10 A Toleranzbereich/Tolerance range g 20 % Einstellung/ Auslösezeit/Tripping time t [s] Setting 3-phase a 2-phase c 3-phase b 2-phase d 3 x I 25.5 7.2 x I...
  • Seite 72 01/11 MN03402003Z-DE/EN Auslösekennlinien/Tripping characteristics PKZM0/ XTPR…BC1 6 7 8 9 10 Abbildung/Figure 22: PKZM0-20/XTPR020BC1...
  • Seite 73: Pkzm0-25/Xtpr025Bc1

    01/11 MN03402003Z-DE/EN Anhang/Appendix PKZM0-25/XTPR025BC1 Bereich/Range 20 - 25 A (NM - HM) Umgebungstemperatur/Ambient temperature 20 °C Auslöseklasse/Tripping class 10 A Toleranzbereich/Tolerance range g 20 % Einstellung/ Auslösezeit/Tripping time t [s] Setting 3-phase a 2-phase c 3-phase b 2-phase d 3 x I 29.5 7.2 x I...
  • Seite 74 01/11 MN03402003Z-DE/EN Auslösekennlinien/Tripping characteristics PKZM0/ XTPR…BC1 6 7 8 9 10 x I r Abbildung/Figure 23: PKZM0-25/XTPR025BC1...
  • Seite 75: Pkzm0-32/Xtpr032Bc1

    01/11 MN03402003Z-DE/EN Anhang/Appendix PKZM0-32/XTPR032BC1 Bereich/Range 26 - 32 A offen/open (NM - HM) 26 - 30 A gekapselt/ encapsulated (NM - HM) Umgebungstemperatur/Ambient temperature 20 °C Auslöseklasse/Tripping class 10 A Toleranzbereich/Tolerance range g 20 % Einstellung/ Auslösezeit/Tripping time t [s] Setting 3-phase a 2-phase c...
  • Seite 76 01/11 MN03402003Z-DE/EN Auslösekennlinien/Tripping characteristics PKZM0/ XTPR…BC1 6 7 8 9 10 Abbildung/Figure 24: PKZM0-32/XTPR032BC1...