Herunterladen Diese Seite drucken
Verfügbare Sprachen

Verfügbare Sprachen

USER INSTRUCTIONS
English
Isolation Amplifier
DB 68
Read these instructions before using the product and retain for future information.
DB 68
1. Before Startup
When operating the isolating amplifier, certain parts of
the module can carry dangerous voltage! Ignoring the
warnings can lead to serious injury and/or cause
damage!
The isolation amplifier should only be installed and
put into operation by qualified staff. The staff must
have studied the warnings in these operating
instructions thoroughly.
In applications with high working voltages sufficient
distance and isolation as well as shock protection
must be ensured.
Safe and trouble-free operation of this device can
only be guaranteed if transport, storage and
installation are carried out correctly and operation
an maintenance are carried out with care.
Appropriate safety measures against electrostatic
discharge (ESD) should be taken during range selection
and assembly on the transmitter.
2. Short Description
The 3-way isolation amplifier is used for electrical isolation and
conversion of bipolar and unipolar process signals. The signal
combination is selected by the Order No.
The 3-way isolation guarantees reliable decoupling of the sensor
circuit from the processing circuit and prevents linked measurement
circuits from influencing each other. The Protective Separation with
high isolation level
provides protection for personnel
downstream devices against impermissibly high voltage.
3. Functioning
The input signal is modulated and then electrically decoupled using
a transformer. The isolated signal is then made available at the
output, demodulated, filtered and amplified.
5. Mounting, Electrical Connection
The isolation amplifier is mounted on standard 35 mm DIN rail.
Terminal assignments
1
Input +
5
Output +
2
Input -
6
Output -
Power supply ≅
3
7
Power supply ≅
4
8
8. Block Diagram
7. Technical Data
Input
Input signal
0 - 10 V
0 - 5 V
(see Product line)
2 - 10 V
1 - 5 V
± 10 V
± 5 V
5 Ω
Input resistance
Current input
Voltage input
1 MΩ
≤ 200 mA
Current input
Overload
Voltage input
≤ 250 V
and
Output
Output signal
0 - 10 V
0 - 5V
(see Product line)
2 - 10 V
1 - 5V
≤ 500 Ω
Load
Current output
≥ 2 kΩ
Voltage output
Ripple
< 10 mV
rms
General data
Transmission error
< 0.2 % full scale
1)
Temperature coefficient
< 0.02 % /K
± 3 %
Zero/Span Compensation
Cut-off frequency -3 dB
500 Hz
Response time
< 2 ms
Test voltage
3 kV AC, 50 Hz, 1 min.
input against output against power supply
2)
Working voltage
600 V AC/DC for overvoltage category II and
(Basic insulation)
pollution degree 2 acc. to EN 61010-1
Protection against
Protective separation according to EN 61140 by
2)
dangerous body currents
reinforced
insulation
EN 61010-1 up to 300 V AC/DC for overvoltage
category II and pollution degree 2 between all
circuits.
Ambient temperature
Operation
-20 to + 60 °C (-4 to +140 °F)
Transport
-35 to + 85 °C (-31 to +185 °F)
and storage
Power supply
24 V AC/DC
AC 48 ... 62 Hz, approx. 2 VA
± 15 %
DC approx. 0,7 W
3)
EMC
EN 61326 -1
Construction
11,2 mm (0.44'') housing, protection type: IP 20
≤ 2.5 mm
Connection
2
, AWG 14
Weight
Approx. 50 g
1) Average TC related to full scale value in specified operating temperature
range, reference temperature 23 °C
2) As far as relevant the standards and rules mentioned above are considered
by development and production of our devices. In addition relevant assembly
rules are to be considered by installation of our devices in other equipments.
For applications with high working voltages, take measures to prevent
accidental contact and make sure that there is sufficient distance or insulation
between adjacent situated devices.
3) Minor deviations possible during interference
6. Order Information
Device
Isolation Amplifier
DB 68 P -
Input
0 ... 10 V
2 ... 10 V
± 10 V
0 ... 5 V
1 ... 5 V
± 5 V
0 ... 20 mA
4 ... 20 mA
± 20 mA
± 10 mA
Output
0 ... 10 V
2 ... 10 V
0 ... 5 V
1 ... 5 V
0 ... 20 mA
4 ... 20 mA
cross-connector
for looping through the power
supply for up to 10 units,
(2 pcs.)
splittable
8. Dimensions
± 10 mA
0 - 20 mA
4 - 20 mA
± 20 mA
0 - 20 mA
4 - 20 mA
in
accordance
with
LIMITED WARRANTY
DRAGO Automation GmbH hereby warrants that the Product
will be free from defects in materials or workmanship for a
period of five (5) years from the date of delivery ("Limited
Warranty"). This Limited Warranty is limited to repair or
replacement at DRAGO's option and is effective only for the
first end-user of the Product. This Limited Warranty applies
only if the Product:
1. is installed according to the instructions furnished by DRAGO;
2. is connected to a proper power supply;
3. is not misused or abused; and
Order No.
4. there is no evidence of tampering, mishandling, neglect,
accidental damage, modification or repair without the
X
X
approval of DRAGO or damage done to the Product by
anyone other than DRAGO.
0
6
Delivery conditions are based upon the „GENERAL
1
CONDITIONS FOR THE SUPPLY OF PRODUCTS AND
3
SERVICES OF THE ELECTRICAL AND ELECTRONICS
7
INDUSTRY"
recommended
2
Elektrotechnik- und Elektronikindustrie (ZVEI) e.V. .
8
9
4
5
Subject to change!
6
7
DRAGO Automation GmbH
5
Waldstrasse 86 - 90
8
2
13403 BERLIN
4
GERMANY
DZU 0801
Phone:
+49 (0)30 40 99 82 - 0
Fax:
+49 (0)30 40 99 82 - 10
E-Mail:
info@drago-automation.de
Internet: www.drago-automation.de
by
the
Zentralverband
loading

Inhaltszusammenfassung für Drago Automation DB 68

  • Seite 2 2) Die angeführten Normen und Bestimmungen werden bei der Entwicklung und BESCHRÄNKTE GARANTIE Herstellung unserer Produkte berücksichtigt, soweit sie anwendbar sind. Die DRAGO Automation GmbH garantiert hiermit, dass das Errichtungsbestimmungen sind beim Einbau unserer Produkte in Geräte und Produkt über einen Zeitraum von fünf (5) Jahren ab Liefer- Anlagen zusätzlich...