Power factor controller
POWER FACTOR CONTROLLER
RG-6T
5. CONTROLS AND MENU OPERATIONS
All settings are made by Menu. The set values except operating mode are kept in memory
even if the device is switched off.When it is switched on, it starts compensation with the
values stored in the memory in Automatic Operating Mode. After entering Menu by pressing
SET button for 3 seconds and if you don't make any adjustments during 20 seconds ,RG-
6T operates with the previously stored values.
To quit Menu without any storing operation, UP or DOWN buttons are pressed
until the ESC symbol is displayed and then SET button is pressed.
The details of controls and adjustments are explained in the following sections.
5.1 Selection of Operating Mode(Automatic / Manual Mode )
Two Operating Modes are available for switching on/off the capacitor steps.
1) Automatic Operating Mode: The capacitor steps are controlled by RG-6T, automatically.
2) Manual Operating Mode: the capacitor steps are switched on/off, manually.
RG-6T returns to Automatic mode if any button is not pressed within 5 minutes.
Mode selection is done as followed.
By pressing SET button 3 seconds SET Menu is started.
SET
AUTO/MAN light is selected by using UP-DOWN
DOWN
buttons.
symbol is displayed.
UP
AUTO/MAN setting is selected by pressing SET
button. If the device is in Manual Mode,
SET
symbol is displayed.If the device is in Automatic
Mode,
symbol is displayed.
DOWN
Automatic Mode (
) or Manual Mode (
selected by using UP-DOWN buttons.
UP
When targeted operating mode is displayed, it is selected by pressing SET button. If
SET
Manual Mode is selected, AUTO/MAN light starts blinking and blinks during this mode.If
Automatic Mode is selected, AUTO/MAN light is continuouslly ON during this mode.
5.1.1 Switching of the Capacitor Steps Manually
When RG-6T is in Manual Mode, capacitor steps are connected by pressing UP button.
Each time UP button is pressed, C+ light turns ON and one step is connected accordingly;
NORMAL light will be ON after the connection of the step. This operation must be repeated
to connect more steps.
Capacitor steps are disconnected by pressing DOWN button. Each time UP button is
pressed, C- light turns ON and one step is disconnected after a delay time; NORMAL light
will be ON after the disconnection of the step.This operation must be repeated to disconnect
more steps.
5.2 Automatic C/k Adjustment
C/k adjustment is started by pressing UP-DOWN
DOWN
buttons together.
UP
5.3 Cosϕ Adjustment
By pressing SET button 3 seconds, SET
SET
Menu is started.
Display
Cosϕ light is selected by using UP
DOWN
and DOWN buttons. COS symbol is
UP
displayed
Cosϕ adjustment is selected by pressing
SET
SET button. Previously adjusted value
is shown at the display.
A value between 0.85-1.00 is adjusted
DOWN
by using UP-DOWN buttons.
UP
When targeted value is displayed, it is strored
SET
by pressing SET button and RG-6T returns to
its normal operating mode.
Display
R G - 6 T
) is
5.4 Step Time Adjustment
SET
DOWN
UP
SET
DOWN
UP
SET
5.5 Step Number Selection
By pressing SET button 3 seconds, SET
Menu is started.
SET
M
W
VAr
OVER V.
VA
STEP light is selected by means of
DOWN
UP-DOWN buttons. StEP symbol is displayed.
UP
STEP number adjustment is selected by pressing
SET button.Previously selected value is shown on
SET
the display
A preferred step number is selected by
DOWN
means of UP-DOWN buttons.
UP
When targeted value is displayed, it is stored by
pressing SET button and RG-6T returns to its
SET
normal operating mode.
5.6 Switching Program Selection
SET
DOWN
UP
SET
DOWN
UP
SET
5.7 Selection of C/k Value by the User
SET
DOWN
UP
SET
DOWN
UP
SET
2
By pressing SET button 3 seconds, SET Menu is started.
Display
TIME light is selected by means of
UP-DOWN buttons.
While TIME light is ON, t 0n symbol is displayed by
means of UP-DOWN buttons and time delay
adjustment for connection of capacitor steps to system
is selected by pressing SET button.
While TIME light is ON, t 0F symbol is displayed by
means of UP-DOWN buttons and time delay
adjustment for disconnection of capacitor steps to
system is selected by pressing SET button.
A value between 2-1800 sec. is adjusted by
using UP-DOWN buttons.
When targeted value is displayed, it is stored by pressing SET button and
RG-6T returns to its normal operating mode.
Display
By pressing SET button 3 seconds, SET Menu is started.
Display
PROGRAM light is selected by means
of UP-DOWN buttons.
symbol is
displayed.
Switching Program is selected by
p r e s s i n g S E T b u t t o n . P r e v i o u s l y
selected value is shown on the display
A value between PS1-PS5 is selected by
using UP-DOWN buttons.
When targeted program is displayed, it is stored by pressing SET button
and RG-6T returns to its normal operating mode.
By pressing SET button 3 seconds, SET Menu is started.
Display
C/ k light is selected by means of
UP-DOWN buttons.
symbol is
displayed.
Manual C/ k adjustment is selected by pressing
SET button. Previously manually selected or
automatically calculated C/ k value is shown
on the display
A value between 0.02-1 is selected by
using UP-DOWN buttons.
When targeted value is displayed, it is stored by
pressing SET button and RG-6T returns to its
normal operating mode.
M
W
VAr
VA
OVER V.
loading