DXH
KANALFEUCHTEFÜHLER /
SCHALTER
MODBUS REGISTER INHALTSVERZEICHNIS
INPUT REGISTERS
1
Temperature level
2
Relative humidity level
3
Dew point
4-10
11
Analogue output value
12
Relay status
13
Relative humidity range
14
Setpoint
15
Hysteresis
16
Setpoint out of range
17-19
Humidity sensor
20
communication lost
HOLDING REGISTERS
1
Device slave address
2
Modbus baud rate
3
Modbus parity
4
Device type
5
HW version
6
FW version
7
Operating mode
8
Output overwrite
9-10
11
Relative humidity range
Minimum custom relative
12
humidity range
Maximum custom relative
13
humidity range
14
Setpoint
15
Hysteresis
16-20
Analogue output overwrite
21
value
22-30
Um mehr zu erfahren über Modbus und über serielle Schnittstelle, folgen Sie diesem Link:
MIW-DXH-DE-000 - 12 / 10 / 15
Data type
Description
signed int.
Actual temperature level
unsigned int.
Actual relative humidity level
signed int.
Calculated dew point
Reserved, returns 0
signed int.
Value of the analogue output
signed int.
Relay status. When it is On, the contact between COM1 and NO1 is closed.
signed int.
Relative humidity working range selected by a jumper or a holding register
signed int.
Setpoint selected by a trimmer or a holding register
signed int.
Hysteresis for relative humidity relay switching
signed int.
Flag that shows if the relative humidity setpoint is out of the working range
Reserved, returns 0
unsigned int.
Flag that shows if the communication with humidity sensor module is lost
Data type
Description
unsigned int.
Modbus device address
unsigned int.
Modbus communication baud rate
unsigned int.
Parity check mode
unsigned int.
Device type (Read only)
unsigned int.
Hardware version of the device (Read only)
unsigned int.
Firmware version of the device (Read only)
Enables the Modbus control and disables the jumpers
unsigned int.
and trimmers
Enables the direct control over the outputs. Always
unsigned int.
settable. Active only if holding register 7 is set to 1.
Reserved, returns 0
Selects the relative humidity working range. Always
signed int.
settable. Active only if holding register 7 is set to 1.
Minimum value of the custom relative humidity range.
signed int.
Always settable. Active only if holding register 7 is set
to 1 and register 11 is set to 5.
Maximum value of the custom relative humidity
signed int.
range. Always settable. Active only if holding register
7 is set to 1 and register 11 is set to 5.
Selected setpoint for relay switching. Always
signed int.
settable. Active only if holding register 7 is set to 1.
Selected hysteresis for relay switching. Always
signed int.
settable. Active only if holding register 7 is set to 1.
Reserved, returns 0
Overwrite value for the analogue output. Always
signed int.
settable. Active only if holding registers 7 and 8 are
set to 1.
Reserved, returns 0
inhaltsverzeichniss
Data
http://www.modbus.org/docs/Modbus_over_serial_line_V1_02.pdf
www.sentera.eu
Data
Values
1.000 =
0—1.000
1.000 =
0—1
1—5
0—1.000
1—5
0—1
0—1
Default
Values
1—247
1
1—4
2
0—2
1
DXH-X = 1032
XXXX
0 x 0100 =
XXXX
0 x 0140 = FW version 1.40
0—1
0
0—1
0
1—5
1
0—Max
0
200 =
Min—1.000
1.000
1.000 =
0—1.000
500
500 =
1—5
3
0—1.000
0
1.000 =
500 =
50,0 °C
100,0 % rH
200 =
20,0 °C
0 =
0 %
100 %
0 =
Off
1 =
On
1 =
20—90 % rH
2 =
0—60 % rH
3 =
0—80 % rH
4 =
0—100 % rH
5 =
Custom
500 =
50,0 % rH
1 =
1,0 % rH
2 =
3,0 % rH
3 =
5,0 % rH
4 =
7,0 % rH
5 =
10,0 % rH
0 =
No
1 =
Yes
0 =
No
1 =
Yes
1 =
9.600
2 =
19.200
3 =
38.400
4 =
57.600
0 =
8N1
1 =
8E1
2 =
8O1
HW version 1.10
0 =
Standalone Mode
1 =
Modbus Mode
0 =
Disabled
1 =
Enabled
1 =
20—90 % rH
2 =
0—60 % rH
3 =
0—80 % rH
4 =
0—100 % rH
5 =
Custom
20,0 % rH
100,0 % rH
50,0 % rH
1 =
1,0 % rH
2 =
3,0 % rH
3 =
5,0 % rH
4 =
7,0 % rH
5 =
10,0 % rH
0 =
0 %
100 %
8 - 9