Fortsetzung Beschreibung der Software
Binary Input Object 1...4
Property
Remark / Value
Object_Identifier
binary-input, instance 1 ... 4
Object_Type
BINARY_INPUT (3)
Object_Name
max. 42 Bytes, default "Input 1" ... "Input 4"
Description
max. 84 Bytes, default ""
INACTIVE (0) / ACTIVE (1),
Present_Value
writable if Out_Of_Service
IN_ALARM: 0
FAULT:
0
Status_Flags
OVERRIDDEN:
OUT_OF_SERVICE:
Event_State
NORMAL (0)
Out_Of_Service
FALSE (0) / TRUE (1)
Polarity
NORMAL (0) / REVERSE (1)
Inactive_Text
max. 20 Bytes, default "Off"
Active_Text
max. 20 Bytes, default "On"
Unsubscribed UnconfirmedCOVNotification
0: no COV notification, default,
Notification_Class
1: local broadcast,
2: global broadcast
R: Read Property, W: Write Property, -E: Storage in EEPROM / Flash
Function Table for Binary Input
Out_Of_Service
Polarity
Binary Input
0
0
0
1
0
0
1
1
0
1
0
1
0
1
1
1
x: Present_Value is writable and not affected by inputs
Group Object 1...3
Property
Remark / Value
Object_Identifier
group, instance 1 ... 3
Object_Type
GROUP (11)
Object_Name
max. 42 Bytes, default "Group 1" ... "Group 3"
Description
max. 84 Bytes, default ""
Present_Value of Binary Inputs,
Present_Value
see next Table
List_Of_Group_Members
see next Table
R: Read Property, W: Write Property, -E: Storage in EEPROM / Flash
Members of Groups
Binary Input
Group
1
2
3
4
1
x
x
x
x
2
x
x
3
x
x
METZ CONNECT GmbH | Im Tal 2 | 78176 Blumberg | Deutschland
Tel. +49 7702 533-0 | Fax +49 7702 533-433
Montageanleitung siehe www.metz-connect.com
0
0 / 1
Present_Value
OUT_OF_SERVICE
0
0
1
1
0
0
x
1
x
1
RW
R
R
RW-E
RW-E
R
RW
R
R
RW
RW-E
RW-E
RW-E
RW-E
RW
R
R
RW-E
RW-E
R
R