Thank you for choosing the McGuard professional presence sensor from
GROTHE GmbH. This new generation of presence sensors provides you a better
performance in security and comfort and a quick and easy installation. With
the presence sensor you can control your light, heating, air condition, alarm
systems, etc. individually. No waste of Energy – get a higher and more secure
living standard.
General Information
The movement sensors McGuard professional with 120° / 240° / 360° detection
area are passive infrared sensors which react to moving sources of heat (peo-
ple, vehicles). If the movement sensor detects changes to the heat radiation in
its detection area, it switches on, depending on the light value of the load con-
nected (e. g. lighting), for an adjustable duration. If the heat source then exists
the detection area, the movement sensor switches the load off again after a
time you have pre-selected (3sec. – 20min.).
Short-term pulse function (for timers, gongs etc.)
An added feature of the installation is offered by the short –term pulse function;
this can be activated by an integrated potentiometer located underneath the
cover ring of the sensor. This way. e. g. automated stairwell lights in larger buil-
dings can be activated automatically or lights in rooms with changing ambient
light can be operated more energy-efficiently.
Installation / Mounting / Connection
- The optimum mounting height is 3m (minimum height 2,50m).
- The movement sensor McGuard professional can be mounted on the wall ort
he ceiling without additional devices. For ceiling mount, the two part senor
must be turned 180° against itself (Fig. 1).
- With the attached corner adapter is it possible to mount the movement sensor
on interior or exterior corners (Fig. 2).
NOTE:
The movement sensor must always be fastened so that the sensor points
downwards.
Electrical connections:
Standard operation (Fig. 3)
Parallel connection (Fig. 4)
Parallel connection and staircase timer (advice Grothe TA 220D, Fig. 5)
Connection with inductors e. g. relays, protectors, ballast equipment (use a
fuse may be necessary, Fig. 6).

NOTES ON SAFETY:

Prior to working an any electrical equipment, always isolate from the electrical
supply (remove fuse / switch off at the main switch). Check that there is no
voltage present. Any installation work must only be carried by a competent
electrician in this voltage-free conditions.
Commisioning and Adjustment
After successful mounting and switching on the main supply, the device
carries out a self-test cycle which lasts approx. 30sec.; this signals that the
connected load is switched on.
After this period has elapsed, the device is ready for operation. With detec-
tion, the focus LED stays permanently (Fig. 7). In test mode, the focus LED light
up permanently and the load is switched on for approx. 2 sec. In short-pulse
mode, the focus LED blinks and the load is active for 0.5 sec., after that, it is
inactive for 9 sec. The adjustment elements are covered in the housing (Fig. 7).
Set the LUX setting to „TEST" (Fig. 7.1). For the adjustment of the detection
area to the local circumstances, you have following possibilities:
Horizontal swivelling of the head by approx. +/- 90°. Middle position is indica-
ted by a notch (Fig. 7).
Range regulation per sensor field via line on potentiometer (Fig. 7.2). Setting is
indicated visually via the focus LED.
Use of the foils for the purposeful hiding of areas (Fig. 8).
Setting element on time-duration (Fig. 7.3)
On-time duration can be set: Impulse, 3 sec. – 20 min.
Short-time pulse function means a switch-on duration of approx. 0,5 sec, follo-
wing by a pause time of approx. 9 sec. In which no movements are detected.
The focus LED is switched on once per sequence for 2 sec. After the pause
time has elapsed, a detected movement starts a new sequence. Suitable, e. g.
for the activation of a gong.
Practical Tips
• Optional function (max. range) is achieved if the mounting is sideways to the
direction of movement (Fig. 9).
• Heed the line of site to the sensor since infrared radiation cannot penetrate
fixed objects.
• In order not to influence the installed light sensor, adhere to a minimum dis-
tance of 1m to the connected lighting and light sources must not be directed
directly at the sensor.
• Consider local circumstances such as neighbour land, distance to the street
or street lighting.
• Unwanted switching on can be triggered, e. g. by small animals or by trees
and bushes moved by the wind in the detection area.
• Through frontal movement towards the sensor, the range can be shortened
significantly (Fig. 10).
Guarantee
McGuard professional is manufactured according to the latest techniques and
subjected to quality control. If however, a defect should occur, GROTHE GmbH
provides a warranty to the following extent.
1.) The warranty covers 24 months from date of purchase of the device by the
final end user. Compliance with the claim deadline is to be demonstrated by
voucher of purchase date by means of an included invoice, delivery note, or
similar document.
2.) The guarantee includes the correction or resupply of a device (according
to our direction) if the function of the device is limited or non existing due to
proven material or manufacturing errors.
3.) The warranty does not cover damage during the transport. Moreover, da-
mages on account of not following the instruction concerning installation and
unprofessional installation of the device.
Product specifications may be subject to change without prior notice.
WARNING
A circuit breaker (250VAC, 10A) type C
according to EN60898-1 of load shall be
installed in the fixed wiring for protection.