10� Technical specifications
Dimensions
Surface-mounted installation, round Ø
(L × W × H)
Surface-mounted installation, square
Concealed installation, round Ø
Concealed installation, square
Output
Incandescent lamps, max. 2000 W at 230 V AC
Fluorescent lamps, max. 1000 W
at cos j = 0.5, inductive load at 230 V AC
8 x max. 58 W each, C ≤ 176 µF
*
at 230 V AC
Mains power supply
220-240 V, 50 / 60 Hz max. 2.5 mm
Angle of coverage
360° with 180° angle of aperture
Application
inside buildings
Sensor system
5.8 GHz high frequency
Transmitter power
approx. 1 mW
Time setting
5 s - 15 min + pulse mode (approx. 2 s)
Twilight setting
2 – 1000 lux + teach mode
Manual override
selectable (4 h)
(permanent light)
IP rating
Surface-mounted: IP54 Concealed: IP20
Temperature range
- 20°C to + 50°C
*
Fluorescent lamps, low-energy lamps, LED lights with electronic ballast
(total capacity of all ballasts connected below the level stated).
126 × 52 mm
95 × 95 × 52 mm
124 × 64 mm
94 × 94 × 64 mm
2
26
11� Troubleshooting
Malfunction
Cause
No power at the sensor
n Fuse faulty, not
switched ON
n Short circuit
n Additional two-way
switch OFF
n Fuse faulty
Sensor will not switch ON
n Bulb faulty
n Twilight setting
set to night-time mode
during daytime oper-
ation
n Additional two-way
switch OFF
n Fuse faulty
Sensor will not switch OFF
n Continuous movement
in the detection zone
n Manual override activat-
ed (red LED lights up)
n Another sensor is par-
allel-connected and still
active
Sensor keeps switching
n Curtains, plants etc.
ON/OFF
moving in the sensor's
detection zone causing
the sensor to respond
LED flashes rapidly
n Load connected is too
(approx. 5 × per second)
high
Remedy
n Replace fuse, turn ON
power switch, check
lead with voltage tester
n Check connections
n Switch ON
n Fit new fuse, check
connections if neces-
sary
n Change bulb
n Adjust setting
n Switch ON
n Fit new fuse, check
connection if necessary
n Check zone
n Deactivate manual
override
n Wait for time setting
of the other sensor to
elapse
n Check zone
n Reduce load or use
contactor