Herunterladen Diese Seite drucken

External Control; Factory Settings - KHS KEMPER -HS2 Einbau- Und Bedienungsanleitung

Hygienespülung

Werbung

Commissioning
Requirements
The commissioning and fault analysis of the
KHS-Hygiene Flushing Box 2 are carried out
by a smartphone and the KEMPER HS2 app.
The KEMPER
HS2
free for Android and iOS smartphones in the
respective
App
The app communicates via Bluetooth interface
with the KHS-Hygiene Flushing Box 2
Commissioning with
KEMPER HS2 app
When installed and connected, the red LED of
the KHS-Hygiene Flushing Box 2 is blinking till
first commissioning.
1
Install KEMPER HS2 app on your
smartphone. Scan QR code or go
to
hs2app.kemper-olpe.de
install.
2
Start
KEMPER
perform the following steps.
3
Connect smartphone to KHS Hygiene
Flushing Box 2 via Bluetooth.
4
Enter the menu <hardware setup>.
Check the settings and change them if
required.
5
Enter the menu <operating
modes>. Configure the
operating times.

External control

The KHS-Hygiene Flushing Box 2 can be
activated externally via a KHS-Mini System
Control or a building management system.
In this case, a direct configuration is not
required. The KHS-Hygiene Flushing Box 2 can
be set up and operated by the external control.
For more information about the
external control, please see the
documentation
System
Control
kit's.
KEMPER KHS-HS2
app
is
available
for
Store
(see
QR-code).
.
to
HS2
app
and
of
the
KHS-Mini
and
Connection

Factory settings

The factory settings of the KHS-Hygiene
Flushing Box 2 are shown in table 1. This is
the valid program if nothing else is configured.
Table 1: Factory settings
Parameter
Description
Flushing
Time between two
interval
flushings
Flushing
Duration of a flush
time
It is recommended to set up a project
specific
program
Flushing Box 2, as each water installation has
different characteristics.
Display of operating mode
The control unit of the KHS-Hygiene Flushing
Box
2
displays
the
states:
Table 2: Operating modes
Element
Status
LED green Short blinking
pulse
Long blinking
pulse
On
Off
LED red
On
Blinking
Off
Buzzer
On 1)
Off
Button
Activated
<Test>
1)
The buzzer can be put to snooze mode with the button
<TEST>. If the error still exists after 24 hours, the buzzer
is activated again.
Use the KEMPER HS2 app for fault
analysis and error acknowledgement.
20
EN
Value
48 h
3 min
for
the
KHS-Hygiene
following
operating
Meaning
In normal operation,
operating voltage on
In normal operation,
Bluetooth interface
aktive
Solenoid valve open
Operating voltage off
Fault (analysis with
KEMPER HS2 app
required)
Warning (analysis
with KEMPER HS2 app
required)
In normal operation
Fault (analysis with
KEMPER HS2 app
required)
In normal operation
Test solenoid valves
With active
Bluetooth-interface:
Disconnect connection
At fault: snooze
buzzer

Werbung

loading