Product description
The SIM-KNX DINRAIL data servers (with 128 or 254 objects) provide
the possibility of connecting arbitrary end devices having a serial
interface and units that have a microcontroller to KNX TP. In this way,
non-KNX end devices become operable via KNX.
Communication is performed via a simple ASCII protocol. The operating
modes RAW Mode, Interoperability Mode and Transparent Mode are
available. The KNX-certified communication system including all
necessary functions for converting KNX datapoint types is already
contained. Transmission properties can be configured for every group
object separately.
The SIM-KNX DINRAIL is a rail-mounted device for installation in
distribution boards on 35 mm DIN rails. Supplied by the KNX bus line
the device does not require an additional power supply. The serial
interface can be connected with a 9-pin female D-Sub connector. Pin2
is used for sending, Pin3 is used for receiving and Pin 5 is used for
GND. The connection to KNX TP is provided via two screw terminals.
Requirements of Directives EMC, RoHS and LVD are met. Standards for
residential, commercial, and industrial environments are fulfilled. The
full text of the EU declaration of conformity is available at the following
internet address:
www.tapko.de/ce
Technical specifications
Power input
Power supply:
Current consumption:
Housing
Dimensions (HxWxD):
Mounting (IEC60715):
Width in space units:
KNX bus connection:
RS232 connector:
Weight:
Environmental conditions
Operating temperature:
Storage temperature:
Ambient humidity:
Mounting, commissioning and safety notes
 After connection to the KNX bus system, the device works with its
default settings as intended
Warning: Do not connect to 230 V. The device is supplied by the
KNX bus and does not require any additional external power supply
 The device may only be installed and put into operation by a
qualified electrician or authorized personnel
 For planning and construction of electric installations the appropriate
specifications, guidelines and regulations in force of the respective
country have to be complied
 For mounting use an appropriate equipment according to IEC60715
 Installation on a 35 mm DIN rail (TH35)
 Connect the KNX bus line as for common KNX bus connections with a
KNX bus cable, to be stripped and plugged into a KNX TP connector
 Do not damage electrical insulations during connecting
 Installation only in dry locations
 Accessibility of the device for operation and visual inspection must be
provided
 For changing settings use the ETS
Release version/date: R1.1 / January 2019
© 2001-2019 TAPKO Technologies GmbH
Im Gewerbepark A15, 93059 Regensburg, Germany
Details, modifications and corrections may be subject to change without notice. TAPKO gives no warranty for the accuracy of the document. All rights reserved.
Operating Instructions
21...30 V DC SELV
< 12 mA
90 x 36 x 60 mm
35 mm top-hat rail (TH35)
2 modules at 18 mm
Screw terminals,
0.3-0.5 mm / 0.8 mm
(finely stranded / single core)
9-pin female D-Sub
75 g
-10...50 °C
-25...70 °C
5...93 % (non-condensing)
Connectors, buttons and LEDs description
Electrical safety
Pollution degree (IEC60664):
Protection type (IEC60529):
Protection class (IEC61140):
Overvoltage category (IEC60664):
Approbation (ISO/IEC14543-3):
CE Marking
EU Directives:
Standards:
Installation and maintenance
 The housing must not be opened
 Protect the device from moisture, dirt and damage
 The device needs no maintenance
 If necessary, the device can be cleaned with a dry cloth
 In the case of damage (at storage, transport) no repairs may be
carried out by unauthorized personnel
 Further documents and database projects:
www.tapko.de/sim-knx
SIM-KNX
DINRAIL
A
RS232 connector
B
Programming button
C
KNX TP connection
Programming LED
1
red:
Programming Mode
active
Rx (received data)
2
green (blinking):
Telegram traffic
red (blinking):
Transmission error
Tx (transmitted data)
3
green (blinking):
Telegram traffic
red (blinking):
Transmission error
2
IP20
III
II
KNX-certified
LVD
(2014/35/EU)
EMC
(2014/30/EU)
RoHS
(2011/65/EU)
EN50491-5-1
EN50491-5-2
EN50491-5-3
EN50581
EN60950-1
loading

Inhaltszusammenfassung für TAPKO SIM-KNX DINRAIL

  • Seite 1 Release version/date: R1.1 / January 2019 © 2001-2019 TAPKO Technologies GmbH Im Gewerbepark A15, 93059 Regensburg, Germany Details, modifications and corrections may be subject to change without notice. TAPKO gives no warranty for the accuracy of the document. All rights reserved.
  • Seite 2  Änderungen an den Einstellungen mit der ETS vornehmen Version/Veröffentlichung: R1.1 / Januar 2019 © 2001-2019 TAPKO Technologies GmbH Im Gewerbepark A15, 93059 Regensburg, Germany Hier enthaltene Daten können sich ohne vorherige Ankündigung ändern. TAPKO garantiert nicht die Richtigkeit und Vollständigkeit des Dokuments. Alle Rechte vorbehalten.