DALI-2 Multi Master Controller
Product Code
ITR832-1001
DALI Line Output
1 x 64, Single Channel
Max. ECG Devices
64 Lighting, 20 DALI-2
and DALI-2 Controls
Device
Display
2x16 LCD Display
Short-Circuit &
Available
Overvoltage Proof
Power Supply
110-240 V AC 50/60 Hz
Power Consumption
6 W
DALI Line Current
1 x 250 mA
Con.
DALI Voltage
Typical 19 V DC (12...20.5)
1 x Ethernet and 1 x USB
Bus Connection
Port
Type of Protection
IP 20
Operation (-5°C...45°C)
Temperature Range
Storage (-25°C...55°C)
Max. Air Humidity
< 90 RH
Colour
Light Grey and White
90 x 70 x 64.5 mm
Dimensions
(H x W x D)
Certification
Certified
Configuration
Via Additional Software
DESCRIPTION
The ITR832-1001 & ITR832-1002 single and dual-channel DALI
Master interface devices are a certified DALI-2 Multi Master
Application Controller capable of controlling DALI-2 Lighting, DALI-2
Controls as well as Interra's unique range of loads and controls which
also connect to the DALI-2 network. DALI devices (ballasts, etc.
ECGs) connected to the line are supplied with the internal DALI power
supply. With the ITR832-1001 single-channel device up to 1x64 DALI
ballasts can be connected, with the ITR832-1002 dual-channel device
up to 2 x 64 DALI ballasts can be connected. With each DALI channel,
16 groups, 16 scenarios and 64 devices can be controlled. Control
and power up to four DALI-2 networks with the DALI Master. Scale up
to large and complex projects by networking multiple DALI Masters
ITR832-1002
together using standard TCP/IP Ethernet connection.
2 x 64, Dual Channel
Each DALI device can be controlled individually, in group or broadcast
128 Lighting, 40 DALI-2
control. All programming data is stored within the system itself
Device
eliminating a central point of failure and the need to always program
with the latest saved configuration file
2x16 LCD Display
Available
Device Type 0 (DT0)
110-240 V AC 50/60 Hz
Device Type 1 (DT1)
13 W
Device Type 6 (DT6)
2 x 250 mA
Device Type 8 (DT8)
Typical 19 V DC (12...20.5)
COMISSIONING FUNCTIONS
1 x Ethernet and 1 x USB
Port
•
Addressing operations can be done via additional software or
IP 20
manual buttons as a short address assignment.
•
Operation (-5°C...45°C)
Faulty ballast detection.
•
Faulty lighting detection.
Storage (-25°C...55°C)
•
Commissioning and control via an embedded web server.
< 90 RH
•
DALI line device selection with the manual button.
Light Grey and White
•
Remote software update via Ethernet connection.
90 x 70 x 64.5 mm
(H x W x D)
•
Emergency lighting test (according to EN 62386-202 standard).
Certified
Via Additional Software
GENERAL FUNCTIONS
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Fluorescent Lamp
Self-Contained Emergency
SAFETY PRECAUTIONS & IMPORTANT NOTES
LED Lamp
•
Colour Control
•
•
•
•
•
•
•
©2025 INTERRA
1/9
Automatic DALI Device Addressing.
Switching, Dimming and Brightness configure
Scene configure
DALI-2 Certified Multi-master application controller
Built in LCD for DALI network testing and alerts display
DALI Bus Voltage Failure Status.
DALI Voltage Recovery Status.
Can be networked together to form large scalable systems.
Ballast and / or Lighting Error.
Working log analysis with UDP.
Broadcast control can be made with manually and software.
Integration with other building systems.
Tunable White color temperature control.
RGB and RGBW color control.
The device may only be installed and put into operation by a qualified
electrician or authorized personnel.
For planning and construction of electric installations, the appropriate
specifications, guidelines and regulations in force of the respective
country have to comply.
Cable Connections: Ensure making correct connections for Black and
Red wires.
Input Voltage: The input voltage shall be 110-240 V AC.
Installation only in dry locations and on a 35 mm DIN rail (TH 35).
Rain, liquid and aggressive gas should not be allowed to be close to
the device.
Screw down strength is less than 0.4 Nm.
Do not get AC 240 V voltage into Bus lines, it can damage all the
devices in the system.
DS2502240101C