RTZ 2, RTZ F
Staircase lighting timer
Technical data
1. Functions
Electronic staircase lighting timer with switch-off warning.
The control input allows the connection of pushbuttons with total glow lamp
load up to 100mA and enables the application in 3- or 4-wire circuits.
The unit can be retriggered via the connected pushbuttons.
A long keypress will switch off the light (energy saving function).
A fast sequence of pushes (pumping) will extend the period to a multiple of
the selected value. Depending upon distinct type, the following operating
methods can be selected by the controls on the unit:
TW Automatic timer with switch-off warning
T
Automatic timer without switch-off warning
1
Steady light (ON)
0
Switch-off
P
Impulse switch mode without time function (only types with option P)
PN Impulse switch mode power fail latch (only types with option PN)
2. Time range
Adjustment range
Time:
0,5 - 12min (in function T, TW)
3. Indicators
Green LED U ON:
indication of supply voltage
Yellow LED ON/OFF:
indication of relay output
4. Mechanical design
Self-extinguishing plastic housing, IP rating IP40
Mounted on DIN-rail TS 35 according to EN 50022
Mounting position:
any
Shockproof terminal connection accordting to VBG 4 (PZ1 required),
IP rating IP20
Tightening torque:
max. 1Nm
Terminal capacity:
1 x 0.5 to 2.5mm² with/without multicore cable end
1 x 4mm² without multicore cable end
2 x 0.5 to 1.5mm² with/without multicore cable end
2 x 2.5mm² flexible without multicore cable end
5. Input circuit
Supply voltage:
Nominal voltage:
Type RTZ 2:
Type RTZ F:
Tolerance:
Rated consumption:
Rated frequency:
Duty cycle:
Reset time:
Hold-up time:
Residual ripple for DC:
Drop out voltage:
Overvoltage category:
Rated surge voltage:
Release 07/07
terminals L - N
230V AC
230V AC
-15% to +10%
2VA (1,0W)
AC 48 to 63Hz
100%
500ms
-
-
>30%
III (according to IEC 60664-1)
4kV
Staircase lighting timer electronic
Switch-off warning
Retrigger, time extension function programmable
Energy saving function
Impulse switch mode selectable
Low switching noise
High switching capacity, 80A peak inrush current
Automatic 3/4 - wire detection
Push-button glow lamp load up to 100mA
Width 17.5 mm
Installation design
6. Output
1 normally open contact
Rated voltage:
Switching capacity (distance <5mm):
Switching capacity (distance >5mm):
Start-up peak (20ms):
Mechanical life:
Electrical life:
Resistive load:
Lamp load:
7. Control input B1
Connection not potential free: pushbutton B1-N (3-conductor circuit)
Glow lamp load:
Overload prodection:
8. Additional control input (only RTZ F)
Connection:
Voltage range:
Galvanic isolation:
Overvoltage category:
Rated surge voltage:
9. Accuracy
Base accuracy:
Adjustment accuracy:
Repedition accuracy:
Voltage influence:
Temperature influence:
10. Ambient conditions
Ambient temperature:
Storage temperature:
Transport temperature:
Relative humidity:
Pollution degree:
Vibration resistance:
Shock resistance:
11. Weight
Single packing:
terminals L - 18
250V AC
10A continuous current
16A continuous current
80A
30 x 10
6
operations
5
10
operations at 16A 250V
80.000 operations at 1000W 250V
pushbutton B1-L (4-conductor circuit)
max. 100mA parallel to each pushbuttons
yes, electronic
control voltage on terminals C1(+)-C2
8...230V AC/DC
yes, basic isolation
III. (according to IEC 60664-1)
4kV
±5% of maximum scale value
<15% of maximum scale value
≤2%
-
≤1%
-25 to +55°C (according to IEC 68-1)
-25 to +70°C
-25 to +70°C
15% to 85%
(according to IEC 721-3-3 class 3K3)
2, if built in 3
(according to IEC 664-1)
10 to 55 Hz 0.35mm
(according to IEC 68-2-6)
15g 11ms
(according to IEC 68-2-27)
106g