Copeland CS3 Serie Betriebsanleitung

Klein- druckschalter
Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 2
Operating instructions
General information:
For application in refrigeration systems in compliance with
standard EN 378.
A professional and appropriate storage and allocation of the
devices is mandatory.
Safety instructions:
Read operating instructions thoroughly. Failure to
comply can result in device failure, system damage
or personal injury.
According to EN 13313 it is intended for use by
persons having the appropriate knowledge and skill.
Before opening any system make sure pressure in
system is brought to and remains at atmospheric
pressure.
Before installation or service disconnect all voltages
from system and device.
Do not exceed the specified maximum ratings for
pressure, temperature, voltage and current.
Keep temperatures within nominal limits. Switch
housing temperature must not exceed 70°C in high
medium temperature applications.
Setting:
CS3 Pressure switches are factory preset to a specific
value (see label).
Note: Cut-in/cut-out and differential may not be
readjusted by the customer (otherwise product
looses warranty).
Function/Type of switch: (Fig. 1 & 2)
Fig. 1: Pressure switch with automatic reset
Fig. 2: High pressure cut-out (manual reset)
Fig.1
Fig.2
4
1
1
2
+
P
P
-
CS3 with automatic reset:
CS3 Pressure switches are equipped with a SPDT snap
action contact switching from 1-2 to 1-4 on rising and from
1-4 to 1-2 on falling pressure.
CS3 with manual reset:
Reaching the preset switching point contact 1-2 opens
and latches. After the pressure drops by appr.13-25 bar
depending on pressure range the switch can be reset
by pushing the reset button.
Installation:
Mounting direction: any
Do not apply torsional force to housing assembly
during mounting (Fig. 3).
Pressure connection: see Fig. 3
= Copper gasket
Copeland Europe GmbH
Pascalstrasse 65 I 52076 Aachen I Germany
Pressure Switch Series CS3
Electrical connection:
Note: Entire electrical connections have to comply with
local regulations. To maintain IP65, proper installation
is mandatory.
Connection with cables PS3-Nxx/-2xx/-4xx
(Fig.4 & 5):
bk = black;
Plug meets requirements of DIN 40050/IEC 529/
EN60529.
Plug has an integrated gasket.
Fasten screw with max. torque 0,05Nm.
Plug cannot be repaired, in case of failure replace
product.
Only one mounting position is possible.
Pressure Test:
After completion of installation, a pressure test must be
carried out as follows:
according to EN 378 for systems which must comply
with
2014/68/EU.
to maximum working pressure of system for other
applications.
Warning:
Failure to do so could result in loss of refrigerant and
personal injury.
The pressure test must be conducted by skilled
persons with due respect regarding the danger
related to pressure.
Tightness Test:
Conduct a tightness test according to EN 378-2 with
appropriate equipment and method to identify leakages of
external joints. The allowable leakage rate must be
according system manufacturer's specification.
4
Service / Maintenance:
In case of repair work or replacing the control always use
2
new gaskets (Fig 3 –
+
-
Type code:
  
CS3 -
e.g. CS3 – W 8 S
Function
B = Pressure cut out, external manual reset,
type approval, EN 12263, PZH
S = Safety pressure cut out, internal manual
reset, type approval, EN 12263 PZHH
W = Pressure limiter, automatic, type approval,
EN 12263, PSH
Note: Function types B or S protect against high pressure
Pressure
setting
range
7/P = 40...70 bar
8/Q = 60...140bar
Note:
Pressure connection
S = 7/16"-20 UNF female with schraeder opener, (with
snubber)
OI_CS3_A1_EN_DE_FR_ES_IT_Rev03_0718303.docx
bl = blue;
br = brown
European
pressure
equipment
).
Max. allowable
Pressure
Pressure
(PS)
140 bar
140 bar
7/8
Standard contacts
P/Q Microswitch
Date: 25.10.2024
Technical Data:
Max.
working
pressure PS
Test pressure PT
Electrical rating
Inductive load
(AC15)
Inductive load (DC)
Motor rating amps
(FLA)
Lock rotor amps
(LRA)
Note: For electronic applications with low electrical loads
(current <100 mA) standard contacts are not suitable.
directive
Protection class
(EN 60529)
Vibration resistance
Temperatures
Ambient (housing)
Note: For high temperature applications, i.e. medium
temperatures between 70°C and 150°C, the maximum
ambient temperature must be derated as per drawing.
see Fig. 6; Tm = Medium temperature,
Ta = Ambient temperature
E.g.: On medium temperature 120°C the ambient
temperature of 55°C around the switch housing should
not be exceeded.
Temperatures
Storage/transport
-40°C...+70°C
-40°C... +150°C
Medium
Medium
CO
compatibility
Marking
acc. Low Voltage Directive
0035 acc. to PED 2014/68/EU
(File No. E85974)
Test
(PT)
154 bar
154 bar
P/N 0718303/Rev03
EN
Range 7/P: 140 bar
Range 8/Q: 140 bar
Range 7/P: 154 bar
Range 8/Q: 154 bar
Standard
Micro-switch
3A 230VAC
1.5A 230VAC
0.1A 230VDC
0.1A 230VDC
6A
2.5A
120/240VAC
120/240VAC
UL: 6A
UL: 1.5A
120/240VAC
120/240VAC
36A
15A
120/240VAC
120/240VAC
UL: 18A
UL: 10A
120/240VAC
120/240VAC
IP65 with PS3-Nxx
IP00 (without appliance socket)
4g (at 10...250 Hz)
-40°C...+70°C
(R744)
2
loading

Inhaltszusammenfassung für Copeland CS3 Serie

  • Seite 2 7/P = 40..70 bar 140 bar 154 bar 8/Q = 60...140bar 140 bar 154 bar Hinweis: 7/8 Standardkontakte P/Q Mikroschalter  Druckanschluss innen, Schraderöffner, (mit S = 7/16"-20 Pulsationsdämpfer) Copeland Europe GmbH Date: 25.10.2024 Pascalstrasse 65 I 52076 Aachen I Germany OI_CS3_A1_EN_DE_FR_ES_IT_Rev03_0718303.docx...