Where to install a smoke alarm
Smoke alarms must be installed in such a way that they can be reached
unhindered by the fire smoke so thaes can be reliably detected during the
development phase.
• Install at least in sleeping areas (especially children's rooms).
• Install at least in escape rooms.
• In the middle of the ceiling of a room.
• At least 50 cm away from the wall and other objects.
• Maximum installation height of 6 meter.
• lf ceiling installation is not possible, the smoke alarm can be installed on
the
wall. The distance to the ceiling should be between 30 and 50 centime-
ter.
Minimum
Where to install a smoke alarm in rooms with special geometries
Corridors with a maximum width of 3M:
Max.15M between 2 smoke alarms. Max. 7,5M to the front side of the
gallery and smoke alarms at edges/crossings of corridors.
Rooms with sloping ceilings:
- lf the ceiling inclination is > 20° to the horizontal: Smoke alarms must be
installed
at least 0.5M and at most 1M from ceiling top.
- Partial roof slopes: lf the flat ceiling is ≤ 1M wide, consider as ceiling
inclination is
of > 20°. lf the flat ceiling is >1M wide, consider as flat ceiling.
Rooms with subdivided ceilings:
- Height of the subdivisions is ≤0.2M: Beams without consideration; smoke
alarm
may be installed on the beams as well as on ceiling.
- Height of subdivisions is >0.2M and area of ceiling panels > 36M²:
Smoke alarm should be installed in each ceiling panel.
- Height of subdivisions > 0.2M and area of ceiling panels ≤ 36M²:
lndividual ceiling without consideration.
Res
PRODUCT SPECIFICATIONS
• Power Supply: Built-in DC3V(CR17450) lithium battery
(Battery not replaceable)
• Battery Lifetime: 10 Years
• Monitored area: 40 M²
• Operating temperature: 0
• Operating humidity: <93 %
• Low battery warning: Yes
• Hush time: 10 hours lnstallation in leisure
• Alarm Volume: ≥85 dB(A) at 3 meters
• lnterconnectable: Yes | Max. 40 devices
• Wireless frequency: 868.3 MHz
• Wireless distance: Max. 100 meters
Product Description
Activation
Before commissioning the smoke alarm, it is important to activate it and test it for
correct operation.
- Use a screw driver to push the activation
switch to the right. When the smoke
alarm isactivated, the LED lights up.
- Test the correct activation of your smoke
alarm by pressing the test button.
lf no sound is generated, the smoke alarm
is not activated properly and should not
be used!
Connect your smoke alarms:
1. Choose one smoke alarm as the master smoke alarm.
2. Turn your master smoke alarm into the connect mode by quickly pressing the
test button 3 times.
3. The red LED will light up red, followed by the blue LED. This indicates that the
smoke alarm turned into the connect mode in which it remains for 30 seconds.
4. Turn the next smoke alarm into the learn mode by quickly pressing the test
button 3 times.
5. The red LED will light up, followed by the green LED. This indicates that the
smoke alarms are connected to each other.
6. Repeat step 1 to 5 for connecting more smoke alarms. Make sure that you
always use the same master smoke alarm!
7. Test if the your smoke alarm were connected successfully by pressing the test
button of a random device until it beeps.The red LED of all connected devices
test button of each alarm.
Reset connection:
1. Disconnect the smoke alarm you want to reset by removing it from the
mounting plate, or by pushing the activation switch to the leftwith a screw driver.
2. Press and hold the test button and activate the smoke alarm again by pushing
the activation switch to the right.
3. Hold the test button while the LED lights up red and release it when the LED
turns of.
4. When the LED lights up again, press the test button.
7. Repeat step 1 to 6 for disconnecting more smoke alarms.
Les piles
etbatteries se
recyclent
Made in China
- 45
a
switch
ated
Backside smoke alarm
loading

Inhaltszusammenfassung für Putogesafe GS511

  • Seite 3 (Akku nicht austauschbar) • Batterielebensdauer: 10 Jahre • überwachter Bereich: 40 m2 • Betriebstemperatur: 0 - 45 Model: GS511 • Betriebsfeuchtigkeit: <93 % • Batteriewarnung: Ja Drahtloser fotoelektrischer Rauchmelder • Stille Zeit: 10 Stunden Installation in der Freizeit • Alarmlautstärke: ≥85 dB(A) bei 3 Metern Benutzerhandbuch •...
  • Seite 4 Verbinden Sie Ihre Rauchmelder Wählen Sie einen Rauchmelder als Master-Rauchmelder 3x Tastendrucktaste Drehen Sie den Alarm in den Rote LED, gefolgt von blauer LED Anschlussmodus Master Rauchmelder Rauchmelder Master Rauchmelder Master Rauchmelder Master Rauchmelder 3x Drücken Sie die Tes aste, um den Alarm in den Rote LED, gefolgt von einer grünen LED, die Rauchmelder anzeigt, der Lernmodus zu schalten miteinander verbunden ist...