Fig. 4
6
1. Safety Instructions
The device shall only be
used for its intended pur-
pose and in undamaged
and perfect condition!
Only genuine CEAG spare
parts may be used for re-
placement and repair!
When working on the emer-
gency luminaire make sure
that it is disconnected from
the voltage! Pay attention to
the different power
supplies in mains or battery
operation. Fig. 4 shows the
indication label on the
emergency luminaire.
Prior to its initial operation,
the luminaire will have to be
checked in accordance
with the instructions as per
section Installation!
Carry out the marking of the
emergency luminaire: As-
sign the circuit and the
lumi-
naire No. and enter them.
Recording in the minutes
shall be performed in com-
pliance with the national re-
gulations (is deleted in case
of automatic recording).
Any foreign matter shall be
removed from the luminaire
prior to its initial operation!
While undertaking any
servicing on the luminaire,
the national safety rules
and regulations for pre-
vention of accidents shall
be observed as well as the
safety instructions included
in these operating instruc-
tions marked with a
2. Conformity with
standards
Conforming to: EN 60 598-1,
EN 60 598-2-22,
DIN 5035 part 5, DIN VDE 4844
and IEC 60 924 as well as
IEC 60 928. Designed, manu-
factured and tested according
to DIN EN ISO 9001.
3 Brief description
3.1 Scope of application
The Exit and Safety luminaire is
suitable for operation on CEAG
safety lighting systems (e. g. ZB
96 or CG 2000) as well as on all
power supply systems acc. to
VDE 0108, EMC directive 89/
336/EEC and low potential di-
rective 73/23/EEC.The ad-
vanced switching mode is
available only with CEAG CG
2000 technology.
3.2 T
3.2 T
echnical data
echnical data
3.2 Technical data
3.2 T
3.2 T
echnical data
echnical data
Dimensions:
(L x H x D):
355 x 100 x 65
Enclosure
material
Aluminium
Type of mount.: Wall mounting
Weight:
1.14 kg
Supply
terminals:
3 x 2,5 mm²
Input voltage: 230 V 50/60
Hz,
220 V DC
+25%/-20%
Rated current
(DC):
60 mA
Power con-
sumption (AC): 14 VA
Perm. ambient
temperature:
-10 °C .. +40 °C
Lamp:
2 x 7 W tungsten
Rated luminous flux for mains
operation:
30 %
Rated luminous flux for
emergency
operation:
100 %
Insulation
class:
I
Protection
category acc.
to EN 60529:
IP 20