2.4
Binary Inputs
The 2 binary inputs BI-1 and BI-2 operate across a wide input-voltage range. Logic 1 (high) is a voltage level
from DC 24 V to 250 V, -20 %, +15 %, with polarity-reversal protection and a pickup threshold of 18 V. In
exceptional cases, for example, with long unshielded lines and a disturbing influence, the pickup threshold
can be set to about 75 V (see
Logic 0 (low) is a voltage level below the set pickup threshold. When the corresponding binary input is acti-
vated, the corresponding yellow LEDs (BI-1, BI-2) light up.
Table 2-6
Binary Input 1 BI-1
Active
–
If the optical fiber or RS232 is being used for communication, the LEDs K1 and K2 indicate the state of the
binary inputs on the remote station.
Accessories, Binary signal transmitter 2-channel 7XV5653-0BA00, Manual
C53000-G9050-C607-2, Edition 03.2020
Table 2-7
and
Binary Inputs
Binary Input 2 BI-2
–
Active
Figure
2-3).
LED BI-1
LED BI-2
Lit
–
Device Structure
2.4 Binary Inputs
LED K1
–
Remote
station
Lit
–
LED K2
–
Remote
station
19