Herunterladen Inhalt Inhalt Diese Seite drucken

Safety Notes; Application; Items Supplied; Technical Data - Bosch Thermotechnik Junkers TA 211 E Bedienungsanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 3
TA 211 E
1

Safety Notes

The regulator is installed into the boiler
facia. The regulator may only be con-
nected according to the wiring diagram.
Under no circumstances should the reg-
ulator be connected to the 230 V mains.
The regulator is to be used exclusively
in connection with a boiler equipped with
Bosch Heatronic control.
Before installing the regulator, the volt-
age supply (230 V, 50 Hz) to the boiler
must be disconnected.
2

Application

TA 211 E is a flow temperature regulator con-
trolled by outside temperature to be installed
into the facia of appliances, equipped with
Bosch Heatronic control.
2.1

Items Supplied

Included in the items supplied (Fig.
the TA 211 E is an outside temperature sen-
sor with mounting material.
2.2

Accessories

A mechanical flow temperature limiter must
be fitted to the flow pipe of underfloor heating
systems, in accordance with the manufactur-
er's instructions.
The TA 211 E is supplied without a time
switch. This is available as an accessory.
A remote control with a time switch can also
be used (not in UK, see the following table)
10
The following combinations are permisable:
Combination
TA 211 E + EU 3 T
TA 211 E + EU 2 D
TA 211 E + EU 3 T + TW 2
TA 211 E + EU 2 D + TW 2
TA 211 E + TFQ 2 T
TA 211 E + TFQ 2 W
TA 211 E + TFP 3
* Not in UK.
Note:
3

Technical Data

) with
2
Feed water temperature
regulating range
Measuring range of the
outside temperature sensor – 20 ...+30 °C
Permissible ambient
temperature of the outside
temperature sensor
Protection class
3.1
Measured Values,
Outside Temperature Sensor AF
°C
– 20
2392
– 16
2088
– 12
1811
– 8
1562
– 4
1342
0
1149
According to Par. 7 of the Heating
System Regulations, the TA 211 E
can be operated only in conjunction
with a time switch.
V
°C
AF
2.64
4
2.49
8
2.33
12
2.16
16
1.99
20
1.82
24
Electrical Cir-
cuit Diagram
Fig.
8
Fig.
8
Fig.
*
9
Fig.
*
9
Fig.
*
10
Fig.
*
10
Fig.
*
10
10 ... +88 °C
– 30 ... +50 °C
III
V
AF
984
1.65
842
1.49
720
1.34
616
1.20
528
1.07
454
0.95

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

7 744 901 102

Inhaltsverzeichnis