Herunterladen Diese Seite drucken

Installation - Siemens SIMATIC ET 200SP HA Produktinformation

Peripheriemodul
Vorschau ausblenden Andere Handbücher für SIMATIC ET 200SP HA:

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
Ex-DQ 2x23.1VDC/20mA
Note
You may use the I/O module with device category 3G in the hazardous area of zone 2.
You may connect actuators of device categories 1G, 2G and 3G for zones 0, 1, and 2
as well as device categories 1D, 2D and 3D for zones 20, 21 and 22 to the outputs of
the I/O module.

Installation

DANGER
Explosion hazard
Ignitable sparks or impermissible surface temperatures can potentially occur during
installation work. Never carry out mounting under explosive conditions!
When mounting, adhere to the installation and setup regulations according to DIN EN
IEC 60079-14 and the country-specific regulations.
DANGER
No standard BaseUnits to Ex modules
No standard BaseUnits may be connected to the BaseUnits of the Ex modules.
Wiring of the BaseUnit
When laying the cables and wiring, adhere to the installation and setup regulations
according to DIN EN IEC 60079-14 as well as the country-specific regulations.
Ensure intrinsically safe and non-intrinsically safe cables are completely separate
during wiring. They must be routed in separate cable ducts and must maintain a
minimum distance of 50 mm from "non-intrinsically safe cables".
The shield connection is separated from the intrinsically safe circuits and is connected
to the local equipotential bonding system. Any significant loop current through the
shield should be avoided because the shield is not intrinsically safe and the "increased
safety" explosion protection type is not present.
You may connect actuators from zone 0, zone 1, zone 2 as well as zone 20, zone 21,
zone 22 and the safe area to the BaseUnit. You can find the pin assignments of the I/O
module in the corresponding operating instructions.
The intrinsic safety of the interconnection of I/O module, sensors and cabling must be
proven by calculating the safety-related characteristic values. These values are stated
in the respective Ex certificates or on the data sheet of the cable.
10
Ex-DQ 2x23.1VDC/20mA
A5E50377641-AA, 04/2021

Werbung

loading

Diese Anleitung auch für:

Simatic et 200sp