Commissioning Instructions
TZIDC-220 für FOUNDATION
Commissioning
Observe all safety instructions and pre-
!
cautions in the operating instructions!
Before operation always make sure that
the cover is fastened with screws!
Important:
The prerequisite for proper operation of the
TZIDC-220 positioner on the bus is that the
Transducer Block can change over to AUTO
mode. This requires that the operating range
of both the positioner and the valve be
matched to each other (as described in step
5 of the procedure below). If this auto-
adjustment should fail or cannot be per-
formed for any reason, the Transducer Block
remains in "Out of Service" mode and the
configuration bit in the "BLOCK-ERR Param-
eter" is "active".
1. Turn on the air supply to the positioner.
2. Connect the bus with arbitrary polarity (auxiliary
power 9 V DC ... 32 V DC) to the bus terminals.
If the emergency shutdown module is installed,
the supply voltage for this module needs to be
24 V DC (terminals +85 / -86) and the switch
needs to be in its ceter position. Otherwise, the
device has no pneumatic function.
3. Check for proper mounting:
- Press and hold
MODE
neously until countdown has run down.
TZIDC-220 changes to operating mode 1.x
- Press and hold
press
or
until mode 1.3 is displayed.
- Press
or
mechanical limit stops in both directions, and
note the values.
Recommended range
between -28° and +28° for linear actuators
between -57° and +57° for rotary actuators
Minimum angle: 25°
4. Return to the remote level:
- Press and hold
MODE
countdown has run down, then release the
buttons. "REMOTE" is displayed.
5. Run the standard Autoadjust function (make
sure that the remote level is activated)
For a linear actuator:
- Press and hold
has run down, then release the button.
- Press and hold
MODE
down has run down, then release the button.
Standard autoadjustment is started automati-
cally, and the progress is displayed.
For a rotary actuator:
- Press
. TZIDC-FF is indicated. Hold
ENTER
until ADJ_ROT is shown, then
ENTER
release the button.
ABB Automation Products GmbH
Schillerstr. 72 · 32425 Minden, Germany
Tel: +49 551-534 · Fax: +49 551 905-555
CCC-support.deapr@de.abb.com
and
simulta-
ENTER
. Additionally briefly
MODE
to move the actuator to its
:
and
until the
ENTER
until the countdown
MODE
again until the count-
The company's policy is one of continuous product improvement and the
right is reserved to modify the information contained herein without notice
T M
Fieldbus
- Press and hold
countdown has run down, then release the
button. Standard autoadjustment is started
automatically, and the progress is displayed.
When standard autoadjustment has completed suc-
cessfully, the determined parameters are saved
automatically, and the remote level is activated
again.
In case of an error during standard autoadjustment,
error code 255 is briefly indicated. TZIDC-220 then
changes to the configuration level, parameter P1.1.
Press and hold
press
or
several times until P1.6 (EXIT) is
displayed.
Release
MODE
briefly press
or
Press and hold
ENTER
run down.
TZIDC-220 automatically returns to the operating
level. Briefly press
check the positioner-actuator assembly for proper
mounting (see operating instructions). Re-adjust if
required and then start standard autoadjustment
again.
Operating modes
Mode selection from operating level
Press and hold
press
as often as required. The selected
operating mode is indicated.
Release
. The position is indicated as a
MODE
percentage or rotation angle.
Overview
Mode
1.1 Positioning w.
fixed setpoint, SP
adjustment via
or
.
1.2 Man. adjust. *
in operating range
Press
or
to
adjust. **
1.3 Man. adjust. *
in sensor range
Press
or
to
adjust. **
*) Positioning is not active.
**) For quick motion: press
Printed in the Fed. Rep. of Germany (02.2009)
44/18-82 XA
again until the
ENTER
. Additionally briefly
MODE
. CANCEL is displayed. If not,
.
until the countdown has
twice to reach mode 1.3 and
. Additionally briefly
MODE
Position
Mode display
display
¬
C
%
mA
conf
conf
¬
C
%
mA
conf
conf
¬
C
%
mA
conf
conf
and
together.
© ABB 2009
¬
C
%
mA
¬
C
%
mA
¬
C
%
mA

Werbung

loading