WARNING
Prerequisites
NOTE
Siemens AG
SIMOVERT MASTERDRIVES
Downloaded from
www.Manualslib.com

Start-up

Work must not be done on the module when the power supply is on or
the motor is turning.
The safety instructions for MASTERDRIVES are to be complied with.
♦ The standard converter start-up with "closed-loop speed control"
has been completed.
♦ Check the existing board combination
• TSY in conjunction with CU1 (SIMOVERT FC)
• CU2 (SIMOVERT VC) / CUVC (Vector Control) /
CUVP
♦ Determine the tachometer type
♦ Select and check the input terminals
HTL ↔ -X402 DTI
TTL ↔ -X401 DTI
♦ Establish and check the connection to the converter (refer to figs.
5-1 and 5-2)
• SIMOVERT FC
DTI -X403
Signalpegel)
• SIMOVERT VC
DTI -X403
♦ Select the 24 V power supply for the tachometer
• 0.3 A power supply module (option)
• Other 24 V power supplies
"Potential separation" is required for the external supply.
♦ Check that the screen is grounded at both cable ends and that the
board is grounded.
1)
only with 6SE7090-0XX84-3DB1
6SE7087-6CX84-3DB0
Digital tacho-Interface
manuals search engine
1)
(Vector Control Compact PLUS)
TSY -X113,-X117 ↔ CU1-X107 (15-V-
CU2 -X103
CUVC -X103
1)
CUVP
-X104
Start-up
(15 V signal level)
(15 V signal level)
(15 V signal level)
4-1