TZIDC DIGITALER STELLUNGSREGLER | DS/TZIDC-DE REV. C
FM / CSA
(eingeschränkter Funktionsumfang)
CSA International
Certificate
Certificate
Class 2258 02
Class 2258 04
Electrical data
Model TZIDC, P/N V18345-x0x2x2xx0x Intelligent Positioner
For use in
Input rated
Max output pressure
Max. ambient temperature
Model TZIDC, P/N V18345-x0x2x2xx0x Intelligent Positioner intrinsically
safe with entity parameters of:
For use in
Terminals 11 / 12
Terminals 81 / 82
Terminals 83 / 84
Terminals 31 / 32
Terminals 41 / 42 and 51 / 52
Terminals Limit 2 41 / 42
and Limit 1 51 / 52
1052414
PROCESS CONTROL EQUIPMENT – For
Hazardous Locations
PROCESS CONTROL EQUIPMENT –
Intrinsically Safe, Entity – For
Hazardous Locations
Class I, Div 2, Groups A, B, C and D
Class II, Div 2, Groups E, F, and G
Class III, Enclosure Type 4X
30 V DC; max. 4 to 20 mA
90 psi
80 psi (Marine version)
85 °C
Class I, Div 1, Groups A, B, C and D;
Class II, Div 1, Groups E, F and G
Class III, Enclosure Type 4X:
V max = 30 V
C
i
I max = 104 mA
L
V max = 30 V
C
i
I max = 110 mA
L
V max = 30 V
C
i
I max = 90 mA
L
V max = 30 V
C
i
I max = 110 mA
L
V max = 30 V
C
I max = 96 mA
L
V max = 15.5 V
C
I max = 52 mA
L
i
Note
•
The "x" in P/N denotes minor mechanical variations or
optional features.
•
Local communication interface (LCI) shall not be used in
hazardous location.
•
Each pair of conductors of each intrinsic safety circuit
shall be shielded.
•
See FM installation drawing No. 901064 for Details.
= 6.6 nF
= 0 μH
i
= 4.2 nF
= 0 μH
i
= 4.2 nF
= 0 μH
i
= 6.6 nF
= 0 μH
i
= 3.7 nF
i
= 0 μH
i
= 20 nF
i
= 30 μH
27