Herunterladen Inhalt Inhalt Diese Seite drucken

Connect The Control Cables; Default I/O Connections - ABB ACS880-01 Kurzanleitung Für Die Installation

Frames r6 to r9
Vorschau ausblenden Andere Handbücher für ACS880-01:
Inhaltsverzeichnis

Werbung

10. Connect the conductors of the input and motor cables. Tighten the screws.
11. Units with option +D150: Connect the conductors of the brake resistor cable to the
R+ and R- terminals.
12. If parallel cables are installed, install the grounding shelf for them. Repeat steps 7
to 12.
13. Reinstall the shroud on the power terminals.
14. Reinstall the side plates of the cable entry box.
15. Install the control cable grounding shelf in the cable entry box.
16. Secure the cables outside the unit mechanically.
17. Ground the motor cable shield at the motor end. For minimal interference, make a
360-degree grounding at the cable lead-through, or keep the pig tail short.

Connect the control cables

See figure G.
1. Cut adequate holes into the rubber grommets and slide the grommets onto the
cables. Slide the cables through the holes of the bottom plate and attach the
grommets to the holes.
2. Strip the cable ends and cut to suitable length (note the extra length of the
grounding conductors).
3. Ground the outer shields of all control cables 360 degrees at a grounding clamp in
the cable entry box.
4. Ground the pair-cable shields to a grounding clamp below the control board.
Leave the other end of the shields unconnected or ground them indirectly via a
high-frequency capacitor with a few nanofarads, eg, 3.3 nF / 630 V.
5. Connect the conductors to the appropriate terminals of the control board (see
page 12).
6. Wire the optional modules if included in the delivery.
7. Reinstall the front cover.

Default I/O connections

The default I/O connections of the Factory macro of the ACS880 primary control
program are shown below.
EN – Quick installation guide 11
EN
DA
DE
ES
FI
FR
IT
NL
PT
RU
SV
TR
CN

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis