Herunterladen Inhalt Inhalt Diese Seite drucken

Functional Check - Siemens REV-R.03/16A Installationsanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
LED_2 is always dark:
Orange on
Controlled device OFF
Orange off
LED_2 lights always:
Orange on
Controlled device ON
Orange off
LED_2 flashes always:
Learning mode active
Orange on
Orange off
Commissioning the controller / transmitter REV23.03RF
1
Configuration
1.1
Accessing the heating engineer level
The heating engineer level will be enabled by pressing simultaneously
the warmer and colder buttons and by rolling the roller selector away
from the display and then toward the display (also refer to Fig. G).
1.1.1 Calibrating the sensor
After activating the heating engineer level, the CAL symbol will flash.
When pressing the roller selector, the room temperature currently
measured flashes and can now be recalibrated by a maximum of
± 2 °C by rolling either toward the display or away from it. To store
the recalibration, press the roller selector (also refer to Fig.
1.1.2 Setpoint limitation
There are 2 setting choices available:
On the heating engineer level, change from the flashing CAL symbol to
the setpoint limitation symbol by rolling toward the display (also refer to
Fig.
). Press to accept. 5...29 °C will flash (factory setting). Press to
accept or continue rolling. Setting 16...29 °C will flash. Press to accept.
1.1.3 Optimum start control
On the heating engineer level, change from the flashing CAL symbol to
the optimum start control symbols
toward the display (also refer to Figs.
will flash (factory setting). Press to accept or continue rolling
until you reach ¼, ½, 1 or optimization OFF
accept.
1.1.4 Control mode
On the heating engineer level, change from the flashing CAL symbol to
the symbols of the various control modes by rolling several times toward
the display (also refer to Fig.
(factory setting) will flash. Press to accept or continue rolling
toward the display to select one of the following control modes:
, PID 6, PID 12 or
mode.
A description of the different control modes is given below (also refer to
Fig.
).
Difficult controlled systems:
Proper on / off controller with a switching differential
of 0.5 C (factory setting).
Self-learning, adaptive control:
Suited for all standard applications.
PID 12
Normal controlled systems:
For locations with normal temperature variations.
PID 6
Fast controlled systems:
For locations with significant temperature variations.
1.1.5 Periodic pump run
This function protects the pump against seizing during longer off
periods. Periodic pump run is activated for a minute every 24 hours at
12:00 (when pump run is activated, the flame symbol
on the display).
On the heating engineer level, change from the flashing CAL symbol to
the
symbol by rolling twice away from the display (factory setting,
periodic pump run off).
8/36
).
or
by rolling twice
and
). Press to accept.
. Press to
). Press to accept.
. Press to accept the required control
appears
LED_2 flashes briefly: Reception of control telegram
7
Finish mounting of REV-R.03/16A
a)
Switch off power
b)
Mark location where REV-R.03/16A is currently fixed
c)
If necessary loosen wiring
d)
Mount receiver at location marked before according
Fig. H to M, wire completely and close housing
e)
Switch on power
Press to accept.
continue rolling. The
Press to accept (also refer to Fig.
1.1.6 Heating / cooling mode
On the heating engineer level, change from the flashing CAL symbol to
the heating / cooling symbols by rolling away from the display.
Press to accept. The
to accept or continue rolling. The cooling symbol
accept (also refer to Fig.
1.1.7 Frost protection mode
Use operating mode selector
.
Fig.
). If the standard value of 5 °C need to be changed, the frost
protection setpoint
(refer to operating instructions).
2

Functional check

a)
Check the display. If there is no display, check the correct fitting
and function of the batteries
b)
Comfort mode
c)
Select temperature menu T and adjust a temperature setpoint
of 29 °C (refer to operating instructions)
d)
The relay must be energized within one minute, causing the
actuating device to operate. Flame symbol
the display. If that is not the case:
Check actuating device and wiring
The room temperature is possibly above 29 °C
e) Reset setpoint temperature
19 °C or individual setting)
f)
Select the required operating mode
3
Reset
User-defined data:
Press the button behind the pin opening for at least one second: this
resets the user-specific settings to their default values (the heating
engineer settings will not be changed). The clock starts at 12:00. During
the reset time, all sections of the display light up, enabling them to be
checked.
All user-defined data plus the heating engineer settings:
Press the button behind the pin opening together with the warmer and
colder buttons for at least one second.
After this reset, the factory settings will be reloaded (also refer to
section "Factory settings" in the operating instructions).
4
Notes
The controler conforms to "Software Class A" and is for use in
"normal" pollution situation
REV23.03RF/SET is a set of units consisting of electric room
temperature controller/thermostat with a weekly timeswitch and
transmitter (REV23.03RF) and a RF receiver (REV-R.03/16A)
14.02.2006
will flash (factory setting). Press to accept or
symbol for periodic pump run on will flash.
).
heating symbol will flash (factory setting). Press
).
to select symbol
must be changed via temperature menu T
to its initial value (standard value
will flash. Press to
(also refer to
will appear on
CE1G2269xx

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Rev23.03rf

Inhaltsverzeichnis