Herunterladen Inhalt Inhalt Diese Seite drucken

ABB ACS880-04 Kurzanleitung Für Die Installation Seite 7

Vorschau ausblenden Andere Handbücher für ACS880-04:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 39
Make sure that the drive is compatible with the grounding
system
The standard drive with no EMC filter and the ground-to-phase varistor connected
can be installed to a symmetrically grounded TN-S system. If you install the drive to
another system, you may need to disconnect the EMC filter and ground-to-phase
varistor. See
ACS880 frames R1 to R11 EMC filter and ground-to-phase varistor
disconnecting instructions (3AUA0000125152
Do not install the drive with EMC filter option +E200 to a system that the filter
is not suitable for. This can cause danger, or damage the drive.
Do not install the drive with the ground-to-phase varistor connected to a system
that the varistor is not suitable for. If you do, the varistor circuit can be
damaged.
Corner-grounded and midpoint-grounded 525...690 V delta systems
Do not install the drive on a 525...690 V corner-grounded or midpoint-grounded
delta system. Disconnecting the EMC filter and ground-to-phase varistor does
not prevent damage to the drive.
Move the drive to the installation site and unpack it
Move the drive module in its transport package to the installation site. Use a pallet
truck when you move a heavy drive package.
To unpack the package:
Cut the bands (A)
Unpack the additional boxes (B)
Remove the outer sheathing by lifting it (C)
Remove the sheathing by lifting it (D).
EN – Quick installation instructions 7
[English]).
EN
DA
DE
ES
FI
FR
IT
NL
PL
PT
RU
SV
TR
ZH

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis