4 About the unit and options

1 Bring out the unit that is mounted on the pallet (d). Use a forklift
or a transpallet (f).
d
e
d
Pallet
e
Cardboard box
f
Forklift
WARNING
Make sure that the forklift, or any other lifting device used,
can bear the weight of the unit.
INFORMATION
See "10 Technical data" [ 4  27] for the weight of the unit.
2 Cut the straps (c).
3 Remove the cardboard protection (e) from the condenser.
4 Remove the plastic wrap from around the unit.
WARNING
Tear apart and throw away plastic packaging bags so that
nobody, especially NOT children, can play with them.
Possible consequence: suffocation.
h
i
b
Cardboard pillars
d
Pallet
h
Screws
i
Protection cover (blue color)
5 Remove the protection cover (i) from the drainpan.
6 Remove the screws (h) that are fixing the unit to the pallet (d).
Installation manual
6
4
f
The LMSEY unit is a compact wall installed refrigeration unit for a
small cold room. It optimises the use of space inside the cold room.
It is managed by an electronic control unit that has already
programmed operating parameters and allows the signalling of any
anomalies.
The appliance can operate as a cooler (+10°C to –5°C) or a freezer
(–15 to –25°C).
Multiple units can be combined within one cold room. Multiple units
are operating according to the primary/secondary principle. (See
"4.4 Combining multiple units" [ 4  7]).
4.1
The LMSEY unit is a refrigeration unit which produces coldness by
vaporising a liquid refrigerant (Hydrocarbon R290 type) at low
pressure in a heat exchanger (evaporator). The resulting vapour is
brought back to liquid state by mechanical compression at a higher
pressure,
(condenser).
Defrosting takes place automatically in pre-set cycles, by injecting
hot gas; manual defrosting is also possible.
4.2
b
d
In this document, LMSEY1A13AVM01 is shown in the instructions,
unless there is a need to treat both models separately.
4.3
LMSEY1A09AVM01 + LMSEY1A13AVM01
About the unit and options

About the system

followed
by
cooling

About the different models

LMSEY1A09+13AVM01
Model
Capacity
LMSEY1A09AVM01
950 W
LMSEY1A13AVM01
1.28 kW
LMSEY2A19AYE01
1.9 kW
LMSEY2A25AYE01
2.58 kW
(a)
Cooling capacity at a rated empty condition according to
EN 17432 (indoor temperature of 0°C, outdoor temperature of
32°C).

System layout

a
b
c
d
e
in
another
heat
exchanger
LMSEY2A19+25AYE01
(a)
Number of cooling
circuits
1
1
2
2
LMSEY1A09/13 + LMSEY2A19/25
Daikin LMS
4P728170-1B – 2023.07