PRODUCT DATA
CUT-OUT DIMENSIONS
Frame
Locking Adapter Counter Nut Cut-out (D) Torque
KDS-R 20-32 KDS-RGA M20
KDS-GM 20
KDS-RGA M25
KDS-GM 25
KDS-RGA M32
KDS-GM 32
KDS-R 40-63 KDS-RGA M40
KDS-GM 40
KDS-RGA M50
KDS-GM 50
KDS-RGA M63
KDS-GM 63
USAGE OPTIONS
Inlay
1
2
Frame
28516.4
28517.4
KDS-R 40-63
x
x
KDS-R CABLE ENTRIES
INSTALLATION
1
Guide cables through frame.
4
D
Push seals all the way in.
7
20.3 mm
3 Nm
25.3 mm
3 Nm
32.3 mm
3 Nm
Mount from outside.
40.4 mm
7 Nm
50.4 mm
7 Nm
63.4 mm
7 Nm
4
28518.4
x
2
Click inlay into position.
5
Assemble locking adapter.
8
Assemble counter nut.
3
Attach seals to cables.
6
Screw locking adapter into
outer frame.
9
Screw counter nut on from inside.

Werbung

loading

Inhaltszusammenfassung für contaclip KDS-R-Serie

  • Seite 1 CONTA-CABLE/ KDS-R CABLE ENTRIES PRODUCT DATA INSTALLATION Guide cables through frame. Click inlay into position. Attach seals to cables. Push seals all the way in. Assemble locking adapter. Screw locking adapter into outer frame. CUT-OUT DIMENSIONS Frame Locking Adapter Counter Nut Cut-out (D) Torque KDS-R 20-32 KDS-RGA M20 KDS-GM 20 20.3 mm...
  • Seite 2 CONTA-CABLE/ KDS-R KABELEINFÜHRUNGEN PRODUKTDATEN INSTALLATION Die Kabel durch den Rahmen führen. Das Inlay in seine Position einrasten. Die Dichtungen an den Kabeln an- bringen. Die Dichtungen vollständig eindrü- Montieren Sie das Verriegelungsad- Das Verriegelungsadapter in den Au- cken. apter. ßenrahmen ausschrauben. ABMESSUNGEN MONTAGEAUSSCHNITTE Verriegelungs- Gegenmutter Ausschnitt...

Diese Anleitung auch für:

Kds-r 20-32Kds-r 40-63Kds-rga m20Kds-rga m25Kds-rga m32Kds-rga m40 ... Alle anzeigen