Herunterladen Diese Seite drucken

Hochiki BGU-E Installationsanleitung

Feuermeldestelle

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

HOCHIKI ESP RANGE ISOLATOR CALL
POINT INSTALLATION INSTRUCTIONS
Product covered: BGU-E(PS)
Description
The BGU-E(PS) is an addressable call-point with an integral short circuit
isolator which is fully ESP compatible. The call point features a two Status
Indicators (SI), which show the condition of the unit.
Wiring
The wiring of the BGU-E(PS) call point isolator should be made as follows:
Open the unit by sliding back the keyhole cover (see fig 1) and using the key
!
(supplied).
The front plate can be removed by pressing the two releasing clips on the left-
hand side (see fig 3) and lifting off.
Locate the terminal block within the unit, which is in the top right-hand corner
!
of the casing (see fig 3).
Make a hole through the cable glands either at the top or at the bottom of the
!
unit (see fig 3) and pass the loop cabling through.
Connect loop wiring using the screw connectors - refer to fig 3 below and
!
wiring descriptions on PCB.
Replace front plate by relocating the right hand side clips into the PCB and
!
pushing the plate forward until it clicks into place.
Ensure alarm button has NOT been depressed during wiring. Use the reset
!
lever (see fig 3) by pulling to the left to correct this if needed.
If using the unit as a splash-proof call point, the supplied rubber gasket MUST
!
be fitted. To fit the gasket, carefully remove glass by releasing the glass-
retaining clip and lifting out. Fit gasket as shown in fig 2. Replace glass
ensuring glass-retaining clip engages.
Close unit casing.
!
Fig 3 - Wiring Diagram (representation only)
Addressing
The BGU-E(PS) can be addressed using the Hand Held Programmer
(TCH-B100 ) and using a programming lead (PL-3). Note, the UNIT cannot be
addressed if loop voltage is present.
Open the unit by sliding back the keyhole cover and using the supplied key.
!
Locate the Programming Connector Socket within the unit, which is on the left-hand side of the main PCB
!
(see fig 3). Insert the rectangular connector plug of the programming lead into this socket and the jack
plug into the jack socket on the TCH-B100 (this is a polarised socket).
Programming of the unit cannot be carried out if the alarm button is depressed. This can be reset by
!
pulling the reset lever (see fig 3 above) to the left until the alarm button pops up.
Program the analogue address in the usual way.
!
Unplug the lead and close unit casing, sliding the keyhole cover back into position
!
1
Fig 1 - door closed
Fig 2 – inside door
showing gasket fitted
Fig 3 - door open
2-3-0-427/ISS2/SEPT05

Werbung

loading

Inhaltszusammenfassung für Hochiki BGU-E

  • Seite 1 Indicators (SI), which show the condition of the unit. Wiring The wiring of the BGU-E(PS) call point isolator should be made as follows: Open the unit by sliding back the keyhole cover (see fig 1) and using the key (supplied).
  • Seite 2 BGU-E(PS)* Sleep mode current 100 µA (typ.) Quiescent mode current 250 µA (typ.) Current - BGU-E(PS) operated (fire condition) 620 µA (typ. without Fire LED on) Current drawn by isolator during fault condition Maximum continuous current Maximum quantity per loop...
  • Seite 3 Abb. 3 – Schaltplan (nur repräsentativ) Adressierung Die BGU-E(PS) kann mit dem Handprogrammierer (TCH-B100 ) und einer Abb. 2 – Tür offen Programmierleitung (PL-3) adressiert werden. Hinweis, die Anlage kann bei Vorhandensein von Schleifenspannung nicht adressiert werden. Öffnen Sie die Anlage durch Zurückschieben der Schlüssellochabdeckung und mit Hilfe des beiliegenden Schlüssels.
  • Seite 4 Maximale Schleifenanzahl ist beim Hersteller der Feuermelder-Schalttafel zu erfragen. Ersatzteile Zugangsschlüssel - Teile-Nr. 1470040-00, Ersatzglas - Teile-Nr. 1470050-00 Hochiki Europe (UK) Ltd. reserves the right to Hochiki Europe (UK) Ltd alter the specification of its products from time Grosvenor Road, Gillingham Business Park, to time without notice.

Diese Anleitung auch für:

Bgu-eps