2.4 Operation Method
The iS5 has several operation methods as shown below.
Operation Method
Operation using Keypad
Operation using
Control Terminals
Operation using both
Keypad and Control
Terminals
Operation using
Option Board
All manuals and user guides at all-guides.com
Function
Run/Stop command and frequency are set only through the
keypad.
Closing FX or RX terminal performs Run/Stop.
Frequency reference is set through V1 or I or V1+I terminal.
Run/Stop is performed by the keypad.
Frequency reference is set through the V1 or I or V1+I
terminal.
Closing FX or RX terminal performs Run/Stop.
Frequency reference is set through the keypad.
Operation using option board.
The iS5 has five option boards and three sub-boards.
Option Boards: RS485, Device-Net, F-Net, ProfiBus and
ModBus
Sub-Boards: Sub-A Board, Sub-B Board and Sub-C Board
(Please refer to
'Chapter 6 - Options'
for more information.)
25
Chapter 2 - Operation
Function Setting
DRV 03: Keypad
DRV 04: Keypad-1 or -2
DRV 03: Fx/Rx-1 or -2
DRV 04: V1 or I or V1+I
DRV 03: Keypad-1 or -2
DRV 04: V1 or I or V1+I
DRV 03: Fx/Rx-1 or -2
DRV 04: Keypad-1 or -2