Herunterladen Inhalt Inhalt Diese Seite drucken

Electric Wiring; General Check - Hitachi UTOPIA IVX PREMIUM Serie Bedienungsanleitung

Vorschau ausblenden Andere Handbücher für UTOPIA IVX PREMIUM Serie:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 47

ELECTRIC WIRING

10 ELECTRIC WIRING

10.1 GENERAL CHECK

1 Ensure that the field-supplied electrical components (mains
power switches, circuit breakers, wires, connectors and wire
terminals) have been properly selected according to the
electrical data indicated. Make sure that they comply with
national and regional electrical codes.
2 Following the Council Directive 2004/108/EC(89/336/EEC),
relating to electromagnetic compatibility, next table indicates:
Maximum permissible system impedance Z
interface point of the user's supply, in accordance with
EN61000-3-11
MODEL
Z
(Ω)
max
RAS-12HNP
-
3 Harmonics situation of each model regarding IEC 61000-3-2
and IEC 61000-3-12 is as follows:
MODELS SITUATION REGARDING IEC
61000-3-2 AND IEC 61000-3-12 Ssc "xx"
Installation restrictions may be applied by
supply authorities in relation to harmonics
4 Check to ensure that the power supply voltage is within +/-
10% of the rated voltage.
5 Check to ensure that power supply has an impedance low
enough to warranty not reduce the starting voltage more
than 85% of the rated voltage.
6 Check to ensure that the ground wire is connected.
7 Connect a fuse of specified capacity.
10.2 ELECTRICAL WIRING CONNECTION FOR OUTDOOR UNITS

The electrical wiring connection for the outdoor unit is shown in figure below
RAS-12HN(P/C)
Earth Wire
Control line
Table for Terminal Connection between units
13
PMML0397B rev.0 - 11/2015 - P5416650
at the
max
MODEL
Z
(Ω)
max
RAS-12HNC
-
MODELS
RAS-12HN(P/C)
Power supply
?
N O T E
Check and test to ensure that if there is more than one source of power
supply, that all are turned OFF.
!
C A U T I O N
Check to ensure that screws for terminal block are tightly tightened.
Check to ensure that the indoor fan and the outdoor fan have stopped
before electrical wiring work or periodical check is performed.
Protect the wires, drain pipe, electrical parts, from rats or other small
animals. If not protected, rats may damage unprotected parts, and at
the worst, a fire will occur.
Wrap the accessory packing around the wires, and plug the wiring
connection hole with the seal material to protect the product from any
condensed water and insects.
Tightly secure the wires with the cord clamp inside the indoor unit.
Lead the wires through the knockout hole in the side cover when
using conduit.
Secure the cable of the remote control switch with the cord clamp
inside the electrical box.
Electrical wiring must comply with national and local codes. Contact
your local authority in regards to standards, rules, regulations, etc.
Check that the ground wire is securely connected.
Connect a fuse of specified capacity.
!
D A N G E R
Do not connect of adjust any wiring or connections unless the
main power switch is OFF.
Check that the earth wire is securely connected, tagged and
locked in accordance with national and local codes.
Wiring
System
Power Supply
DC inverter
Operating
DC inverter
Remote Control DC inverter
O.U.: Outdoor Unit; I.U.: Indoor unit
Units type
Connection of terminals
O.U. to O.U.
L1 to L1, L2 to L2, L3 to L3, N to N
I.U. to I.U.
L1 to L1, N to N
O.U. to I.U. or I.U. toI.U.
1 to1, 2 to 2
I.U. to I.U.
A to A, B to B

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Utopia ivx standard serieRas-12hnpRas-12hnc

Inhaltsverzeichnis