7

Technical Specifications

7.1

Scope of Delivery

Siemens Building Technologies
Fire Safety & Security Products
Housing
Colour: Casing cover
Casing base
Dimensions in mm (w x h x d)
Weight
Protection rating
Power supply
Power consumption
Temperature range
Relative humidity
Antenna
Operating frequency
Transmitting power
Transponder
Connecting cable
Transducer
Interfaces
Digital Inputs
1 x casing cover
1 x casing base complete with electronics
1 x accessory bag (screws)
1 x installation instructions
1 x repair form
Technical Specifications
Synthetic ABS / PBT (electronics cast)
Similar to RAL 9006 (white aluminium)
black
120 x 76 x 17
Approx. 160 g
IP 65
9 V - 15 V DC
Max. 2.6 W
-25 °C to +60 °C
95% (no dew formation)
Integrated
13.56 MHz
200 mW ± 2 dB
ISO14443A:
Mifare Standard 1k und 4k,
Mifare Ultra-Light,
Mifare DESfire
my-D proximity
ISO14443B:
My-C (SLE66CL160S)
ISO15683:
my-D vicinity, I-Code SLI, TagIT HFI,
STM LRI512
50 cm LiYY 12x0,2 mm
1 x LED red, 1 x LED green
1 x buzzer
Clock / Data emulation from:
Magnetic card (ISO7811-2, 5 bit)
Wiegand
RS232-TTL, Magnetic card
4 inputs
2
/ AWG24
25
12.2005