Wiring For Remote Trip Facility - ABB F2 63A 230V CM4 Montageanleitung

Automatik-fernantrieb
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

4.1. Wiring for Remote Trip Facility

If the remote trip function is required for an actuated RCCB, the RCCB should be electrically linked to
the F2 ... 230V CM4 as follows. The remote trip facility is possible for RCCBs with a nominal residual
current of I
= 500 mA even without a resistor in the connection line
∆n
Remote actuator F2 ... 230V CM4
Terminal 15 (phase Lx)
Terminal 16 (neutral N)
!
The maximum permissible voltage across terminals 15 and 16 may not exceed 250 V
loads or sockets connected via the RCCB must be equipped with the enclosed labels "Warning!
Mains voltage is automatically connected".
Output
4-pole RCCB
F204
Terminal 4, 6 or 8
Terminal N (upper)
DE
EN
F204 with N on the right
Terminal 2, 4 or 6
Terminal N (upper)
AC
DE
. The
EN
23